| Complementary |
| Motor power kW | 4 kW at 220/230 V AC 50/60 Hz (AC-3); 7.5 kW at 380/400 V AC 50/60 Hz (AC-3); 9 kW at 415/440 V AC 50/60 Hz (AC-3); 10 kW at 500 V AC 50/60 Hz (AC-3); 10 kW at 660/690 V AC 50/60 Hz (AC-3); 4 kW at 220/230 V AC 50/60 Hz (AC-3e); 7.5 kW at 380/400 V AC 50/60 Hz (AC-3e); 9 kW at 415/440 V AC 50/60 Hz (AC-3e); 10 kW at 500 V AC 50/60 Hz (AC-3e); 10 kW at 660/690 V AC 50/60 Hz (AC-3e); 4 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power hp | 1 hp at 115 V AC 50/60 Hz for 1 phase motors; 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors; 5 hp at 200/208 V AC 50/60 Hz for 3 phases motors; 5 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 10 hp at 460/480 V AC 50/60 Hz for 3 phases motors; 15 hp at 575/600 V AC 50/60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit; 32 A (at 60 °C) for power circuit |
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 300 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 300 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 145 A 40 °C - 10 s for power circuit; 240 A 40 °C - 1 s for power circuit; 40 A 40 °C - 10 min for power circuit; 84 A 40 °C - 1 min for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 50 A gG at |
| Average impedance | 2.5 mOhm - Ith 32 A 50 Hz for power circuit |
| Power dissipation per pole | 2.5 W AC-1; 0.8 W AC-3; 0.8 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 15 Mcycles |
| Electrical durability | 1.65 Mcycles 18 A AC-3 at Ue |
| Control circuit type | AC at 50/60 Hz standard |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz |
| Inrush power in VA | 70 VA 60 Hz cos phi 0.75 (at 20 °C); 70 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Hold-in power consumption in VA | 7.5 VA 60 Hz cos phi 0.3 (at 20 °C); 7 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 2…3 W at 50/60 Hz |
| Operating time | 12...22 ms closing; 4...19 ms opening |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Rail; Plate |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; CSA C22.2 No 60947-4-1 |
| Product certifications | UL; CCC; CSA; Marine; UKCA; EAC; CB Scheme |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor open (10 Gn for 11 ms) ; Shocks contactor closed (15 Gn for 11 ms) |
| Height | 77 mm |
| Width | 45 mm |
| Depth | 86 mm |
| Net weight | 0.33 kg |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Motor control; Resistive load |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 18 A (at |
| [Uc] control circuit voltage | 230 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.000 cm |
| Package 1 Width | 9.000 cm |
| Package 1 Length | 11.000 cm |
| Package 1 Weight | 343.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 20 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 7.150 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 320 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 126.500 kg |
The LC1D18P7 contactor from the TeSys Deca Advanced series by Schneider Electric is a 3-pole contactor for motor control and operation with resistive loads. It is designed for use in industrial plants where reliable and safe switching functions are required for medium power applications. The device has a rated operational current of 18 A at a rated operational voltage of 400 V AC in usage category AC-3, covering a motor power of 7.5 kW. The control circuit voltage is 230 V AC at 50/60 Hz, making it suitable for standard industrial applications. The contact configuration includes 3 closed contacts in the main current circuit, plus additional auxiliary contacts in the configuration of 1 closed + 1 open, which can be used for signaling and control tasks.
Applications
The contactor is designed for various usage categories, including AC-3, AC-3e, AC-1, and AC-4. Category AC-3 refers to operation with three-phase motors under normal load conditions, while AC-3e is intended for operation with three-phase motors under increased load (e.g., in crane applications). Category AC-4 covers applications with high inrush currents, such as those occurring during frequent starting operations or with drives requiring high torque. The rated insulation voltage is 690 V for the circuit, complying with IEC 60947-4-1 standards, allowing the device to be used in installations requiring higher voltage safety. Overvoltage category III and pollution degree 3 indicate suitability for industrial environments with increased stress from voltage surges and contamination.
Functions and Equipment in Detail
The contactor has a mechanical life of 15 million switching cycles and an electrical life of 1.65 million cycles at 18 A AC-3, indicating high reliability and durability. The power loss per pole is 0.8 W at AC-3 and AC-3e, ensuring efficient heat dissipation and low thermal stress. Heat dissipation ranges between 2 and 3 W at 50/60 Hz. The operating time is 12 to 22 ms, enabling fast switching response. The coil is designed without an integrated control module, allowing for simple installation and maintenance. Contacts are equipped with Everlink and spring terminals, ensuring a secure and long-lasting electrical connection. Mechanically interlocked contacts and mirror contacts make the device suitable for safety applications, as they guarantee secure locking of switching states.
Technology Explained Simply
The rated short-time withstand current is 145 A for 10 seconds and 240 A for 1 second for the circuit, demonstrating the contactor’s ability to handle temporary overloads under transient conditions. The rated breaking capacity is 300 A at 440 V, highlighting its capability to safely interrupt short-circuit currents. The rated making capacity is 300 A at 440 V for the circuit, indicating its ability to safely close under load conditions. The rated impulse withstand voltage is 6 kV, ensuring insulation strength against electrical overvoltages. The control circuit voltage limits range from 0.3 to 0.6 Uc for drop-out voltage and from 0.8 to 1.1 Uc for operation, ensuring stable function even with voltage fluctuations. The pickup power is 70 VA at 50/60 Hz, and the holding power consumption is 7 VA at 50 Hz and 7.5 VA at 60 Hz.
Compatibility and Accessories
The contactor is equipped with compatibility code LC1D, enabling the use of suitable accessories such as auxiliary switch blocks (e.g., LAD8N02, LADN22S), time modules (e.g., LA4-DT2U, LADR0), interlocking blocks (e.g., LAD6K10M), and motor protection switches (e.g., GV2P20, GV2L20). These components can be used to extend functionality, introduce time delays, or provide mechanical interlocking in control systems. The safety cover is integrated as standard, supporting compliance with safety regulations during installation and maintenance.
Mounting and Installation
Mounting is done via screw terminals, with device dimensions of 45 mm (width) × 77 mm (height) × 86 mm (depth). The weight is 0.33 kg. Installation is quick and easy, as spring terminals and Everlink technology enable secure connections without additional tools. Certifications according to UL, CSA, GOST, CCC, DNV, RINA, BV, GL, and LROS (Lloyds Register of Shipping) demonstrate international recognition and suitability for various markets and applications, including marine and industrial environments.
Operational Advantages
The contactor offers high operational safety through mechanically interlocked contacts and mirror contacts, enabling secure state monitoring. Long service life and low power loss ensure efficient and low-maintenance operation. Compatibility with various accessories allows flexible adaptation to specific requirements. Certifications and compliance with international standards (IEC 60947, EN/ISO 13849-1) guarantee reliability and safety in industrial use. The operating time of 12 to 22 ms enables fast response in control systems. The integrated safety cover supports compliance with occupational safety regulations during installation and maintenance.
Safety Level
The contactor meets safety level requirements of B10d = 1369863 cycles at rated load and B10d = 20000000 cycles at mechanical load according to EN/ISO 13849-1, confirming its suitability for safety-critical applications. The mechanical life of 15 million cycles and electrical life of 1.65 million cycles underscore the robustness and reliability of the device.
Certifications
The device is certified according to UL, CSA, GOST, CCC, DNV, RINA, BV, GL, and LROS (Lloyds Register of Shipping), confirming international recognition and suitability for various markets and applications, including marine and industrial environments. Product standards comply with IEC 60947-4-1, IEC 60947-1, and EN/ISO 13849-1.