| Complementary |
| Compatibility code | LC1D |
| Pole contact composition | 2 NO + 2 NC |
| Protective cover | With |
| [Ith] conventional free air thermal current | 60 A (at 60 °C) for power circuit |
| Irms rated making capacity | 800 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 800 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 320 A 40 °C - 10 s for power circuit; 720 A 40 °C - 1 s for power circuit; 72 A 40 °C - 10 min for power circuit; 165 A 40 °C - 1 min for power circuit |
| Associated fuse rating | 80 A gG at |
| Average impedance | 1.5 mOhm - Ith 60 A 50 Hz for power circuit |
| Power dissipation per pole | 5.4 W AC-1 |
| [Ui] rated insulation voltage | Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Power circuit: 690 V conforming to IEC 60947-4-1 |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 6 Mcycles |
| Electrical durability | 1.4 Mcycles 60 A AC-1 at Ue |
| Control circuit type | AC at 50/60 Hz |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz |
| Inrush power in VA | 140 VA 60 Hz cos phi 0.75 (at 20 °C); 160 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Hold-in power consumption in VA | 13 VA 60 Hz cos phi 0.3 (at 20 °C); 15 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 4…5 W at 50/60 Hz |
| Operating time | 4...19 ms opening; 12...26 ms closing |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Tightening torque | Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2; Power circuit: 8 N.m - on screw clamp terminals - cable 25…35 mm² hexagonal screw head 4 mm; Power circuit: 5 N.m - on screw clamp terminals - cable 1…25 mm² hexagonal screw head 4 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 |
| Mounting support | Plate; Rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1 |
| Product certifications | GL; LROS (Lloyds register of shipping); GOST; UL; DNV; RINA; CSA; CCC; BV |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Shocks contactor open (8 Gn for 11 ms) ; Shocks contactor closed (10 Gn for 11 ms) ; Vibrations contactor opened (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) |
| Height | 127 mm |
| Width | 85 mm |
| Depth | 125 mm |
| Net weight | 1.44 kg |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load |
| Utilisation category | AC-1 |
| Poles description | 4P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 60 A (at |
| [Uc] control circuit voltage | 110 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 15.200 cm |
| Package 1 Width | 11.200 cm |
| Package 1 Length | 13.200 cm |
| Package 1 Weight | 1.454 kg |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 5 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 7.645 kg |
TeSys LC1D power contactor. 4-pole, 2 NO + 2 NC. Coil 110 V AC. Dimensions (WxHxD) 85x127x125 mm, weight 1.44 kg. Category AC-1. Without integrated circuit module. Quick and easy setup. Safe and durable power connection with Everlink and spring terminals. Suitable for safety applications due to mechanically coupled contacts and mirror contacts. Certifications according to GL, LROS (Lloyds register of shipping), GOST, UL, DNV, RINA, CSA, CCC, BV. Product standards in accordance with.