| Complementary |
| Compatibility code | LC1D |
| Pole contact composition | 2 NO + 2 NC |
| Protective cover | With |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit; 40 A (at 60 °C) for power circuit |
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 450 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 450 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 240 A 40 °C - 10 s for power circuit; 380 A 40 °C - 1 s for power circuit; 50 A 40 °C - 10 min for power circuit; 120 A 40 °C - 1 min for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 63 A gG at |
| Average impedance | 2 mOhm - Ith 40 A 50 Hz for power circuit |
| Power dissipation per pole | 3.2 W AC-1 |
| [Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 15 Mcycles |
| Electrical durability | 1.4 Mcycles 40 A AC-1 at Ue |
| Control circuit type | AC at 50/60 Hz |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.3...0.6 Uc (-40…60 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz |
| Inrush power in VA | 70 VA 60 Hz cos phi 0.75 (at 20 °C); 70 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Hold-in power consumption in VA | 7.5 VA 60 Hz cos phi 0.3 (at 20 °C); 7 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 2…3 W at 50/60 Hz |
| Operating time | 12...22 ms closing; 4...19 ms opening |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Rail; Plate |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; CSA C22.2 No 60947-4-1 |
| Product certifications | UL; CCC; CSA; Marine; UKCA; EAC; CB Scheme |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor open (8 Gn for 11 ms) |
| Height | 91 mm |
| Width | 45 mm |
| Depth | 99 mm |
| Net weight | 0.425 kg |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load |
| Utilisation category | AC-1 |
| Poles description | 4P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 40 A (at |
| [Uc] control circuit voltage | 110 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.800 cm |
| Package 1 Width | 9.500 cm |
| Package 1 Length | 12.000 cm |
| Package 1 Weight | 468.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 16 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 7.990 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 256 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 136.340 kg |
The LC1D258F7 contactor from the TeSys Deca Advanced series by Schneider Electric is a 4-pole contactor designed for use in industrial applications. It is designed for resistive loads and corresponds to usage category AC-1. The device features a coil with a control circuit voltage of 110 V AC at 50/60 Hz and is rated for an operational rated current of 40 A. The contact configuration in the main circuit includes 2 normally open contacts and 2 normally closed contacts, supplemented by additional auxiliary contacts with 1 normally open and 1 normally closed contact, mechanically linked to ensure secure signal transmission. The auxiliary contacts comply with standards IEC 60947-5-1 and IEC 60947-4-1, with the mirror contact suitable for additional safety applications.
Applications
This contactor is designed for use in industrial applications, particularly in applications with resistive loads, such as heaters, dynamic brakes, or other consumers that do not represent inductive or capacitive loads. Category AC-1 ensures reliability during continuous operation under rated load. The high rated breaking capacity of 450 A at 440 V enables use in systems with high inrush currents. The rated impulse voltage withstand of 6 kV and overvoltage category III make the device suitable for environments with increased electrical stress. The insulation strength is 690 V in the main circuit and control circuit, enabling use in systems with high voltages.
Functions and Equipment in Detail
The contactor features coil technology without an integrated wiring module, enabling simple installation and maintenance. The contacts are equipped with Everlink and spring terminals, ensuring a secure and long-lasting electrical connection. The mechanical life is 15 million switching cycles, and the electrical life is 1.4 million switching cycles at 40 A AC-1 and rated voltage. The operating time is 12–22 ms for closing and 4–19 ms for opening. The maximum operating rate is 3600 switching operations per hour at 60 °C. The pickup power is 70 VA at 50/60 Hz, and the holding power consumption is 7 VA at 50 Hz and 7.5 VA at 60 Hz. The heat dissipation is between 2 and 3 W at 50/60 Hz.
Technology Explained Simply
The contactor coil is powered by 110 V AC and mechanically actuates the main contacts and auxiliary contacts. The control circuit voltage limits are 0.3 to 0.6 Uc for release and 0.8 to 1.1 Uc for operation, with exact values varying by frequency. The rated short-time current withstand is 240 A for 10 seconds and 380 A for 1 second in the main circuit, ensuring stability during short-term overloads. The conventional thermal current withstand is 40 A in the main circuit and 10 A in the control circuit at 60 °C. The average impedance is 2 MΩ at 40 A and 50 Hz in the main circuit.
Compatibility and Accessories
The contactor is compatible with various accessories, including auxiliary switch blocks such as LADN31 (3NO1NC), LADN22 (2NO2NC), LADN40 (4NO), LADN11 (1NO1NC), LADN04 (4NC), LADN02 (2NC), LADN22S (2NO2NC), LAD8N20 (2NO side-mounted), LAD8N02 (2NC side-mounted), delayed auxiliary switch block LAD-S2 (1–30 seconds), time blocks such as LADR0 (0.10–3.00 s), LADR2 (1–30.00 s), LADT4 (10.00–180.00 s), LADT2 (0.10–30.00 s), and wiring modules such as LAD4RCG (50–127 V AC) and LAD4RCU (110–250 VAC). Protective covers such as LAD9ET1 and LAD9ET1S are available for LC1 D09–D38 and DT20–DT40 modules. Additionally, the motor protection circuit breaker GV2LE22 (3-pole, 25A, magnetic trip) is available as a supplement.
Mounting and Installation
Mounting is done via screw terminals with a tightening torque of 1.7 Nm for the control circuit and 1.8 Nm for the main circuit. The terminals are designed for screwdrivers with flat Ø 6, Phillips No. 2, and Pozidriv No. 2. Dimensions are 45 mm width, 105 mm height, and 99 mm depth. The device is equipped with a safety cover ensuring secure operation. Installation is carried out in standard control panels or enclosures, with electrical and mechanical requirements of standards IEC 60947-4-1, IEC 60947-5-1, and EN/ISO 13849-1 to be considered.
Operational Advantages
The contactor offers high reliability through mechanically linked auxiliary contacts and robust construction. The long service life and high operating rate make it suitable for continuous use. Simple mounting and maintenance via Everlink and spring terminals reduce installation time. Certifications according to GL, CCC, RINA, DNV, CSA, BV, GOST, UL, and LROS (Lloyds Register of Shipping) confirm suitability for international applications, particularly in shipping and machinery. The safety cover and mechanical connection of auxiliary contacts increase operational safety.
Safety Level and Compliance with Standards
The device complies with safety level B10d = 1369863 cycles at rated load and B10d = 20000000 cycles at mechanical load according to EN/ISO 13849-1. Overvoltage category III and pollution degree 3 ensure suitability for industrial environments with increased pollution risk. The rated insulation voltage of 690 V in the main and control circuits, along with certifications according to IEC 60947-4-1, IEC 60947-5-1, and CSA/UL, confirm compliance with international standards.