| Complementary |
| Motor power kW | 9 kW at 220/230 V AC 50/60 Hz (AC-3); 18.5 kW at 380/400 V AC 50/60 Hz (AC-3); 18.5 kW at 415/440 V AC 50/60 Hz (AC-3); 18.5 kW at 500 V AC 50/60 Hz (AC-3); 18.5 kW at 660/690 V AC 50/60 Hz (AC-3); 9 kW at 220/230 V AC 50/60 Hz (AC-3e); 18.5 kW at 380/400 V AC 50/60 Hz (AC-3e); 18.5 kW at 415/440 V AC 50/60 Hz (AC-3e); 18.5 kW at 500 V AC 50/60 Hz (AC-3e); 18.5 kW at 660/690 V AC 50/60 Hz (AC-3e); 7.5 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power hp | 2 hp at 115 V AC 60 Hz for 1 phase motors; 5 hp at 230/240 V AC 60 Hz for 1 phase motors; 10 hp at 200/208 V AC 60 Hz for 3 phases motors; 10 hp at 230/240 V AC 60 Hz for 3 phases motors; 20 hp at 460/480 V AC 60 Hz for 3 phases motors; 25 hp at 575/600 V AC 60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for control circuit; 50 A (at 60 °C) for power circuit |
| Irms rated making capacity | 250 A DC for control circuit conforming to IEC 60947-5-1; 550 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 550 A at 440 V for power circuit conforming to IEC 60947 |
| Associated fuse rating | 10 A gG for control circuit conforming to IEC 60947-5-1; 63 A at |
| Average impedance | 2 mOhm - Ith 50 A 50 Hz for power circuit |
| Power dissipation per pole | 3 W AC-3; 5 W AC-1; 3 W AC-3e |
| [Ui] rated insulation voltage | Control circuit: 600 V CSA certified; Control circuit: 600 V UL certified; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Control circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 690 V conforming to IEC 60947-4-1 |
| Overvoltage category | III |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 30 Mcycles |
| Control circuit type | DC low consumption |
| Coil technology | Built-in bidirectional peak limiting diode suppressor |
| Control circuit voltage limits | 0.1...0.3 Uc (-40…70 °C):drop-out DC; 0.8...1.25 Uc (-40…60 °C):operational DC; 1...1.25 Uc (60…70 °C):operational DC |
| Inrush power in W | 2.4 W (at 20 °C) |
| Hold-in power consumption in W | 2.4 W at 20 °C |
| Operating time | 77 ±15 % ms closing; 25 ±20 % ms opening |
| Time constant | 28 ms |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Connections - terminals | Control circuit: spring terminals 1 2.5 mm² - cable stiffness: flexible without cable end; Control circuit: spring terminals 2 2.5 mm² - cable stiffness: flexible without cable end; Power circuit: spring terminals 1 4 mm² - cable stiffness: flexible without cable end; Power circuit: spring terminals 2 4 mm² - cable stiffness: flexible without cable end |
| Auxiliary contact composition | 1 NO + 1 NC |
| Minimum switching voltage | 17 V for control circuit |
| Minimum switching current | 5 mA for control circuit |
| Insulation resistance | > 10 MOhm for control circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contacts; 1.5 ms on energisation between NC and NO contacts |
| Mounting support | Plate; Rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; CSA C22.2 No 60947-4-1 |
| Product certifications | UL; CCC; CSA; Marine; UKCA; EAC; CB Scheme |
| IP degree of protection | IP2X conforming to IEC 60529; IP2X conforming to VDE 0106 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor opened (8 Gn for 11 ms) ; Vibrations contactor opened (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) |
| Height | 99 mm |
| Width | 45 mm |
| Depth | 101 mm |
| Net weight | 0.54 kg |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys; TeSys Deca |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load; Motor control |
| Utilisation category | AC-3; AC-3e; AC-1 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 50 A (at |
| [Uc] control circuit voltage | 24 V DC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 11.4 cm |
| Package 1 Width | 11.0 cm |
| Package 1 Length | 5.5 cm |
| Package 1 Weight | 604.0 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 15 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 9.355 kg |
TeSys LC1D power contactor. 3-pole, 3 NO contacts. Additional auxiliary contacts - 1 NO + 1 NC contact, rated operating power at AC-3, 400 V 18.5 kW, rated operating current Ie at AC-3, 400 V 38 A, coil 24 V DC. Dimensions (WxHxD) 45x85x101 mm, weight 0.54 kg. Category AC-1, AC-3. Integrated bidirectional amplitude limiter diode. Quick and easy setup. Safe and durable power connection with Everlink and spring terminals. Suitable for safety applications due to mechanically coupled contacts and mirror contacts. Certifications according to LROS (Lloyds register of shipping), GOST, CCC, RINA, BV, CSA, DNV, GL, UL. Product standards according to UL 508, EN/IEC 60947-4-1, EN/IEC 60947-5-1, CSA C22.2 No 14.