| Complementary |
| Motor power kW | 5.5 kW at 220/230 V AC 50/60 Hz (AC-3); 11 kW at 380/400 V AC 50/60 Hz (AC-3); 11 kW at 415/440 V AC 50/60 Hz (AC-3); 15 kW at 500 V AC 50/60 Hz (AC-3); 15 kW at 660/690 V AC 50/60 Hz (AC-3); 5.5 kW at 220/230 V AC 50/60 Hz (AC-3e); 11 kW at 380/400 V AC 50/60 Hz (AC-3e); 11 kW at 415/440 V AC 50/60 Hz (AC-3e); 15 kW at 500 V AC 50/60 Hz (AC-3e); 15 kW at 660/690 V AC 50/60 Hz (AC-3e); 5.5 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power hp | 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors; 2 hp at 115 V AC 50/60 Hz for 1 phase motors; 7.5 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 15 hp at 460/480 V AC 50/60 Hz for 3 phases motors; 20 hp at 575/600 V AC 50/60 Hz for 3 phases motors; 7.5 hp at 200/208 V AC 50/60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit; 40 A (at 60 °C) for power circuit |
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 450 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 450 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 240 A 40 °C - 10 s for power circuit; 380 A 40 °C - 1 s for power circuit; 50 A 40 °C - 10 min for power circuit; 120 A 40 °C - 1 min for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 63 A gG at |
| Average impedance | 2 mOhm - Ith 40 A 50 Hz for power circuit |
| Power dissipation per pole | 3.2 W AC-1; 1.25 W AC-3; 1.25 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 15 Mcycles |
| Electrical durability | 1.65 Mcycles 25 A AC-3 at Ue |
| Control circuit type | AC at 50/60 Hz standard |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz |
| Inrush power in VA | 70 VA 60 Hz cos phi 0.75 (at 20 °C); 70 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Hold-in power consumption in VA | 7.5 VA 60 Hz cos phi 0.3 (at 20 °C); 7 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 2…3 W at 50/60 Hz |
| Operating time | 12...22 ms closing; 4...19 ms opening |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Plate; Rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; CSA C22.2 No 60947-4-1 |
| Product certifications | UL; CCC; CSA; Marine; UKCA; EAC; CB Scheme |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor open (8 Gn for 11 ms) |
| Height | 85 mm |
| Width | 45 mm |
| Depth | 92 mm |
| Net weight | 0.37 kg |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load; Motor control |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 25 A (at |
| [Uc] control circuit voltage | 24 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.000 cm |
| Package 1 Width | 9.200 cm |
| Package 1 Length | 11.200 cm |
| Package 1 Weight | 404.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 20 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 8.395 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 320 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 145.600 kg |
The LC1D25B7 contactor from the TeSys Deca Advanced series by Schneider Electric is a 3-pole contactor for controlling motors and resistive loads. It features a main contact configuration with 3 closers and integrated auxiliary contacts in the configuration 1 closer + 1 opener. The control circuit voltage is 24 V AC at 50/60 Hz, making it suitable for use in standard AC networks. The device is designed for usage categories AC-1, AC-3, AC-3e, and AC-4, enabling motor control under various load conditions. At an operating voltage of 400 V AC and category AC-3, the rated operational power is 11 kW, and the rated operational current Ie is 25 A. The maximum motor power at 660/690 V AC is 15 kW, allowing use in industrial installations with higher voltage. The rated insulation voltage for the circuit is 690 V according to IEC 60947-4-1, with certifications under UL and CSA also valid at 600 V. The overvoltage category III and pollution degree 3 indicate suitability for industrial environments with increased electrical stress and contamination risk. The rated impulse withstand voltage is 6 kV, ensuring high electrical strength under transient voltage stresses.
Applications
This contactor is primarily designed for motor control in industrial installations, especially in applications with medium to high loads, such as in manufacturing, packaging technology, or material handling. The AC-3e usage category also enables use with special drives featuring high inrush currents. The combination of a 3-pole main contact configuration and integrated auxiliary contacts makes it suitable for complex control logics where additional signals for status monitoring or feedback to control devices are required. Certifications according to UL, CSA, GL, DNV, CCC, and RINA extend the application range into international markets, particularly in marine engineering and machinery construction.
Functions and Equipment in Detail
The device features a safety cover that enables protected access to contacts and supports compliance with safety regulations. Contacts are mechanically coupled and include mirror contacts, enhancing reliability in safety-critical applications. Electrical connections are made via Everlink and spring terminals, ensuring secure and long-lasting connections. The coil technology is designed without an integrated wiring module, simplifying installation and easing maintenance. Control circuit voltage limits are 0.3 to 0.6 Uc for release and 0.8 to 1.1 Uc for operation, with exact values varying depending on frequency (50 Hz or 60 Hz) and temperature (-40…70 °C). The pickup power is 70 VA at 50/60 Hz, and the holding power consumption is 7.5 VA (60 Hz) or 7 VA (50 Hz). Heat dissipation ranges from 2 to 3 W at 50/60 Hz.
Technology Explained Simply
The rated make capacity of 450 A at 440 V for the circuit and the nominal breaking capacity of 450 A at 440 V demonstrate the contactor’s ability to safely switch high current surges. The rated short-time current withstand of 240 A for 10 seconds at 40 °C for the circuit ensures stability under short-term overloads. The mechanical life is 15 million switching cycles, and the electrical life is 1.65 million cycles at 25 A AC-3. Power loss per pole is 3.2 W at AC-1 and 1.25 W at AC-3/AC-3e, describing the thermal load during operation. The conventional thermal current (Ith) is 40 A for the circuit at 60 °C, indicating maximum continuous load capacity. The average impedance is 2 MΩ at 40 A and 50 Hz for the circuit.
Compatibility and Accessories
The contactor is compatible with various accessories that extend its functionality. These include auxiliary switch blocks such as LADN40 (4S non-delayed), LADN11 (1S1O non-delayed), LADN31 (3S1O non-delayed), or LADN22 (2S+2O non-delayed), which can be mounted on the front panel as needed. Time modules such as LA4DT4U (make-delayed, 25–500 s) or LADT4 (pickup-delayed, 10–180 s) enable time-controlled switching operations. Mechanical interlocks like LAD9V2 or main current connectors like LAD9V6 support safe mounting and wiring. For integration into busbar systems, the GV2G245 is available. Combining it with motor protection circuit breakers such as GV2ME22 enables a complete motor control unit.
Mounting and Installation
Mounting is done via standard screw terminals on the front. Everlink and spring terminals ensure a secure and durable electrical connection. Dimensions are 45 mm (width) × 85 mm (height) × 92 mm (depth), enabling compatibility with standard control panels. Weight is 0.37 kg. Installation requires no special tools, as terminals are accessible with screwdrivers. The integrated safety cover supports compliance with occupational safety regulations.
Operational Advantages
The contactor offers high operational reliability through mechanically coupled contacts and mirror contacts, which is particularly beneficial in safety-critical installations. The long service life of 15 million mechanical and 1.65 million electrical switching cycles reduces maintenance and replacement intervals. Integrated auxiliary contacts enable flexible control logic without additional components. Certifications according to international standards (UL, CSA, GL, DNV, CCC, RINA) extend the application range across various industries and markets. Easy mounting and maintenance via Everlink and spring terminals, along with clear terminal labeling, simplify installation and servicing.