Schneider Electric LC1D25AKUE, EAN: 3606487540113

Schneider Electric LC1D25AKUE contactor 3p+1S+1Ö 25 A

Schneider Electric LC1D25AKUE contactor 3p+1S+1Ö 25 A

Lieske Part No. 706938
Mfg Part No LC1D25AKUE
EAN-Code 3606487540113
Manufacturer Schneider Electric
Here only 115,96 EUR
137,99 EUR incl. VAT

Further information for Schneider Electric LC1D25AKUE contactor 3p+1S+1Ö 25 A

Additional features
Motor power (kW)5.5 kW at 220 - 230 V AC 50 Hz (AC-3); 11 kW at 380 - 400 V AC 50 Hz (AC-3); 11 kW at 415 V AC 50 Hz (AC-3); 11 kW at 440 V AC 50 Hz (AC-3); 15 kW at 500 V AC 50 Hz (AC-3); 15 kW at 660 - 690 V AC 50 Hz (AC-3); 5.5 kW at 220 - 230 V AC 50 Hz (AC-3e); 11 kW at 380 - 400 V AC 50 Hz (AC-3e); 11 kW at 415 V AC 50 Hz (AC-3e); 11 kW at 440 V AC 50 Hz (AC-3e); 15 kW at 500 V AC 50 Hz (AC-3e); 15 kW at 660 - 690 V AC 50 Hz (AC-3e)
Compatibility codeLC1D
Composition of pole contact3 S
Protection coverWith
[Ith] conventional thermal current in free air40 A (at 60 °C) for power circuit; 10 A (at 60 °C) for signal circuit
[Irms] Rated making capacity450 A at 440 V for circuit conforming to IEC 60947; 140 A AC for signal circuit conforming to IEC 60947-5-1; 250 A DC for signal circuit conforming to IEC 60947-5-1
Rated breaking capacity450 A at 440 V for circuit complies with IEC 60947
[Icw] rated short-time current withstand240 A 40 °C - 10 s for circuit; 380 A 40 °C - 1 s for circuit; 50 A 40 °C - 10 min for circuit; 120 A 40 °C - 1 min for circuit; 100 A - 1 s for signal circuit; 120 A - 500 ms for signal circuit; 140 A - 100 ms for signal circuit
Associated fuse10 A gG for signal circuit, compliant with IEC 60947-5-1; 63 A gG at
Average impedance2 MOhm - Ith 40 A 50 Hz for circuit
Power dissipation per pole1,25 W AC-3; 1,25 W AC-3e; 3,2 W AC-1
[Ui] Rated insulation voltageCircuit: 690 V according to IEC 60947-4-1; Signal circuit: 690 V according to IEC 60947-1
Over voltage categoryIII
Pollution degree3
[Uimp] Rated impulse voltage withstand6 kV corresponds to IEC 60947
Security level ratingB10d = 1369863 cycles contactor with rated load corresponds to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load corresponds to EN/ISO 13849-1
Mechanical life15 Mcycles
Electrical lifetime0.9 Mcycles 40 A AC-1 at Ue
Control circuit typeAC/DC at 50/60 Hz AC/DC, electronic
Coil technologyIntegrated bidirectional surge limiting
Input power in VA25 VA 50/60 Hz (at 20 °C)
Absorption power in W18 W (at 20 °C)
Hold power consumption in VA1.6 VA 50/60 Hz (at 20 °C)
Holding power consumption in W1.1 W at 20 °C
Heat emission1,1 W at 50/60 Hz
Operating time45 - 55 ms closing; 20 - 90 ms opening
Maximum operating rate3600 cyc/h at 60 °C
Configuration of auxiliary contacts1 S + 1 Ö
Type of auxiliary contactsMechanically linked type 1 S + 1 NC complies with IEC 60947-5-1; Mirror contact type 1 NO complies with IEC 60947-4-1
Signalling angular frequency25 - 400 Hz
Min. switching voltage17 V for signal circuit
Min. switching current5 mA for signal circuit
Insulation resistance> 10 MΩ for signal circuits
Non-overlapping time1.5 ms with switching between normally open and normally closed contact; 1.5 ms with actuation between normally open and normally closed contact
Mounting bracketPlate; rail
Contractual warranty
Warranty (in months)18
Main features
Product seriesTeSys Deca Advanced
Product or component typeContactor
Device short nameLC1D
Application of contactorMotor control; resistive load
Application categoryAC-1; AC-3; AC-3e
Pole description3P
[Ue] Rated operational voltageCircuit:
[Ie] rated operational current25 A (at
[Uc] control circuit voltage100 - 250 V AC 50/60 Hz; 100 - 250 V DC
Mounting
StandardsEN 60947-4-1; IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No. 60947-4-1; IEC 60335-1
Product certificationsCB control; CCC; cULus; CE; UKCA; EU-RO-MR by DNV
Degree of protection (IP)IP20 front side corresponds to IEC 60529
Protection treatmentTH corresponds to IEC 60068-2-30
Climate resistanceComplies with IACS E10 damp heat exposure; complies with IEC 60947-1 Annex Q Category D damp heat exposure
Device ambient temperature-40…60 °C; 60…70 °C with power reduction
Operating altitude0 - 3.000 m
Fire-resistance850 °C corresponds to IEC 60695-2-1
Mechanical robustnessVibrations contactor open (2 Gn, 5 - 300 Hz); Vibrations contactor closed (4 Gn, 5 - 300 Hz); Shocks contactor closed (15 Gn for 11 ms); Shocks contactor open (8 Gn for 11 ms)
Height110 mm
Width45 mm
Depth92 mm
Product weight524 g
Packaging units
VPE 1 typePCE
Number of devices per package1
VPE 1 height5,600 cm
VPE 1 width10,800 cm
VPE 1 length11,600 cm
Packaging weight (Lbs)514,000 g
VPE 2 typeS02
VPE 2 quantity15
VPE 2 height15,000 cm
VPE 2 width30,000 cm
VPE 2 length40,000 cm
VPE 2 weight8,475 kg
VPE 3 typeP06
VPE 3 quantity240
VPE 3 height75,000 cm
VPE 3 width60,000 cm
VPE 3 length80,000 cm
VPE 3 weight144,100 kg
Leistungsschütz TeSys DECA. 3 polig, 3 Schließer. Zusätzliche Hilfskontakte- 1 Schließer + 1 Öffner, Bemessungsbetriebsleistung bei AC-3, 400 V 11 kW, Bemessungsbetriebsstrom Ie bei AC-3, 400 V 25 A, Spule 100-250 V AC/DC. Abmessung (BxHxT) 45x110x95 mm, Gewicht 0,32 kg. Kategorie AC-3, AC-1, AC-4. integrierte bidirektionale Amplitudenbegrenzerdiode. Schnelle, sichere und wartungsfreie Stromverbindung mit SnapIN Anschlussklemme. Geeignet für Sicherheitsanwendungen durch mechanisch gekoppelte Kontakte und Spiegelkontakte.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/706938
qrcode für Schneider Electric LC1D25AKUE contactor 3p+1S+1Ö 25 A