| Additional features |
| Motor power (kW) | 5.5 kW at 220 - 230 V AC 50/60 Hz (AC-3); 11 kW at 380 - 400 V AC 50/60 Hz (AC-3); 11 kW at 415 - 440 V AC 50/60 Hz (AC-3); 15 kW at 500 V AC 50/60 Hz (AC-3); 15 kW at 660 - 690 V AC 50/60 Hz (AC-3); 5.5 kW at 400 V AC 50/60 Hz (AC-4); 5.5 kW at 220 - 230 V AC 50/60 Hz (AC-3e); 11 kW at 380 - 400 V AC 50/60 Hz (AC-3e); 11 kW at 415 - 440 V AC 50/60 Hz (AC-3e); 15 kW at 500 V AC 50/60 Hz (AC-3e); 15 kW at 660 - 690 V AC 50/60 Hz (AC-3e) |
| Compatibility code | LC1D |
| Composition of pole contact | 3 S |
| Protection cover | With |
| [Ith] conventional thermal current in free air | 40 A (at 60 °C) for power circuit; 10 A (at 60 °C) for signal circuit |
| [Irms] Rated making capacity | 450 A at 440 V for circuit conforming to IEC 60947; 140 A AC for signal circuit conforming to IEC 60947-5-1; 250 A DC for signal circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 450 A at 440 V for circuit complies with IEC 60947 |
| [Icw] rated short-time current withstand | 240 A 40 °C - 10 s for circuit; 380 A 40 °C - 1 s for circuit; 50 A 40 °C - 10 min for circuit; 120 A 40 °C - 1 min for circuit; 100 A - 1 s for signal circuit; 120 A - 500 ms for signal circuit; 140 A - 100 ms for signal circuit |
| Associated fuse | 10 A gG for signal circuit, compliant with IEC 60947-5-1; 63 A gG at |
| Average impedance | 2 MOhm - Ith 40 A 50 Hz for circuit |
| Power dissipation per pole | 1,25 W AC-3; 1,25 W AC-3e; 3,2 W AC-1 |
| [Ui] Rated insulation voltage | Circuit: 690 V according to IEC 60947-4-1; Signal circuit: 690 V according to IEC 60947-1 |
| Over voltage category | III |
| Pollution degree | 3 |
| [Uimp] Rated impulse voltage withstand | 6 kV corresponds to IEC 60947 |
| Security level rating | B10d = 1369863 cycles contactor with rated load corresponds to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load corresponds to EN/ISO 13849-1 |
| Mechanical life | 30 Mcycles |
| Electrical lifetime | 1.4 Mcycles 40 A AC-1 at Ue |
| Control circuit type | DC low power consumption |
| Coil technology | Integrated bidirectional transient voltage suppressor diodes |
| Control circuit voltage limits | 0.1 - 0.3 Uc (-40…70 °C): drop voltage DC; 0.8 - 1.25 Uc (-40…60 °C): operation DC; 1 - 1.25 Uc (60…70 °C): operation DC |
| Input power in VA | 2.4 W (at 20 °C) |
| Absorption power in W | 2.4 W (at 20 °C) |
| Operating time | 77 ±15 % ms closing; 25 ±20 % ms opening |
| Time constant | 40 ms |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Configuration of auxiliary contacts | 1 S + 1 Ö |
| Type of auxiliary contacts | Mechanically linked type 1 S + 1 NC complies with IEC 60947-5-1; Mirror contact type 1 NO complies with IEC 60947-4-1 |
| Signalling angular frequency | 25 - 400 Hz |
| Min. switching voltage | 17 V for signal circuit |
| Min. switching current | 5 mA for signal circuit |
| Insulation resistance | > 10 MΩ for signal circuits |
| Non-overlapping time | 1.5 ms with switching between normally open and normally closed contact; 1.5 ms with actuation between normally open and normally closed contact |
| Mounting bracket | Plate; rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Application of contactor | Motor control; resistive load |
| Application category | AC-1; AC-3; AC-3e; AC-4 |
| Pole description | 3P |
| [Ue] Rated operational voltage | Circuit: |
| [Ie] rated operational current | 25 A (at |
| [Uc] control circuit voltage | 48 V DC |
| Mounting |
| Standards | EN 60947-4-1; IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No. 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ |
| Product certifications | CB control; CCC; cULus; CE; UKCA; EU-RO-MR by DNV |
| Degree of protection (IP) | IP20 front side corresponds to IEC 60529 |
| Protection treatment | TH corresponds to IEC 60068-2-30 |
| Climate resistance | Complies with IACS E10 damp heat exposure; complies with IEC 60947-1 Annex Q Category D damp heat exposure |
| Device ambient temperature | -40…60 °C; 60…70 °C with power reduction |
| Operating altitude | 0 - 3.000 m |
| Fire-resistance | 850 °C corresponds to IEC 60695-2-1 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5 - 300 Hz); Vibrations contactor closed (4 Gn, 5 - 300 Hz); Shocks contactor closed (15 Gn for 11 ms); Shocks contactor open (8 Gn for 11 ms) |
| Height | 110 mm |
| Width | 45 mm |
| Depth | 101 mm |
| Product weight | 624 g |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 5,500 cm |
| VPE 1 width | 10,500 cm |
| VPE 1 length | 11,000 cm |
| Packaging weight (Lbs) | 640,000 g |
| VPE 2 type | S02 |
| VPE 2 quantity | 15 |
| VPE 2 height | 15,000 cm |
| VPE 2 width | 30,000 cm |
| VPE 2 length | 40,000 cm |
| VPE 2 weight | 9,902 kg |
Leistungsschütz TeSys DECA. 3 polig, 3 Schließer. Zusätzliche Hilfskontakte- 1 Schließer + 1 Öffner, Bemessungsbetriebsleistung bei AC-3, 400 V 11 kW, Bemessungsbetriebsstrom Ie bei AC-3, 400 V 25 A, Spule 48 V DC. Abmessung (BxHxT) 45x110x95 mm, Gewicht 0,32 kg. Kategorie AC-3, AC-1, AC-4. integrierte bidirektionale Amplitudenbegrenzerdiode. Schnelle, sichere und wartungsfreie Stromverbindung mit SnapIN Anschlussklemme. Geeignet für Sicherheitsanwendungen durch mechanisch gekoppelte Kontakte und Spiegelkontakte.