| Additional features |
| Motor power (kW) | 5.5 kW at 220 - 230 V AC 50/60 Hz (AC-3); 11 kW at 380 - 400 V AC 50/60 Hz (AC-3); 11 kW at 415 - 440 V AC 50/60 Hz (AC-3); 15 kW at 500 V AC 50/60 Hz (AC-3); 15 kW at 660 - 690 V AC 50/60 Hz (AC-3); 5.5 kW at 400 V AC 50/60 Hz (AC-4); 5.5 kW at 220 - 230 V AC 50/60 Hz (AC-3e); 11 kW at 380 - 400 V AC 50/60 Hz (AC-3e); 11 kW at 415 - 440 V AC 50/60 Hz (AC-3e); 15 kW at 500 V AC 50/60 Hz (AC-3e); 15 kW at 660 - 690 V AC 50/60 Hz (AC-3e) |
| Compatibility code | LC1D |
| Composition of pole contact | 3 S |
| Protection cover | With |
| [Ith] conventional thermal current in free air | 40 A (at 60 °C) for power circuit; 10 A (at 60 °C) for signal circuit |
| [Irms] Rated making capacity | 450 A at 440 V for circuit conforming to IEC 60947; 140 A AC for signal circuit conforming to IEC 60947-5-1; 250 A DC for signal circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 450 A at 440 V for circuit complies with IEC 60947 |
| [Icw] rated short-time current withstand | 240 A 40 °C - 10 s for circuit; 380 A 40 °C - 1 s for circuit; 50 A 40 °C - 10 min for circuit; 120 A 40 °C - 1 min for circuit; 100 A - 1 s for signal circuit; 120 A - 500 ms for signal circuit; 140 A - 100 ms for signal circuit |
| Associated fuse | 10 A gG for signal circuit, compliant with IEC 60947-5-1; 63 A gG at |
| Average impedance | 2 MOhm - Ith 40 A 50 Hz for circuit |
| Power dissipation per pole | 1,25 W AC-3; 1,25 W AC-3e; 3,2 W AC-1 |
| [Ui] Rated insulation voltage | Circuit: 690 V according to IEC 60947-4-1; Signal circuit: 690 V according to IEC 60947-1 |
| Over voltage category | III |
| Pollution degree | 3 |
| [Uimp] Rated impulse voltage withstand | 6 kV corresponds to IEC 60947 |
| Security level rating | B10d = 1369863 cycles contactor with rated load corresponds to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load corresponds to EN/ISO 13849-1 |
| Mechanical life | 30 Mcycles |
| Electrical lifetime | 1.4 Mcycles 40 A AC-1 at Ue |
| Control circuit type | DC low power consumption |
| Coil technology | Integrated bidirectional transient voltage suppressor diodes |
| Control circuit voltage limits | 0.1 - 0.3 Uc (-40…70 °C): drop voltage DC; 0.8 - 1.25 Uc (-40…60 °C): operation DC; 1 - 1.25 Uc (60…70 °C): operation DC |
| Input power in VA | 2.4 W (at 20 °C) |
| Absorption power in W | 2.4 W (at 20 °C) |
| Operating time | 77 ±15 % ms closing; 25 ±20 % ms opening |
| Time constant | 40 ms |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Configuration of auxiliary contacts | 1 S + 1 Ö |
| Type of auxiliary contacts | Mechanically linked type 1 S + 1 NC complies with IEC 60947-5-1; Mirror contact type 1 NO complies with IEC 60947-4-1 |
| Signalling angular frequency | 25 - 400 Hz |
| Min. switching voltage | 17 V for signal circuit |
| Min. switching current | 5 mA for signal circuit |
| Insulation resistance | > 10 MΩ for signal circuits |
| Non-overlapping time | 1.5 ms with switching between normally open and normally closed contact; 1.5 ms with actuation between normally open and normally closed contact |
| Mounting bracket | Plate; rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Application of contactor | Motor control; resistive load |
| Application category | AC-1; AC-3; AC-3e; AC-4 |
| Pole description | 3P |
| [Ue] Rated operational voltage | Circuit: |
| [Ie] rated operational current | 25 A (at |
| [Uc] control circuit voltage | 12 V DC |
| Mounting |
| Standards | EN 60947-4-1; IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No. 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ |
| Product certifications | CB control; CCC; cULus; CE; UKCA; EU-RO-MR by DNV |
| Degree of protection (IP) | IP20 front side corresponds to IEC 60529 |
| Protection treatment | TH corresponds to IEC 60068-2-30 |
| Climate resistance | Complies with IACS E10 damp heat exposure; complies with IEC 60947-1 Annex Q Category D damp heat exposure |
| Device ambient temperature | -40…60 °C; 60…70 °C with power reduction |
| Operating altitude | 0 - 3.000 m |
| Fire-resistance | 850 °C corresponds to IEC 60695-2-1 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5 - 300 Hz); Vibrations contactor closed (4 Gn, 5 - 300 Hz); Shocks contactor closed (15 Gn for 11 ms); Shocks contactor open (8 Gn for 11 ms) |
| Height | 110 mm |
| Width | 45 mm |
| Depth | 101 mm |
| Product weight | 624 g |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 5,600 cm |
| VPE 1 width | 11,700 cm |
| VPE 1 length | 10,800 cm |
| Packaging weight (Lbs) | 654,000 g |
| VPE 2 type | S02 |
| VPE 2 quantity | 15 |
| VPE 2 height | 15,000 cm |
| VPE 2 width | 30,000 cm |
| VPE 2 length | 40,000 cm |
| VPE 2 weight | 9,975 kg |
| VPE 3 type | P06 |
| VPE 3 quantity | 240 |
| VPE 3 height | 75,000 cm |
| VPE 3 width | 60,000 cm |
| VPE 3 length | 80,000 cm |
| VPE 3 weight | 168,100 kg |
The LC1D25AJL contactor from the TeSys Deca Advanced series by Schneider Electric is a 3-pole contactor for motor control and operation with resistive loads. It is designed for usage categories AC-1, AC-3, AC-3e, and AC-4, with category AC-3 representing the typical application for controlling three-phase motors. The device features a rated operational current of 25 A and is designed for a control circuit voltage of 12 V DC, with the coil exhibiting low power consumption. The rated operating voltage of the circuit is up to 690 V, with a nominal breaking capacity of 450 A at 440 V, complying with IEC 60947 standards. The maximum motor power is 11 kW at 380–400 V AC 50/60 Hz (AC-3) and 5.5 kW at 400 V AC 50/60 Hz (AC-4), highlighting its suitability for industrial drive systems.
Applications
This contactor is designed for use in industrial plants, particularly for controlling three-phase motors in production lines, conveyor systems, or pump systems. The AC-3e usage category also enables operation under increased demands, such as frequent start-stop cycles. Category AC-4 is suitable for applications with high inrush currents, such as loads with high starting torque. The integrated bidirectional peak-limiting diode suppressor coil technology protects control electronics from transient voltage spikes, enhancing reliability in electrically demanding environments.
Functions and Equipment in Detail
The device features 3 closed contacts in the main circuit and integrated auxiliary contacts with one closed and one open contact. The auxiliary contacts are mechanically linked and comply with IEC 60947-5-1, ensuring safe and reliable signal transmission. Additionally, a mirror contact (1 open) is included, suitable for safety applications according to IEC 60947-4-1. The operating time is 77 ±15 % ms for closing and 25 ±20 % ms for opening, enabling fast response. The maximum operating rate is 3600 switching cycles per hour at 60 °C, suitable for high operational loads.
Technology Explained Simply
The contactor coil is designed for 12 V DC and features integrated bidirectional peak-limiting diode suppressor technology, which limits voltage spikes when the coil is de-energized. This protects control electronics and reduces network interference. The rated impulse voltage withstand is 6 kV, ensuring high insulation strength and safety during overvoltage events. The overvoltage category III and pollution degree 3 make the device suitable for industrial environments with increased contamination risk. The rated insulation voltage is 690 V for both power and signal circuits, enabling use in high-voltage installations.
Compatibility and Accessories
The contactor is equipped with compatibility code LC1D, allowing use with compatible accessories such as motor protection relays (e.g. LRD22), auxiliary switch blocks (e.g. LADN02A, LADN11A), or time blocks (e.g. LADT0, LADT2). The SnapIN connection terminals ensure fast, secure, and maintenance-free electrical connections. The mechanically coupled contacts and mirror contacts meet safety requirements according to EN/ISO 13849-1, with a safety level B10d of 20,000,000 cycles under mechanical load.
Mounting and Installation
Mounting is done via SnapIN connection terminals, enabling simple and secure connections. Dimensions are 45 mm (width) × 110 mm (height) × 95 mm (depth), allowing installation in standard control panels. Installation requires no additional tools, as the terminals are fixed by pressure locking. The associated fuse for the signal circuit is 10 A gG, according to IEC 60947-5-1.
Operational Advantages
The contactor offers a high mechanical life of 30 million switching cycles and an electrical life of 1.4 million cycles at 40 A AC-1. The low pickup power of 2.4 W at 20 °C reduces energy consumption. The integrated coil protection and robust construction ensure high reliability and low maintenance. The use of mechanically linked auxiliary contacts and mirror contacts increases safety in critical applications.