| Complementary |
| Motor power kW | 15 kW at 220/230 V AC 50/60 Hz (AC-3); 22 kW at 380/400 V AC 50/60 Hz (AC-3); 25 kW at 415 V AC 50/60 Hz (AC-3); 30 kW at 440 V AC 50/60 Hz (AC-3); 30 kW at 500 V AC 50/60 Hz (AC-3); 33 kW at 660/690 V AC 50/60 Hz (AC-3); 15 kW at 220/230 V AC 50/60 Hz (AC-3e); 22 kW at 380/400 V AC 50/60 Hz (AC-3e); 25 kW at 415 V AC 50/60 Hz (AC-3e); 30 kW at 440 V AC 50/60 Hz (AC-3e); 30 kW at 500 V AC 50/60 Hz (AC-3e); 33 kW at 660/690 V AC 50/60 Hz (AC-3e); 11 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power hp | 3 hp at 115 V AC 50/60 Hz for 1 phase motors; 7.5 hp at 230/240 V AC 50/60 Hz for 1 phase motors; 15 hp at 200/208 V AC 50/60 Hz for 3 phases motors; 15 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 40 hp at 460/480 V AC 50/60 Hz for 3 phases motors; 40 hp at 575/600 V AC 50/60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit; 80 A (at 60 °C) for power circuit |
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 900 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 900 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 400 A 40 °C - 10 s for power circuit; 810 A 40 °C - 1 s for power circuit; 84 A 40 °C - 10 min for power circuit; 208 A 40 °C - 1 min for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 100 A gG at |
| Average impedance | 1.5 mOhm - Ith 80 A 50 Hz for power circuit |
| Power dissipation per pole | 3.7 W AC-3; 9.6 W AC-1; 3.7 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified; Power circuit: 690 V conforming to IEC 60947-4-1 |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 6 Mcycles |
| Electrical durability | 1.45 Mcycles 50 A AC-3 at Ue |
| Control circuit type | AC at 50/60 Hz |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz |
| Inrush power in VA | 140 VA 60 Hz cos phi 0.75 (at 20 °C); 160 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Hold-in power consumption in VA | 13 VA 60 Hz cos phi 0.3 (at 20 °C); 15 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 4…5 W at 50/60 Hz |
| Operating time | 4...19 ms opening; 12...26 ms closing |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Connections - terminals | Control circuit: lugs-ring terminals - external diameter: 8 mm; Power circuit: lugs-ring terminals - external diameter: 16.5 mm |
| Tightening torque | Control circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M3.5; Control circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5; Power circuit: 6 N.m - on lugs-ring terminals hexagonal screw head 10 mm M6; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2; Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Rail; Plate |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; CSA C22.2 No 14; UL 60947-4-1; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; IEC 60335-1:Clause 30.2 |
| Product certifications | CCC; UL; CB Scheme; CSA; CE; UKCA; Marine; EAC |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor open (10 Gn for 11 ms) |
| Height | 122 mm |
| Width | 55 mm |
| Depth | 120 mm |
| Net weight | 0.855 kg |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys; TeSys Deca |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load; Motor control |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 50 A (at |
| [Uc] control circuit voltage | 110 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.0 cm |
| Package 1 Width | 14.0 cm |
| Package 1 Length | 15.0 cm |
| Package 1 Weight | 850.0 g |
The LC1D50A6F7 contactor from the TeSys Deca series by Schneider Electric is a 3-pole contactor for controlling electrical loads, particularly for motor drives and resistive loads. It features a rated operational current of 50 A and is designed for use categories AC-1, AC-3, AC-3e, and AC-4, supporting a motor power of 22 kW at 400 V AC-3. The control circuit voltage is 110 V AC at 50/60 Hz. The device is equipped with an additional auxiliary contact arrangement consisting of one normally closed (NC) and one normally open (NO) contact, making it suitable for complex control logic. The contacts are mechanically coupled and feature mirror contacts, enhancing suitability for safety applications.
Applications
This contactor is designed for use in industrial plants where reliable and safe switching functions for motors and resistive loads are required. It is used in manufacturing plants, process engineering, and machine building, where high switching cycles and mechanical stresses occur. The use categories AC-3 and AC-3e make it particularly suitable for operating three-phase motors, while AC-4 is intended for applications with high inrush currents, such as crane systems or presses.
Functions and Equipment in Detail
The device features coil technology without an integrated wiring module, enabling simple mounting and maintenance. The contacts are equipped with Everlink technology and spring terminals, ensuring a secure and long-lasting electrical connection. The auxiliary contacts are instantaneous and allow integration into control and monitoring systems. The mechanical life expectancy is 6 million switching cycles, while the electrical life expectancy at 50 A AC-3 is 1.45 million switching cycles. The rated insulation voltage for the circuit is 690 V according to IEC 60947-4-1, and the impulse voltage withstand is 6 kV.
Technology Explained Simply
The contactor coil is supplied with 110 V AC, enabling magnetic attraction of the contacts once the control circuit is activated. The operating voltage variation ranges from 0.8 to 1.1 times the nominal voltage at temperatures from -40 to 60 °C, ensuring stable performance under variable conditions. The pickup power is 160 VA at 50 Hz, and the holding power is 15 VA. The rated breaking capacity is 900 A at 440 V, highlighting the contactor’s ability to safely interrupt short-circuit currents. The overvoltage category III and pollution degree 3 indicate suitability for industrial environments with high electrical and mechanical stresses.
Compatibility and Accessories
The contactor is compatible with various accessories, including auxiliary switch blocks such as LADN316 (3NO1NC), LADN046 (4NC), LAD8N206 (2NO), and LADN226 (2NO2NC), enabling expansion of control functions. Additionally, time delay blocks such as LADT26 (delayed pickup) or LADT46 (delayed release) and wiring modules such as LAD4RC3G or RC element LAD4RC3U can be integrated. For motor protection, the GV3L50 motor protection switch 3p 50A is suitable. The mechanical interlock LAD4CM enables safe combination with other contactors.
Mounting and Installation
The contactor is designed for mounting on a 35 mm DIN rail (EN 50022) and can be screwed onto metal plates, especially in applications with vibrations exceeding 3g. Dimensions are 55 mm (width) × 122 mm (height) × 120 mm (depth), and the net weight is 0.855 kg. Cable connections are made via Everlink spring terminals, ensuring a secure connection even under high switching cycles. Installation is performed by simply clipping the device onto the rail and wiring the main and auxiliary contacts.
Operational Advantages
The contactor offers high reliability through mechanically coupled contacts and mirror contacts, ensuring safe switching functions even in critical applications. The Everlink technology ensures a long-lasting and maintenance-friendly electrical connection. The high life expectancy and suitability for various use categories make it a universally applicable component in industrial electrical engineering. Certifications according to GOST, DNV, RINA, CSA, CCC, UL, LROS, BV, and GL underscore the international acceptance and safety of the product.