| Complementary |
| Motor power kW | 5.5 kW at 220/230 V AC 50/60 Hz (AC-3); 11 kW at 380/400 V AC 50/60 Hz (AC-3); 11 kW at 415/440 V AC 50/60 Hz (AC-3); 15 kW at 500 V AC 50/60 Hz (AC-3); 15 kW at 660/690 V AC 50/60 Hz (AC-3); 5.5 kW at 220/230 V AC 50/60 Hz (AC-3e); 11 kW at 380/400 V AC 50/60 Hz (AC-3e); 11 kW at 415/440 V AC 50/60 Hz (AC-3e); 15 kW at 500 V AC 50/60 Hz (AC-3e); 15 kW at 660/690 V AC 50/60 Hz (AC-3e); 5.5 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power hp | 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors; 2 hp at 115 V AC 50/60 Hz for 1 phase motors; 7.5 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 15 hp at 460/480 V AC 50/60 Hz for 3 phases motors; 20 hp at 575/600 V AC 50/60 Hz for 3 phases motors; 7.5 hp at 200/208 V AC 50/60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit; 40 A (at 60 °C) for power circuit |
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 450 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 450 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 240 A 40 °C - 10 s for power circuit; 380 A 40 °C - 1 s for power circuit; 50 A 40 °C - 10 min for power circuit; 120 A 40 °C - 1 min for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 63 A gG at |
| Average impedance | 2 mOhm - Ith 40 A 50 Hz for power circuit |
| Power dissipation per pole | 3.2 W AC-1; 1.25 W AC-3; 1.25 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 15 Mcycles |
| Electrical durability | 1.65 Mcycles 25 A AC-3 at Ue |
| Control circuit type | AC at 50/60 Hz standard |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz |
| Inrush power in VA | 70 VA 60 Hz cos phi 0.75 (at 20 °C); 70 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Hold-in power consumption in VA | 7.5 VA 60 Hz cos phi 0.3 (at 20 °C); 7 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 2…3 W at 50/60 Hz |
| Operating time | 12...22 ms closing; 4...19 ms opening |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Rail; Plate |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; CSA C22.2 No 60947-4-1 |
| Product certifications | UL; CCC; CSA; Marine; UKCA; EAC; CB Scheme |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor open (8 Gn for 11 ms) |
| Height | 85 mm |
| Width | 45 mm |
| Depth | 92 mm |
| Net weight | 0.37 kg |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load; Motor control |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 25 A (at |
| [Uc] control circuit voltage | 230 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.000 cm |
| Package 1 Width | 9.200 cm |
| Package 1 Length | 11.000 cm |
| Package 1 Weight | 402.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 20 |
| Package 2 Height | 15 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 8.320 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 320 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 143.500 kg |
The LC1D25P7 contactor from the TeSys Deca Advanced series by Schneider Electric is a 3-pole contactor for controlling electrical loads, particularly for motor drives and resistive loads. It features an integrated auxiliary contact configuration with 1 normally closed (NC) and 1 normally open (NO) contact, which can be used for signaling functions in control systems. The rated operational power is 11 kW at 400 V AC in usage category AC-3, with a rated operational current Ie of 25 A. The control circuit voltage of the coil is 230 V AC at 50/60 Hz. The device is designed for use in industrial installations where reliable and safe switching functions are required.
Applications
The contactor is designed for controlling three-phase motors and resistive loads. It covers usage categories AC-1, AC-3, AC-3e, and AC-4, with AC-3 being the standard category for motor drives. Motor power is, for example, 5.5 kW at 220/230 V AC and 15 kW at 660/690 V AC, depending on the voltage level. The AC-4 rating allows use in applications with high switching frequencies, such as drives with high mechanical loads. Certifications according to UL, CSA, GL, CCC, RINA, GOST, DNV, BV, and LROS (Lloyds Register of Shipping) make the device suitable for marine and industrial applications.
Functions and Equipment in Detail
The contactor features a safety cover that enables protected access to the contacts. The main current contacts are configured as 3 normally open (NO) contacts, with current connection achieved via Everlink technology and spring terminals, ensuring a secure and long-lasting connection. The auxiliary contacts are instantaneous and can be used for control and monitoring tasks. The coil operates at 230 V AC and is supplied without an integrated switching module, enabling easy integration into existing control systems.
Technology Explained Simply
The rated insulation voltage is 690 V for the current circuit and complies with standards IEC 60947-4-1, CSA, and UL. The overvoltage category III and pollution degree 3 indicate that the device is designed for industrial environments with increased electrical stress and risk of contamination. The rated impulse voltage withstand is 6 kV, ensuring high electrical stability during transient voltage surges. The mechanical life is 15 million switching cycles, and the electrical life is 1.65 million cycles at 25 A AC-3. Heat dissipation is 2 to 3 W at 50/60 Hz, indicating efficient cooling and low thermal load on the surrounding environment.
Compatibility and Accessories
The contactor is compatible with various accessories that extend its functionality. These include auxiliary switch blocks such as LADN11 (1NO+1NC), LADN31 (3NO+1NC), or LADN40 (4NO), which provide additional signal contacts. Time modules such as LA4DT4U (on-delay 25–500 s) or LADT2 (inrush delay 0.10–30.00 s) enable time-controlled switching operations. Main current connectors such as LAD9V6 (reversible screw connection) or LAD9V5 (parallel) simplify wiring. Mechanical interlocks such as LAD9V2 or protective covers such as LAD9ET1S enhance safety and protection of the device.
Mounting and Installation
Mounting is performed in standard control panels using screws or mounting profiles. Dimensions are 45 mm (width) × 85 mm (height) × 92 mm (depth), enabling compact placement in control systems. Spring terminals and Everlink technology ensure secure and quick connection of main current conductors. The control circuit voltage of 230 V AC requires a corresponding power supply, which must be provided via the network or a control source.
Operational Advantages
The contactor offers high reliability through mechanically coupled contacts and mirror contacts, suitable for safety applications. The long service life and robust construction reduce maintenance and replacement intervals. Certifications according to international standards ensure suitability for use in various industries, including shipping and industrial automation. The integrated auxiliary contacts enable flexible control and monitoring of processes.