| Additional features |
| Motor power (kW) | 5.5 kW at 220 - 230 V AC 50/60 Hz (AC-3); 11 kW at 380 - 400 V AC 50/60 Hz (AC-3); 11 kW at 415 - 440 V AC 50/60 Hz (AC-3); 15 kW at 500 V AC 50/60 Hz (AC-3); 15 kW at 660 - 690 V AC 50/60 Hz (AC-3); 5.5 kW at 400 V AC 50/60 Hz (AC-4); 5.5 kW at 220 - 230 V AC 50/60 Hz (AC-3e); 11 kW at 380 - 400 V AC 50/60 Hz (AC-3e); 11 kW at 415 - 440 V AC 50/60 Hz (AC-3e); 15 kW at 500 V AC 50/60 Hz (AC-3e); 15 kW at 660 - 690 V AC 50/60 Hz (AC-3e) |
| Compatibility code | LC1D |
| Composition of pole contact | 3 S |
| Protection cover | With |
| [Ith] conventional thermal current in free air | 40 A (at 60 °C) for power circuit; 10 A (at 60 °C) for signal circuit |
| [Irms] Rated making capacity | 450 A at 440 V for circuit conforming to IEC 60947; 140 A AC for signal circuit conforming to IEC 60947-5-1; 250 A DC for signal circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 450 A at 440 V for circuit complies with IEC 60947 |
| [Icw] rated short-time current withstand | 240 A 40 °C - 10 s for circuit; 380 A 40 °C - 1 s for circuit; 50 A 40 °C - 10 min for circuit; 120 A 40 °C - 1 min for circuit; 100 A - 1 s for signal circuit; 120 A - 500 ms for signal circuit; 140 A - 100 ms for signal circuit |
| Associated fuse | 10 A gG for signal circuit, compliant with IEC 60947-5-1; 63 A gG at |
| Average impedance | 2 MOhm - Ith 40 A 50 Hz for circuit |
| Power dissipation per pole | 1,25 W AC-3; 1,25 W AC-3e; 3,2 W AC-1 |
| [Ui] Rated insulation voltage | Circuit: 690 V according to IEC 60947-4-1; Signal circuit: 690 V according to IEC 60947-1 |
| Over voltage category | III |
| Pollution degree | 3 |
| [Uimp] Rated impulse voltage withstand | 6 kV corresponds to IEC 60947 |
| Security level rating | B10d = 1369863 cycles contactor with rated load corresponds to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load corresponds to EN/ISO 13849-1 |
| Mechanical life | 30 Mcycles |
| Electrical lifetime | 1.4 Mcycles 40 A AC-1 at Ue |
| Control circuit type | DC Standard |
| Coil technology | Integrated bidirectional transient voltage suppressor diodes |
| Control circuit voltage limits | 0.1 - 0.25 Uc (-40…70 °C): drop-out voltage DC 50/60 Hz; 0.7 - 1.25 Uc (-40…60 °C): operation DC 50 Hz; 1 - 1.25 Uc (60…70 °C): operation DC 60 Hz |
| Absorption power in W | 5.4 W (at 20 °C) |
| Holding power consumption in W | 5.4 W at 20 °C |
| Operating time | 63 ±15 % ms closing; 20 ±20 % ms opening |
| Time constant | 28 ms |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Configuration of auxiliary contacts | 1 S + 1 Ö |
| Type of auxiliary contacts | Mechanically linked type 1 S + 1 NC complies with IEC 60947-5-1; Mirror contact type 1 NO complies with IEC 60947-4-1 |
| Signalling angular frequency | 25 - 400 Hz |
| Min. switching voltage | 17 V for signal circuit |
| Min. switching current | 5 mA for signal circuit |
| Insulation resistance | > 10 MΩ for signal circuits |
| Non-overlapping time | 1.5 ms with switching between normally open and normally closed contact; 1.5 ms with actuation between normally open and normally closed contact |
| Mounting bracket | Plate; rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Application of contactor | Motor control; resistive load |
| Application category | AC-1; AC-3; AC-3e; AC-4 |
| Pole description | 3P |
| [Ue] Rated operational voltage | Circuit: |
| [Ie] rated operational current | 25 A (at |
| [Uc] control circuit voltage | 60 V DC |
| Mounting |
| Standards | EN 60947-4-1; IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No. 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ |
| Product certifications | CB control; CCC; cULus; CE; UKCA; EU-RO-MR by DNV |
| Degree of protection (IP) | IP20 front side corresponds to IEC 60529 |
| Protection treatment | TH corresponds to IEC 60068-2-30 |
| Climate resistance | Complies with IACS E10 damp heat exposure; complies with IEC 60947-1 Annex Q Category D damp heat exposure |
| Device ambient temperature | -40…60 °C; 60…70 °C with power reduction |
| Operating altitude | 0 - 3.000 m |
| Fire-resistance | 850 °C corresponds to IEC 60695-2-1 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5 - 300 Hz); Vibrations contactor closed (4 Gn, 5 - 300 Hz); Shocks contactor closed (15 Gn for 11 ms); Shocks contactor open (8 Gn for 11 ms) |
| Height | 110 mm |
| Width | 45 mm |
| Depth | 101 mm |
| Product weight | 624 g |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 5 cm |
| VPE 1 width | 10,5 cm |
| VPE 1 length | 11,5 cm |
| Packaging weight (Lbs) | 644 g |
| VPE 2 type | S02 |
| VPE 2 quantity | 15 |
| VPE 2 height | 15 cm |
| VPE 2 width | 30 cm |
| VPE 2 length | 40 cm |
| VPE 2 weight | 9,975 kg |
| VPE 3 type | P06 |
| VPE 3 quantity | 240 |
| VPE 3 height | 75 cm |
| VPE 3 width | 60 cm |
| VPE 3 length | 80 cm |
| VPE 3 weight | 168,1 kg |
The LC1D25AND contactor from the TeSys Deca Advanced series by Schneider Electric is a 3-pole contactor for motor control and operation with resistive loads. It is designed for usage categories AC-1, AC-3, AC-3e, and AC-4 and features a rated operational current of 25 A. The control circuit voltage is 60 V DC, with the coil protected by integrated bidirectional surge-limiting diode suppressors to limit overvoltages. The operating time is 63 ±15 % ms for closing and 20 ±20 % ms for opening, enabling fast and precise switching. The maximum operating rate is 3600 switching cycles per hour at 60 °C, suitable for high-demand industrial applications.
Applications
This contactor is designed for controlling electric motors, particularly in systems with motor power up to 11 kW at 380–400 V AC (AC-3) and up to 15 kW at 660–690 V AC (AC-3). It can also be used for resistive loads. Usage categories AC-3 and AC-4 cover typical industrial applications such as motor starting and braking. Category AC-3e allows operation under increased loads, for example with pumps or compressors. The rated insulation voltage is 690 V for power and signal circuits, ensuring safe insulation even at high voltages.
Functions and Equipment in Detail
The device features 3 main circuit closers and additional auxiliary contacts configured as 1 closer + 1 opener. The auxiliary contacts are mechanically linked and comply with IEC 60947-5-1. Additionally, a mirror contact (1 opener) is included, suitable for safety applications and meeting IEC 60947-4-1. The auxiliary contacts enable integration into control and monitoring systems, for example to signal the contactor status. The connection terminals are SnapIN type, enabling quick, secure, and maintenance-free electrical connections.
Technology Explained Simply
The integrated bidirectional surge-limiting diode suppression protects the coil from transient voltage spikes that may occur during switching operations. The control circuit voltage of 60 V DC is designed for operational safety in industrial environments. The operating voltage ranges are between 0.7–1.25 Uc at -40…60 °C and 1–1.25 Uc at 60…70 °C, ensuring reliable performance over a wide temperature range. The pickup and holding power is 5.4 W each at 20 °C, ensuring stable magnetic field generation. The time constant of 28 ms influences the switching speed and dynamics of the contactor.
Compatibility and Accessories
The contactor is marked with compatibility designation LC1D, enabling use with other TeSys Deca Advanced components. Suitable accessories include delayed auxiliary switch blocks (LAD-R4, LAD-S2), time blocks (LADT0, LADT2, LADT4), motor protection relays (LRD22, GV2ME22A), various auxiliary switch blocks (LADN02A, LADN04A, LADN11A, LADN13A, LADN20A, LADN22A, LADN31A, LADN40A), and mechanical interlocks (LAD9V2). These components allow functional expansion, for example through time delays, additional contacts, or motor protection functions.
Mounting and Installation
Mounting is done via SnapIN connection terminals, enabling quick and secure connections. Dimensions are 45 mm (width) × 110 mm (height) × 95 mm (depth), allowing compact integration into enclosures. Installation must be performed by qualified personnel, with all power supplies switched off before mounting. The use of appropriate fuses (e.g., 10 A gG for the signal circuit) is recommended to ensure safety.
Operational Advantages
The contactor offers a high mechanical life of 30 million switching cycles and an electrical life of 1.4 million cycles at 40 A AC-1. The rated short-time withstand current is 240 A for 10 seconds and 380 A for 1 second, ensuring high stability under short-circuit conditions. Overvoltage category III and pollution degree 3 make the device suitable for industrial environments. The rated impulse withstand voltage of 6 kV protects against transient voltage surges. The safety level rating (B10d = 1369863 cycles at rated load, B10d = 20000000 cycles at mechanical load) according to EN/ISO 13849-1 confirms suitability for safety applications.