| Additional features |
| Motor power (kW) | 5.5 kW at 220 - 230 V AC 50/60 Hz (AC-3); 11 kW at 380 - 400 V AC 50/60 Hz (AC-3); 11 kW at 415 - 440 V AC 50/60 Hz (AC-3); 15 kW at 500 V AC 50/60 Hz (AC-3); 15 kW at 660 - 690 V AC 50/60 Hz (AC-3); 5.5 kW at 400 V AC 50/60 Hz (AC-4); 5.5 kW at 220 - 230 V AC 50/60 Hz (AC-3e); 11 kW at 380 - 400 V AC 50/60 Hz (AC-3e); 11 kW at 415 - 440 V AC 50/60 Hz (AC-3e); 15 kW at 500 V AC 50/60 Hz (AC-3e); 15 kW at 660 - 690 V AC 50/60 Hz (AC-3e) |
| Compatibility code | LC1D |
| Composition of pole contact | 3 S |
| Protection cover | With |
| [Ith] conventional thermal current in free air | 40 A (at 60 °C) for power circuit; 10 A (at 60 °C) for signal circuit |
| [Irms] Rated making capacity | 450 A at 440 V for circuit conforming to IEC 60947; 140 A AC for signal circuit conforming to IEC 60947-5-1; 250 A DC for signal circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 450 A at 440 V for circuit complies with IEC 60947 |
| [Icw] rated short-time current withstand | 240 A 40 °C - 10 s for circuit; 380 A 40 °C - 1 s for circuit; 50 A 40 °C - 10 min for circuit; 120 A 40 °C - 1 min for circuit; 100 A - 1 s for signal circuit; 120 A - 500 ms for signal circuit; 140 A - 100 ms for signal circuit |
| Associated fuse | 10 A gG for signal circuit, compliant with IEC 60947-5-1; 63 A gG at |
| Average impedance | 2 MOhm - Ith 40 A 50 Hz for circuit |
| Power dissipation per pole | 1,25 W AC-3; 1,25 W AC-3e; 3,2 W AC-1 |
| [Ui] Rated insulation voltage | Circuit: 690 V according to IEC 60947-4-1; Signal circuit: 690 V according to IEC 60947-1 |
| Over voltage category | III |
| Pollution degree | 3 |
| [Uimp] Rated impulse voltage withstand | 6 kV corresponds to IEC 60947 |
| Security level rating | B10d = 1369863 cycles contactor with rated load corresponds to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load corresponds to EN/ISO 13849-1 |
| Mechanical life | 30 Mcycles |
| Electrical lifetime | 1.4 Mcycles 40 A AC-1 at Ue |
| Control circuit type | DC Standard |
| Coil technology | Integrated bidirectional transient voltage suppressor diodes |
| Control circuit voltage limits | 0.1 - 0.25 Uc (-40…70 °C): drop-out voltage DC 50/60 Hz; 0.7 - 1.25 Uc (-40…60 °C): operation DC 50 Hz; 1 - 1.25 Uc (60…70 °C): operation DC 60 Hz |
| Absorption power in W | 5.4 W (at 20 °C) |
| Holding power consumption in W | 5.4 W at 20 °C |
| Operating time | 63 ±15 % ms closing; 20 ±20 % ms opening |
| Time constant | 28 ms |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Configuration of auxiliary contacts | 1 S + 1 Ö |
| Type of auxiliary contacts | Mechanically linked type 1 S + 1 NC complies with IEC 60947-5-1; Mirror contact type 1 NO complies with IEC 60947-4-1 |
| Signalling angular frequency | 25 - 400 Hz |
| Min. switching voltage | 17 V for signal circuit |
| Min. switching current | 5 mA for signal circuit |
| Insulation resistance | > 10 MΩ for signal circuits |
| Non-overlapping time | 1.5 ms with switching between normally open and normally closed contact; 1.5 ms with actuation between normally open and normally closed contact |
| Mounting bracket | Plate; rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Application of contactor | Motor control; resistive load |
| Application category | AC-1; AC-3; AC-3e; AC-4 |
| Pole description | 3P |
| [Ue] Rated operational voltage | Circuit: |
| [Ie] rated operational current | 25 A (at |
| [Uc] control circuit voltage | 220 V DC |
| Mounting |
| Standards | EN 60947-4-1; IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No. 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ |
| Product certifications | CB control; CCC; cULus; CE; UKCA; EU-RO-MR by DNV |
| Degree of protection (IP) | IP20 front side corresponds to IEC 60529 |
| Protection treatment | TH corresponds to IEC 60068-2-30 |
| Climate resistance | Complies with IACS E10 damp heat exposure; complies with IEC 60947-1 Annex Q Category D damp heat exposure |
| Device ambient temperature | -40…60 °C; 60…70 °C with power reduction |
| Operating altitude | 0 - 3.000 m |
| Fire-resistance | 850 °C corresponds to IEC 60695-2-1 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5 - 300 Hz); Vibrations contactor closed (4 Gn, 5 - 300 Hz); Shocks contactor closed (15 Gn for 11 ms); Shocks contactor open (8 Gn for 11 ms) |
| Height | 110 mm |
| Width | 45 mm |
| Depth | 101 mm |
| Product weight | 624 g |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 5 cm |
| VPE 1 width | 10,5 cm |
| VPE 1 length | 11,5 cm |
| Packaging weight (Lbs) | 644 g |
| VPE 2 type | S02 |
| VPE 2 quantity | 15 |
| VPE 2 height | 15 cm |
| VPE 2 width | 30 cm |
| VPE 2 length | 40 cm |
| VPE 2 weight | 9,975 kg |
| VPE 3 type | P06 |
| VPE 3 quantity | 240 |
| VPE 3 height | 75 cm |
| VPE 3 width | 60 cm |
| VPE 3 length | 80 cm |
| VPE 3 weight | 168,1 kg |
The LC1D25AMD contactor from the TeSys Deca Advanced series by Schneider Electric is a 3-pole contactor for motor control and operation with resistive loads. It is designed for usage categories AC-1, AC-3, AC-3e, and AC-4 and features a rated operational current of 25 A. The control circuit voltage is 220 V DC, with the coil protected by integrated bidirectional surge-limiting diode suppressors to limit overvoltages. The device is suitable for controlling motors up to 11 kW at 380–400 V AC (AC-3). The rated insulation voltage is 690 V for both the power circuit and signal circuit, in accordance with standards IEC 60947-4-1 and IEC 60947-1. The overvoltage category III and pollution degree 3 make the contactor suitable for industrial applications in environments with increased pollution risk. The rated impulse voltage withstand is 6 kV, ensuring high electrical strength.
Applications
This contactor is primarily intended for controlling electric motors in industrial plants, particularly in drive technology, conveyor systems, pumps, and fans. It can also be used for resistive loads such as heaters or resistors. The AC-3e usage category enables use in special motor control requirements, such as frequent starting and stopping. The AC-4 category is suitable for applications with high mechanical stress, such as crane drives. The mechanical life is 30 million switching cycles, and the electrical life is 1.4 million switching cycles at 40 A AC-1 and rated voltage.
Functions and Features in Detail
The contactor includes 3 main circuit closing contacts and integrated auxiliary contacts with one closing and one opening contact. The auxiliary contacts are mechanically linked and comply with IEC 60947-5-1. Additionally, a mirror contact (1 opening) is available, suitable for safety applications and meeting the requirements of IEC 60947-4-1. The operating time is 63 ±15 % ms for closing and 20 ±20 % ms for opening. The maximum operating rate is 3600 switching cycles per hour at 60 °C. The coil has an inrush power of 5.4 W and a holding power consumption of 5.4 W at 20 °C. The control circuit voltage limits range from 0.7 to 1.25 Uc at -40…60 °C for operation, with operation up to 1.25 Uc possible at 60…70 °C.
Technology Explained Simply
The integrated bidirectional surge-limiting diode suppression protects the coil from transient voltage spikes caused by switching operations in the network. This extends the coil’s lifespan and increases the reliability of the contactor. The SnapIN connection terminals allow for quick, secure, and maintenance-free electrical connections without tools. The construction with mechanically coupled contacts and mirror contacts ensures high safety in critical applications, as the contacts switch synchronously, guaranteeing safe disconnection. The rated short-time current withstand is 240 A for 10 seconds at 40 °C in the power circuit, ensuring stability during short-term overloads.
Compatibility and Accessories
The contactor is compatible with a variety of accessories, including delayed auxiliary switch blocks such as the LAD-R4 (10–180 seconds delayed reset) or the LAD-S2 (1–30 seconds delayed operation). It can be combined with motor protection relays such as the LRD22 (16–24 A, 1NO+1NC, Class 10A) or the GV2ME22A (3p, 20–25 A, push-button operation, SnapIN). Various auxiliary switch blocks are also available, such as the LADN02A (2 opening) or LADN11A (1NO+1NC), which are mounted using SnapIN terminals. The LAD9V2 interlock enables mechanical interlocking for TeSys D contactors.
Mounting and Installation
Mounting is done via SnapIN terminals, enabling quick and secure connections without tools. Dimensions are 45 mm (width) × 110 mm (height) × 95 mm (depth). Installation requires no special tools, as the terminals connect by simple snapping. Connections are clearly labeled, with main contacts (L1, L2, L3) and auxiliary contacts (13, 14, 21, 22) distinctly marked. The protective cover is integrated and protects contacts from mechanical damage and contamination.
Operational Advantages
The contactor offers high operational safety through mechanically coupled contacts and mirror contacts, suitable for safety applications. The integrated coil protection technology extends lifespan and reduces failure risks. The SnapIN technology enables fast installation and maintenance, minimizing downtime. The high electrical and mechanical life, along with high short-time current withstand, make the contactor suitable for demanding industrial applications. The use of standard norms such as IEC 60947-4-1 and IEC 60947-5-1 ensures interoperability with other components in plant engineering.