| Complementary |
| Motor power kW | 9 kW at 220/230 V AC 50/60 Hz (AC-3); 18.5 kW at 380/400 V AC 50/60 Hz (AC-3); 18.5 kW at 415/440 V AC 50/60 Hz (AC-3); 18.5 kW at 500 V AC 50/60 Hz (AC-3); 18.5 kW at 660/690 V AC 50/60 Hz (AC-3); 9 kW at 220/230 V AC 50/60 Hz (AC-3e); 18.5 kW at 380/400 V AC 50/60 Hz (AC-3e); 18.5 kW at 415/440 V AC 50/60 Hz (AC-3e); 18.5 kW at 500 V AC 50/60 Hz (AC-3e); 18.5 kW at 660/690 V AC 50/60 Hz (AC-3e); 7.5 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power hp | 10 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 10 hp at 200/208 V AC 50/60 Hz for 3 phases motors; 5 hp at 240 V AC 50/60 Hz for 1 phase motors; 20 hp at 480 V AC 50/60 Hz for 3 phases motors; 25 hp at 600 V AC 50/60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit; 50 A (at 60 °C) for power circuit |
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 550 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 550 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 60 A 40 °C - 10 min for power circuit; 430 A 40 °C - 1 s for power circuit; 150 A 40 °C - 1 min for power circuit; 310 A 40 °C - 10 s for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 63 A gG at |
| Average impedance | 2 mOhm - Ith 50 A 50 Hz for power circuit |
| Power dissipation per pole | 5 W AC-1; 3 W AC-3; 3 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified; Power circuit: 690 V conforming to IEC 60947-4-1 |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 30 Mcycles |
| Electrical durability | 1.4 Mcycles 50 A AC-1 at Ue |
| Control circuit type | DC standard |
| Coil technology | Built-in bidirectional peak limiting diode suppressor |
| Control circuit voltage limits | 0.1...0.25 Uc (-40…70 °C):drop-out DC; 0.7...1.25 Uc (-40…60 °C):operational DC; 1...1.25 Uc (60…70 °C):operational DC |
| Inrush power in W | 5.4 W (at 20 °C) |
| Hold-in power consumption in W | 5.4 W at 20 °C |
| Operating time | 20 ±20 % ms opening; 63 ±15 % ms closing |
| Time constant | 28 ms |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Plate; Rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; CSA C22.2 No 60947-4-1 |
| Product certifications | UL; CCC; CSA; Marine; UKCA; EAC; CB Scheme |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor open (8 Gn for 11 ms) |
| Height | 85 mm |
| Width | 45 mm |
| Depth | 101 mm |
| Net weight | 0.54 kg |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys; TeSys Deca |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load; Motor control |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 50 A (at |
| [Uc] control circuit voltage | 24 V DC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.000 cm |
| Package 1 Width | 9.000 cm |
| Package 1 Length | 11.000 cm |
| Package 1 Weight | 590.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 15 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 9.035 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 240 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 152.500 kg |
The LC1D38BD contactor from the TeSys Deca series by Schneider Electric is a 3-pole contactor for controlling electrical loads, particularly for motor drives and resistive loads. It features three main contacts (3S) and integrated auxiliary contacts in the configuration of 1 NO + 1 NC, suitable for controlling auxiliary functions such as signal indication or feedback to control devices. The control circuit voltage is 24 V DC, making it particularly suitable for applications with DC power supply in industrial environments. The device is designed for usage categories AC-1, AC-3, AC-3e, and AC-4, with category AC-3 representing the typical application for motor control.
Applications
The contactor is designed for controlling motors with a rated power of up to 18.5 kW at 380/400 V AC 50/60 Hz (AC-3). At other voltages and frequencies, the permissible motor powers vary accordingly, for example, achieving 9 kW (AC-3) at 220/230 V AC 50/60 Hz. Category AC-4, which applies to frequent and short-duration switching operations, enables control of motors with 7.5 kW at 400 V AC 50/60 Hz. The application areas thus include industrial drive technology, such as conveyor systems, pumps, fans, and machine tools, where reliable and safe switching functions are required.
Functions and Equipment in Detail
The contactor features an integrated bidirectional amplitude limiter diode, acting as a transient voltage suppressor, which protects the coil from transient voltage spikes. This increases the coil's lifespan and reduces electromagnetic emissions in the network. The contacts are mechanically linked and feature mirror contacts, enhancing reliability in safety applications by ensuring a mechanical connection between the contacts. The main current connection is made via Everlink technology with spring terminals, enabling a secure and long-lasting connection and accelerating installation.
Technology Explained Simply
The rated operational current is 50 A at an ambient temperature of 60 °C for the current circuit, while the rated operational current Ie for AC-3 at 400 V AC is 38 A. The rated insulation voltage is 690 V for the current circuit according to IEC 60947-4-1 and 600 V for the signal circuit according to IEC 60947-1. The overvoltage category III and pollution degree 3 indicate that the device is designed for industrial environments with increased pollution risk and transient voltage surges. The rated impulse withstand voltage is 6 kV, ensuring electrical strength under transient conditions.
Compatibility and Accessories
The contactor is compatible with various accessories that extend its functionality. These include auxiliary switch blocks such as LADN31 (3S1Ö) or LADN11 (1S1Ö), time delay blocks such as LADR0 (delayed release 0.10–3.00 s) or LADT4 (delayed pickup 10.00–180.00 s), and motor protection circuit breakers such as GV3L40 or GV3P40. For special applications, special diodes such as LAD4TBDL (24 VDC) or mechanical interlocks such as LAD9V2 are also available. Using these accessories allows adaptation to specific requirements such as time delays, additional signals, or mechanical interlocks.
Mounting and Installation
Mounting is done via screw terminals with a tightening torque of 1.7 Nm, ensuring a secure connection. The dimensions are 45 mm (width) × 85 mm (height) × 101 mm (depth), allowing integration into standard control panels with DIN dimensions. The maximum operating rate is 3600 switching operations per hour at 60 °C, enabling high load capacity in continuously operated systems. The operating time is 20 ±20 % ms for opening and 63 ±15 % ms for closing, ensuring a fast response to control signals.
Advantages in Operation
The mechanical life is 30 million switching cycles, and the electrical life is 1.4 million cycles at 50 A AC-1. The power loss per pole is 5 W (AC-1) and 3 W (AC-3/AC-3e), indicating efficient heat generation and low energy losses. The integrated safety cover increases operational safety and protects against accidental contact with the contacts. Certifications according to RINA, GOST, CSA, BV, DNV, LROS, UL, CCC, and GL confirm compliance with international safety and quality standards, enabling use in global applications. The coil consumes 5.4 W for both pull-in and holding power at 20 °C, ensuring efficient power supply.