Schneider Electric LC1D40AMD, EAN: 3389119408530

Schneider Electric LC1D40AMD contactor 3p 40A

Industrial Material > Industrial relays and contactors > Contactors

Schneider Electric LC1D40AMD contactor 3p 40A

Lieske Part No. 636846
Mfg Part No LC1D40AMD
EAN-Code 3389119408530
Manufacturer Schneider Electric
Here only 303,05 EUR
360,63 EUR incl. VAT

Further information for Schneider Electric LC1D40AMD contactor 3p 40A

Complementary
Motor power kW11 kW at 220/230 V AC 50/60 Hz (AC-3); 18.5 kW at 380/400 V AC 50/60 Hz (AC-3); 22 kW at 415/440 V AC 50/60 Hz (AC-3); 22 kW at 500 V AC 50/60 Hz (AC-3); 30 kW at 660/690 V AC 50/60 Hz (AC-3); 9 kW at 400 V AC 50/60 Hz (AC-4)
Motor power hp5 hp at 230/240 V AC 50/60 Hz for 1 phase motors; 10 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 30 hp at 575/600 V AC 50/60 Hz for 3 phases motors; 10 hp at 200/208 V AC 50/60 Hz for 3 phases motors; 3 hp at 115 V AC 50/60 Hz for 1 phase motors; 30 hp at 460/480 V AC 50/60 Hz for 3 phases motors
Compatibility codeLC1D
Pole contact composition3 NO
Protective coverWith
[Ith] conventional free air thermal current10 A (at 60 °C) for signalling circuit; 60 A (at 60 °C) for power circuit
Irms rated making capacity140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 800 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity800 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current320 A 40 °C - 10 s for power circuit; 720 A 40 °C - 1 s for power circuit; 72 A 40 °C - 10 min for power circuit; 165 A 40 °C - 1 min for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit
Associated fuse rating10 A gG for signalling circuit conforming to IEC 60947-5-1; 80 A gG at
Average impedance1.5 mOhm - Ith 60 A 50 Hz for power circuit
Power dissipation per pole2.4 W AC-3; 5.4 W AC-1
[Ui] rated insulation voltagePower circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified; Power circuit: 690 V conforming to IEC 60947-4-1
Overvoltage categoryIII
Pollution degree3
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947
Safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability10 Mcycles
Electrical durability0.7 Mcycles 60 A AC-1 at Ue
Control circuit typeDC standard
Coil technologyBuilt-in bidirectional peak limiting diode suppressor
Control circuit voltage limits0.1...0.3 Uc (-40…70 °C):drop-out DC; 0.75...1.25 Uc (-40…60 °C):operational DC; 1...1.25 Uc (60…70 °C):operational DC
Inrush power in W19 W (at 20 °C)
Hold-in power consumption in W7.4 W at 20 °C
Operating time50 ±15 % ms closing; 20 ±20 % ms opening
Time constant34 ms
Maximum operating rate3600 cyc/h at 60 °C
Auxiliary contact composition1 NO + 1 NC
Auxiliary contacts typetype mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency25...400 Hz
Minimum switching voltage17 V for signalling circuit
Minimum switching current5 mA for signalling circuit
Insulation resistance> 10 MOhm for signalling circuit
Non-overlap time1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact
Mounting supportRail; Plate
Contractual warranty
Warranty (in months)18
Environment
StandardsEN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; CSA C22.2 No 14; UL 60947-4-1; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; IEC 60335-1:Clause 30.2
Product certificationsCCC; UL; CB Scheme; CSA; CE; UKCA; Marine; EAC
IP degree of protectionIP20 front face conforming to IEC 60529
Protective treatmentTH conforming to IEC 60068-2-30
Climatic withstandconforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat
Permissible ambient air temperature around the device-40…60 °C; 60…70 °C with derating
Operating altitude0...3000 m
Fire resistance850 °C conforming to IEC 60695-2-1
Mechanical robustnessVibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor open (10 Gn for 11 ms)
Height122 mm
Width55 mm
Depth120 mm
Net weight0.925 kg
Logistical informations
Country of originFR
Main
RangeTeSys; TeSys Deca
Range of productTeSys Deca Advanced
Product or component typeContactor
Device short nameLC1D
Contactor applicationMotor control; Resistive load
Utilisation categoryAC-3; AC-1; AC-4
Poles description3P
[Ue] rated operational voltagePower circuit:
[Ie] rated operational current60 A (at
[Uc] control circuit voltage220 V DC
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height6.2 cm
Package 1 Width13.7 cm
Package 1 Length15.2 cm
Package 1 Weight996.0 g
Unit Type of Package 2S02
Number of Units in Package 210
Package 2 Height15.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight10.128 kg
Leistungsschütz TeSys LC1D. 3 polig, 3 Schließer. Zusätzliche Hilfskontakte- 1 Schließer + 1 Öffner, Bemessungsbetriebsleistung bei AC-3, 400 V 18.5 kW, Bemessungsbetriebsstrom Ie bei AC-3, 400 V 40 A, Spule 220 V DC. Abmessung (BxHxT) 55x122x120 mm, Gewicht 0,925 kg. Kategorie AC-3, AC-1, AC-4. integrierte bidirektionale Amplitudenbegrenzerdiode. Schnelle und einfache Einrichtung. Sichere und langlebige Stromverbindung mit Everlink und Federklemmen. Geeignet für Sicherheitsanwendungen durch mechanisch gekoppelte Kontakte und Spiegelkontakte. Zertifizierungen nach CSA, UL, CCC, GOST. Produktstandards gem.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/636846
qrcode für Schneider Electric LC1D40AMD contactor 3p 40A