| Complementary |
| Motor power kW | 15 kW at 220/230 V AC 50/60 Hz (AC-3); 22 kW at 380/400 V AC 50/60 Hz (AC-3); 25 kW at 415 V AC 50/60 Hz (AC-3); 30 kW at 440 V AC 50/60 Hz (AC-3); 30 kW at 500 V AC 50/60 Hz (AC-3); 33 kW at 660/690 V AC 50/60 Hz (AC-3); 15 kW at 220/230 V AC 50/60 Hz (AC-3e); 22 kW at 380/400 V AC 50/60 Hz (AC-3e); 25 kW at 415 V AC 50/60 Hz (AC-3e); 30 kW at 440 V AC 50/60 Hz (AC-3e); 30 kW at 500 V AC 50/60 Hz (AC-3e); 33 kW at 660/690 V AC 50/60 Hz (AC-3e); 11 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power hp | 3 hp at 115 V AC 50/60 Hz for 1 phase motors; 7.5 hp at 230/240 V AC 50/60 Hz for 1 phase motors; 15 hp at 200/208 V AC 50/60 Hz for 3 phases motors; 15 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 40 hp at 460/480 V AC 50/60 Hz for 3 phases motors; 40 hp at 575/600 V AC 50/60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit; 80 A (at 60 °C) for power circuit |
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 900 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 900 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 400 A 40 °C - 10 s for power circuit; 810 A 40 °C - 1 s for power circuit; 84 A 40 °C - 10 min for power circuit; 208 A 40 °C - 1 min for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 100 A gG at |
| Average impedance | 1.5 mOhm - Ith 80 A 50 Hz for power circuit |
| Power dissipation per pole | 3.7 W AC-3; 9.6 W AC-1; 3.7 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified; Power circuit: 690 V conforming to IEC 60947-4-1 |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 6 Mcycles |
| Electrical durability | 1.45 Mcycles 50 A AC-3 at Ue |
| Control circuit type | AC at 50/60 Hz standard |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz |
| Inrush power in VA | 140 VA 60 Hz cos phi 0.75 (at 20 °C); 160 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Hold-in power consumption in VA | 13 VA 60 Hz cos phi 0.3 (at 20 °C); 15 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 4…5 W at 50/60 Hz |
| Operating time | 4...19 ms opening; 12...26 ms closing |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Plate; Rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; CSA C22.2 No 14; UL 60947-4-1; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; IEC 60335-1:Clause 30.2 |
| Product certifications | CCC; UL; CB Scheme; CSA; CE; UKCA; Marine; EAC |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor open (10 Gn for 11 ms) |
| Height | 122 mm |
| Width | 55 mm |
| Depth | 120 mm |
| Net weight | 0.855 kg |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range | TeSys; TeSys Deca |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Motor control; Resistive load |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 50 A (at |
| [Uc] control circuit voltage | 230 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.200 cm |
| Package 1 Width | 13.500 cm |
| Package 1 Length | 15.500 cm |
| Package 1 Weight | 918.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 10 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 9.654 kg |
The LC1D50AP7 contactor from the TeSys Deca series by Schneider Electric is a 3-pole contactor for motor control and operation of resistive loads. It has a rated operational current of 50 A at AC-3 and is designed for a control circuit voltage of 230 V AC 50/60 Hz. The device is suitable for use in various application categories, including AC-1, AC-3, AC-3e, and AC-4, supporting a motor power of 22 kW at 400 V AC-3. The additional auxiliary contacts consist of one close contact and one open contact, making it suitable for applications requiring signal transmission or feedback.
Applications
This contactor is designed for controlling electric motors in industrial installations, particularly in drive technology, conveyor systems, and machine building. The AC-3e category enables use with motors having high starting currents, while AC-4 is intended for frequent switching operations under high mechanical stress. Certifications according to UL, CSA, CCC, GOST, GL, BV, RINA, LROS, and DNV also make it suitable for use in marine and international installations.
Functions and Equipment in Detail
The device features a safety cover that enables mechanical interlocking of contacts. The contacts are mechanically coupled and equipped with mirror contacts, ensuring a secure and reliable switching function even in safety-critical applications. Electrical connections are made via Everlink and spring terminals, enabling quick and secure installation. The coil is designed without an integrated wiring module, allowing easy integration into existing circuits.
Technology Explained Simply
The rated insulation voltage is 690 V for the current circuit according to IEC standards, with an impulse voltage withstand of 6 kV. The overvoltage category III and pollution degree 3 indicate suitability for industrial environments with increased electrical stress and contamination risk. The rated breaking capacity of 900 A at 440 V meets IEC standard requirements. The mechanical life is 6 million switching cycles, and the electrical life is 1.45 million switching cycles at 50 A AC-3 and rated voltage.
Compatibility and Accessories
The contactor is compatible with various accessories, including auxiliary switch blocks such as LADN40, LADN20, LADN02, LADN11, LADN31, and LAD8N11, which provide additional close and open contacts. Time modules such as LA4DT4U, LA4-DT0U, and LA4-DT2U enable integration of time delays. Interlocking blocks such as LAD6K10M and mechanical interlocks such as LAD4CM support safe control of multiple contactors. Motor protection circuit breakers such as GV3P50 and relays such as LRD350 can be used to extend protection functions.
Mounting and Installation
Mounting is done via screw connection or spring terminals, with dimensions of 55 mm (width) × 122 mm (height) × 120 mm (depth). The mounting height is designed for standard control panels. The control circuit voltage of 230 V AC 50/60 Hz requires a corresponding supply. The operating voltage range is between 0.8 and 1.1 times the rated voltage at 50 Hz and 0.85 to 1.1 times the rated voltage at 60 Hz, with a drop voltage between 0.3 and 0.6 times the rated voltage.
Operational Advantages
The use of Everlink and spring terminals ensures a reliable and long-lasting electrical connection. Mechanical interlocking and mirror contacts increase safety in critical applications. The high service life and certifications for international standards enable use in various industries and regions. Compatibility with various accessories extends the functionality of the contactor without requiring modifications to the device.