| Complementary |
| Motor power kW | 5.5 kW at 220/230 V AC 50/60 Hz (AC-3); 11 kW at 380/400 V AC 50/60 Hz (AC-3); 11 kW at 415/440 V AC 50/60 Hz (AC-3); 15 kW at 500 V AC 50/60 Hz (AC-3); 15 kW at 660/690 V AC 50/60 Hz (AC-3); 5.5 kW at 220/230 V AC 50/60 Hz (AC-3e); 11 kW at 380/400 V AC 50/60 Hz (AC-3e); 11 kW at 415/440 V AC 50/60 Hz (AC-3e); 15 kW at 500 V AC 50/60 Hz (AC-3e); 15 kW at 660/690 V AC 50/60 Hz (AC-3e); 5.5 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power hp | 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors; 2 hp at 115 V AC 50/60 Hz for 1 phase motors; 7.5 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 15 hp at 460/480 V AC 50/60 Hz for 3 phases motors; 20 hp at 575/600 V AC 50/60 Hz for 3 phases motors; 7.5 hp at 200/208 V AC 50/60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit; 40 A (at 60 °C) for power circuit |
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 450 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 450 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 240 A 40 °C - 10 s for power circuit; 380 A 40 °C - 1 s for power circuit; 50 A 40 °C - 10 min for power circuit; 120 A 40 °C - 1 min for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 63 A gG at |
| Average impedance | 2 mOhm - Ith 40 A 50 Hz for power circuit |
| Power dissipation per pole | 3.2 W AC-1; 1.25 W AC-3; 1.25 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 15 Mcycles |
| Electrical durability | 1.65 Mcycles 25 A AC-3 at Ue |
| Control circuit type | AC at 50/60 Hz |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz |
| Inrush power in VA | 70 VA 60 Hz cos phi 0.75 (at 20 °C); 70 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Hold-in power consumption in VA | 7.5 VA 60 Hz cos phi 0.3 (at 20 °C); 7 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 2…3 W at 50/60 Hz |
| Operating time | 12...22 ms closing; 4...19 ms opening |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Connections - terminals | Control circuit: lugs-ring terminals - external diameter: 8 mm; Power circuit: lugs-ring terminals - external diameter: 10 mm |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Rail; Plate |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; CSA C22.2 No 60947-4-1 |
| Product certifications | UL; CCC; CSA; Marine; UKCA; EAC; CB Scheme |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor open (8 Gn for 11 ms) |
| Height | 85 mm |
| Width | 45 mm |
| Depth | 92 mm |
| Net weight | 0.37 kg |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load; Motor control |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 25 A (at |
| [Uc] control circuit voltage | 200 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.500 cm |
| Package 1 Width | 9.500 cm |
| Package 1 Length | 12.000 cm |
| Package 1 Weight | 424.000 g |
The LC1D256L7 contactor from the TeSys Deca Advanced series by Schneider Electric is a 3-pole contactor for controlling motors and resistive loads. It features a main contact configuration of 3 closers and integrated auxiliary contacts with 1 closer and 1 opener. The coil is designed for a control circuit voltage of 200 V AC at 50/60 Hz. The device is suitable for usage categories AC-1, AC-3, AC-3e, and AC-4, achieving a rated operational power of 11 kW and a rated operational current of 25 A at AC-3 and 400 V AC. The rated operational voltage for the circuit is up to 690 V, with insulation strength according to IEC 60947-4-1 and UL/CSA certification up to 600 V. The overvoltage category III and pollution degree 3 make the contactor suitable for industrial applications with increased loads. The rated impulse voltage withstand is 6 kV, ensuring high electrical safety.
Applications
This contactor is primarily designed for motor control, especially for drives with a power of up to 11 kW at 400 V AC (AC-3). It is also suitable for resistive loads and can be used in systems with high switching cycles. Approvals from RINA, CCC, BV, UL, LROS, DNV, GL, CSA, and GOST enable its use in international markets, including marine and industrial applications. The mechanical life is 15 million switching cycles, and the electrical life is 1.65 million cycles at 25 A AC-3 and rated voltage, ensuring high operational reliability over a long period.
Functions and Equipment in Detail
The contactor features a safety cover that enables mechanical interlocking of contacts and mirror contacts, making it suitable for safety applications. Current connections are made via Everlink and spring terminals, ensuring a secure and long-lasting connection. The coil technology is designed without an integrated wiring module, enabling easy installation and maintenance. The operating time ranges between 12 and 22 seconds, which is sufficient for most industrial applications. The power loss is 1.25 W per pole at AC-3 and AC-3e, ensuring efficient heat dissipation.
Technology Explained Simply
The control circuit voltage of 200 V AC is supplied via terminals A1 and A2. The coil consumes 70 VA during operation at 50 Hz (cos φ 0.75) and 7.5 VA in holding mode at 60 Hz (cos φ 0.3). The rated short-time current withstand is 240 A at 40 °C and 10 seconds for the circuit, ensuring high stability during short-term overloads. The rated breaking capacity is 450 A at 440 V, describing the contactor’s ability to safely interrupt loads under defined conditions. The conventional thermal current rating is 40 A for the circuit at 60 °C, defining the thermal load capacity under normal operating conditions.
Compatibility and Accessories
The contactor is compatible with various accessory modules, including time modules such as LA4-DT0U (0.1–2 s) or LA4-DT2U (1.5–30 s), and auxiliary switch blocks such as LADN136 (1S3O) or LADN206 (2S). Additionally, time blocks like LADT46 (1S1O, delayed pickup) and interface modules like LA4-DFB are available. These modules extend the functionality of the contactor for specific applications such as time delays, additional switching functions, or integration into higher-level control systems.
Mounting and Installation
Mounting is done via a standard plug connection, with device dimensions of 45 mm (width) × 85 mm (height) × 92 mm (depth). Spring terminals allow for quick and secure wire connections, with cross-section ratings of 1 to 4 mm² for main circuits (LC1D25) and 1 to 2.5 mm² for auxiliary contacts. Installation is in standard control panels, with a weight of 0.37 kg facilitating handling. The operating temperature range is from -40 °C to +70 °C, with operating voltage limits of 0.8–1.1 Uc (at -40…60 °C).
Operational Advantages
The contactor offers high operational reliability through mechanically interlocked contacts and mirror contacts, which is crucial for safety applications. The long service life and low power loss ensure reliable and energy-efficient operation. Compatibility with various accessory modules allows flexible adaptation to specific requirements. Certifications according to international standards ensure usability in various markets and industries. Easy installation and maintenance via Everlink and spring terminals reduce installation effort and maintenance time.