| Complementary |
| Motor power kW | 7.5 kW at 220/230 V AC 50/60 Hz (AC-3); 15 kW at 380/400 V AC 50/60 Hz (AC-3); 15 kW at 415/440 V AC 50/60 Hz (AC-3); 18.5 kW at 500 V AC 50/60 Hz (AC-3); 18.5 kW at 660/690 V AC 50/60 Hz (AC-3); 7.5 kW at 220/230 V AC 50/60 Hz (AC-3e); 15 kW at 380/400 V AC 50/60 Hz (AC-3e); 15 kW at 415/440 V AC 50/60 Hz (AC-3e); 18.5 kW at 500 V AC 50/60 Hz (AC-3e); 18.5 kW at 660/690 V AC 50/60 Hz (AC-3e); 7.5 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power hp | 2 hp at 115 V AC 50/60 Hz for 1 phase motors; 5 hp at 230/240 V AC 50/60 Hz for 1 phase motors; 10 hp at 200/208 V AC 50/60 Hz for 3 phases motors; 10 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 20 hp at 460/480 V AC 50/60 Hz for 3 phases motors; 25 hp at 575/600 V AC 50/60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit; 50 A (at 60 °C) for power circuit |
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 550 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 550 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 260 A 40 °C - 10 s for power circuit; 430 A 40 °C - 1 s for power circuit; 60 A 40 °C - 10 min for power circuit; 138 A 40 °C - 1 min for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 63 A gG at |
| Average impedance | 2 mOhm - Ith 50 A 50 Hz for power circuit |
| Power dissipation per pole | 2 W AC-3; 5 W AC-1; 2 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 30 Mcycles |
| Electrical durability | 1.65 Mcycles 32 A AC-3 at Ue |
| Control circuit type | DC low consumption |
| Coil technology | Built-in bidirectional peak limiting diode suppressor |
| Control circuit voltage limits | 0.1...0.3 Uc (-40…70 °C):drop-out DC; 0.8...1.25 Uc (-40…60 °C):operational DC; 1...1.25 Uc (60…70 °C):operational DC |
| Inrush power in W | 2.4 W (at 20 °C) |
| Hold-in power consumption in W | 2.4 W at 20 °C |
| Operating time | 77 ±15 % ms closing; 25 ±20 % ms opening |
| Time constant | 40 ms |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Plate; Rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; CSA C22.2 No 60947-4-1 |
| Product certifications | UL; CCC; CSA; Marine; UKCA; EAC; CB Scheme |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor open (8 Gn for 11 ms) |
| Height | 85 mm |
| Width | 45 mm |
| Depth | 101 mm |
| Net weight | 0.535 kg |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Motor control; Resistive load |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 32 A (at |
| [Uc] control circuit voltage | 24 V DC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.000 cm |
| Package 1 Width | 9.300 cm |
| Package 1 Length | 11.300 cm |
| Package 1 Weight | 590.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 15 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 9.144 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 240 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 154.576 kg |
The LC1D32BL contactor from the TeSys Deca Advanced series by Schneider Electric is a 3-pole contactor for motor control and operation of resistive loads. It is designed for use in industrial plants where reliable and safe switching functions are required under high loads. The device features a control circuit with a coil voltage of 24 V DC and is rated for a nominal operating current of 32 A. The primary application is in the control of electric motors, with motor power ranging from 7.5 kW to 18.5 kW depending on voltage and usage category. At 400 V AC and usage category AC-3, the motor power is 15 kW. Usage categories include AC-3, AC-3e, AC-1, and AC-4, with AC-3 being the standard category for controlling three-phase motors.
Applications
This contactor is suitable for use in industrial plants, particularly in manufacturing and processing industries, where it is used to control electric motors in drive systems, conveyor systems, or machines. Certifications according to DNV, RINA, BV, GL, LROS, CCC, GOST, CSA, and UL also make it suitable for marine and safety-critical applications. The integrated bidirectional amplitude-limiting diode protects the coil against overvoltage, increasing service life and improving reliability in operation.
Functions and Equipment in Detail
The contactor features 3 close contacts in the main current circuit and additionally includes an auxiliary switch block with 1 close contact and 1 open contact. These auxiliary contacts enable integration into complex control logics, for example for feedback to control devices or synchronization with other components. The contacts are mechanically coupled and feature mirror contacts, which increases reliability in safety-critical applications. Current connection is achieved via Everlink technology with spring terminals, ensuring a secure and long-lasting connection.
Technology Explained Simply
The contactor coil is operated at 24 V DC and features an integrated bidirectional peak-limiting diode suppressor that limits overvoltage in the control circuit. The pickup power is 2.4 W at 20 °C, and the holding power consumption is also 2.4 W. The operating time is 77 ±15 % ms for closing and 25 ±20 % ms for opening. The time constant is 40 ms. The maximum operating rate is 3600 switching cycles per hour at an ambient temperature of 60 °C. The mechanical life is 30 million switching cycles, and the electrical life is 1.65 million switching cycles at 32 A and AC-3 operation.
Compatibility and Accessories
The contactor is compatible with various accessories that extend its functionality. These include motor protection circuit breakers such as the GV2LE32 or GV2ME32, auxiliary switch blocks such as the LADN02 or LADN20, and protection circuits such as the diode LA4DB3B. For mounting in busbar systems, products such as the GV2G445 or GV2G245 are available. Mechanical interlocks such as the LAD9V2 or kits for reversing contactors such as the LAD9R1 enable integration into complex switching systems.
Mounting and Installation
Mounting is carried out in standard control panels or enclosures. Dimensions are 45 mm (width) × 85 mm (height) × 101 mm (depth). The spring terminals allow for quick and secure connection without additional tools. Installation is carried out in accordance with applicable standards and regulations, particularly IEC 60947-4-1 and EN/ISO 13849-1. The rated insulation voltage is 690 V for the circuit and complies with the requirements of IEC 60947-4-1. The overvoltage category is III, and the pollution degree is 3, indicating use in industrial environments with increased pollution risk.
Operational Advantages
The contactor offers high operational safety through mechanically coupled contacts and mirror contacts. The integrated diode protection circuit increases service life and reduces maintenance. The spring terminals ensure a reliable current connection that remains stable even under vibration. Certifications according to international standards enable use in various industries, including shipping and power generation. The high mechanical and electrical life reduces maintenance intervals and lowers operating costs over the lifetime of the device.