| Complementary |
| Motor power kW | 5.5 kW at 220/230 V AC 50/60 Hz (AC-3); 11 kW at 380/400 V AC 50/60 Hz (AC-3); 11 kW at 415/440 V AC 50/60 Hz (AC-3); 15 kW at 500 V AC 50/60 Hz (AC-3); 15 kW at 660/690 V AC 50/60 Hz (AC-3); 5.5 kW at 220/230 V AC 50/60 Hz (AC-3e); 11 kW at 380/400 V AC 50/60 Hz (AC-3e); 11 kW at 415/440 V AC 50/60 Hz (AC-3e); 15 kW at 500 V AC 50/60 Hz (AC-3e); 15 kW at 660/690 V AC 50/60 Hz (AC-3e); 5.5 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power hp | 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors; 2 hp at 115 V AC 50/60 Hz for 1 phase motors; 7.5 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 15 hp at 460/480 V AC 50/60 Hz for 3 phases motors; 20 hp at 575/600 V AC 50/60 Hz for 3 phases motors; 7.5 hp at 200/208 V AC 50/60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit; 40 A (at 60 °C) for power circuit |
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 450 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 450 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 240 A 40 °C - 10 s for power circuit; 380 A 40 °C - 1 s for power circuit; 50 A 40 °C - 10 min for power circuit; 120 A 40 °C - 1 min for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 63 A gG at |
| Average impedance | 2 mOhm - Ith 40 A 50 Hz for power circuit |
| Power dissipation per pole | 3.2 W AC-1; 1.25 W AC-3; 1.25 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 15 Mcycles |
| Electrical durability | 1.65 Mcycles 25 A AC-3 at Ue |
| Control circuit type | AC at 50/60 Hz |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz |
| Inrush power in VA | 70 VA 60 Hz cos phi 0.75 (at 20 °C); 70 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Hold-in power consumption in VA | 7.5 VA 60 Hz cos phi 0.3 (at 20 °C); 7 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 2…3 W at 50/60 Hz |
| Operating time | 12...22 ms closing; 4...19 ms opening |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Connections - terminals | Control circuit: lugs-ring terminals - external diameter: 8 mm; Power circuit: lugs-ring terminals - external diameter: 10 mm |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Plate; Rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; CSA C22.2 No 60947-4-1 |
| Product certifications | UL; CCC; CSA; Marine; UKCA; EAC; CB Scheme |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor open (8 Gn for 11 ms) |
| Height | 85 mm |
| Width | 45 mm |
| Depth | 92 mm |
| Net weight | 0.37 kg |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load; Motor control |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 25 A (at |
| [Uc] control circuit voltage | 120 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.600 cm |
| Package 1 Width | 9.500 cm |
| Package 1 Length | 11.700 cm |
| Package 1 Weight | 38.000 g |
The LC1D256G7 contactor from the TeSys Deca Advanced series by Schneider Electric is a 3-pole contactor for controlling electrical loads, particularly for motor drives and resistive loads. It is designed for use in industrial installations where reliable and safe switching performance under high loads is required. The device features a control circuit voltage of 120 V AC at 50/60 Hz and is rated for an operational rated current of 25 A. The rated operational power is 11 kW at 400 V AC in usage category AC-3, making it suitable for controlling motors in typical industrial applications. Additionally, auxiliary contacts are integrated: 1 normally closed contact and 1 normally open contact, which can be used for controlling auxiliary functions or signal transmission.
Applications
The contactor is intended for various usage categories, including AC-1 (resistive load), AC-3 (motors with direct start), AC-3e (motors with reduced starting torque), and AC-4 (motors with frequent starts and stops). Motor power ratings vary depending on operating voltage, with 11 kW (AC-3) and 5.5 kW (AC-4) achievable at 400 V AC. The application also includes control of 3-phase motors across various voltage ranges, with power ratings applying to UL/CSA-certified products. Certifications according to BV, RINA, LROS, UL, CSA, DNV, CCC, GL, and GOST make the device suitable for international applications, including shipping and industrial automation.
Functions and Equipment in Detail
The contactor features a safety cover that allows protected access to the contacts. Current connections are made using Everlink technology and spring terminals, ensuring a secure and long-lasting connection. The contacts are mechanically coupled and feature mirror contacts, increasing reliability in safety applications. The coil technology is designed without an integrated wiring module, enabling simple installation and maintenance. The control circuit voltage limits range from 0.3 to 0.6 Uc for release and from 0.8 to 1.1 Uc for operation, with exact values varying depending on frequency and temperature.
Technology Explained Simply
The rated insulation voltage is 690 V for the power circuit and complies with IEC 60947-4-1 and IEC 60947-1 for the signal circuit. Overvoltage category III and pollution degree 3 indicate suitability for industrial environments with increased contamination risk. The rated impulse withstand voltage is 6 kV, ensuring high electrical strength. The rated breaking capacity is 450 A at 440 V, highlighting the contactor’s ability to interrupt short-circuit currents. The mechanical life is 15 million switching cycles, and the electrical life is 1.65 million cycles at 25 A AC-3. The power loss per pole is 3.2 W at AC-1 and 1.25 W at AC-3 and AC-3e, indicating efficient heat dissipation.
Compatibility and Accessories
The contactor is compatible with various accessories, including auxiliary switch blocks such as LADN046 (4NC non-delayed), LADN226 (2NO2NC), LADN316 (3NO1NC), and LADN116 (1NO1NC), which can be used for additional control functions. Time delay blocks such as LADT26 (delayed pickup) and LADS26 (delayed release) enable time-controlled switching operations. Other components include varistors (LAD-4VU), interlocking blocks (LAD6K10F), protective covers (LAD9ET1S), and motor protection circuit breakers (GV2LE22). These accessories extend the functionality of the contactor and allow adaptation to specific requirements.
Mounting and Installation
Mounting is done via standard plug-in connection or screw fastening. Dimensions are 45 mm (width) × 85 mm (height) × 92 mm (depth), enabling compact integration into enclosures. Weight is 0.37 kg. Spring terminals and Everlink technology ensure quick and secure connections. Installation is carried out in accordance with applicable standards and safety regulations, with certifications confirming compliance with international standards.
Operational Advantages
The contactor offers high operational safety through mechanically coupled contacts and mirror contacts, ensuring reliable switching performance even under high loads. The long service life and low power loss reduce maintenance requirements and operating costs. Compatibility with various accessories allows flexible adaptation to different applications. Certifications according to international standards guarantee suitability for global markets, including shipping and industrial automation. The control circuit voltage of 120 V AC and rating for 25 A make the device suitable for a wide range of applications, from small motors to larger industrial drives.