| Complementary |
| Motor power kW | 4 kW at 220/230 V AC 50/60 Hz (AC-3); 7.5 kW at 380/400 V AC 50/60 Hz (AC-3); 9 kW at 415/440 V AC 50/60 Hz (AC-3); 10 kW at 500 V AC 50/60 Hz (AC-3); 10 kW at 660/690 V AC 50/60 Hz (AC-3); 4 kW at 220/230 V AC 50/60 Hz (AC-3e); 7.5 kW at 380/400 V AC 50/60 Hz (AC-3e); 9 kW at 415/440 V AC 50/60 Hz (AC-3e); 10 kW at 500 V AC 50/60 Hz (AC-3e); 10 kW at 660/690 V AC 50/60 Hz (AC-3e); 4 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power hp | 1 hp at 115 V AC 50/60 Hz for 1 phase motors; 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors; 5 hp at 200/208 V AC 50/60 Hz for 3 phases motors; 5 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 10 hp at 460/480 V AC 50/60 Hz for 3 phases motors; 15 hp at 575/600 V AC 50/60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit; 32 A (at 60 °C) for power circuit |
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 300 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 300 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 145 A 40 °C - 10 s for power circuit; 240 A 40 °C - 1 s for power circuit; 40 A 40 °C - 10 min for power circuit; 84 A 40 °C - 1 min for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 50 A gG at |
| Average impedance | 2.5 mOhm - Ith 32 A 50 Hz for power circuit |
| Power dissipation per pole | 2.5 W AC-1; 0.8 W AC-3; 0.8 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 15 Mcycles |
| Electrical durability | 1.65 Mcycles 18 A AC-3 at Ue |
| Control circuit type | AC at 50/60 Hz standard |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz |
| Inrush power in VA | 70 VA 60 Hz cos phi 0.75 (at 20 °C); 70 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Hold-in power consumption in VA | 7.5 VA 60 Hz cos phi 0.3 (at 20 °C); 7 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 2…3 W at 50/60 Hz |
| Operating time | 12...22 ms closing; 4...19 ms opening |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Plate; Rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; CSA C22.2 No 60947-4-1 |
| Product certifications | UL; CCC; CSA; Marine; UKCA; EAC; CB Scheme |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor open (10 Gn for 11 ms) ; Shocks contactor closed (15 Gn for 11 ms) |
| Height | 77 mm |
| Width | 45 mm |
| Depth | 86 mm |
| Net weight | 0.33 kg |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load; Motor control |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 18 A (at |
| [Uc] control circuit voltage | 220 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.500 cm |
| Package 1 Width | 10.000 cm |
| Package 1 Length | 12.000 cm |
| Package 1 Weight | 365.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 20 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 7.270 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 320 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 124.976 kg |
The LC1D18M7 contactor from the TeSys Deca Advanced series by Schneider Electric is a 3-pole contactor for controlling electrical loads, particularly for motor drives and resistive loads. It has a rated operational current of 18 A and is designed for a control circuit voltage of 220 V AC at 50/60 Hz. The primary application is motor control, and it is suitable for various usage categories such as AC-1, AC-3, AC-3e, and AC-4. At an operating voltage of 400 V AC and category AC-3, the rated operational power is 7.5 kW. The device is equipped with a safety cover and offers additional auxiliary contacts in the configuration of 1 normally closed + 1 normally open, which can be used for controlling auxiliary functions such as signal indication or feedback.
Applications
This contactor is suitable for industrial applications where reliable and safe switching functions for three-phase motors are required. It is commonly used in machine building, conveying technology, pump and fan systems, as well as in process engineering. The combination of mechanically coupled contacts and mirror contacts also makes it suitable for safety applications where secure disconnection of circuits is required. Certifications according to GOST, UL, RINA, CCC, DNV, BV, GL, CSA, and LROS (Lloyds Register of Shipping) confirm its suitability for international and maritime operating conditions.
Functions and Equipment in Detail
The contactor features a contact configuration of 3 normally open contacts in the main circuit and an additional auxiliary contact block with 1 normally open and 1 normally closed contact. The contacts are equipped with Everlink technology and spring terminals, ensuring a secure and long-lasting electrical connection. The coil is designed for 220 V AC and operates at frequencies of 50/60 Hz. The operating voltage ranges are defined: for operation, the range is 0.8 to 1.1 times nominal voltage (at 50 Hz) or 0.85 to 1.1 times nominal voltage (at 60 Hz), while the release voltage is 0.3 to 0.6 times nominal voltage. The pickup power is 70 VA at 50/60 Hz, and the holding power consumption is 7 VA (50 Hz) or 7.5 VA (60 Hz). The heat dissipation is between 2 and 3 W at 50/60 Hz.
Technology Explained Simply
The rated insulation voltage is 690 V for the circuit and complies with standards IEC 60947-4-1 and IEC 60947-1. The overvoltage category III and pollution degree 3 indicate suitability for industrial environments with increased stress. The rated impulse voltage withstand is 6 kV, ensuring high electrical strength even under transient voltage surges. The rated breaking capacity is 300 A at 440 V, highlighting the contactor’s ability to interrupt short-circuit currents. The mechanical life is 15 million switching cycles, and the electrical life at 18 A AC-3 and nominal voltage is 1.65 million cycles. The operating time is between 12 and 22 milliseconds.
Compatibility and Accessories
The contactor is equipped with compatibility code LC1D, enabling the use of suitable accessories such as time modules (e.g. LA4-DT0U, LA4-DT2U), auxiliary switch blocks (e.g. LAD8N20, LADN22, LADN13, LADN31, LADN11), protective covers (e.g. LAD9ET1S), time blocks (e.g. LADR0, LADR2, LADT4), and mechanical interlocks (e.g. LAD9V2). Additionally, motor protection circuit breakers such as the GV2LE20 or main current connectors (e.g. LAD9V5, LAD9V6) can be combined. The use of wiring modules such as the LAD4RCU is possible, although the device is delivered standard without an integrated wiring module.
Mounting and Installation
Mounting is done in standard control panels or enclosures. Dimensions are 45 mm (width) × 77 mm (height) × 86 mm (depth). The spring terminals allow for quick and secure connection of wires. Installation instructions are described in the manufacturer’s datasheet. The use of appropriate fuses is required; for the signal circuit, a 10 A gG fuse is recommended.
Operational Advantages
The contactor offers high operational safety through mechanically coupled contacts and mirror contacts, ensuring secure disconnection. Its long service life and robust construction ensure reliable performance even under harsh operating conditions. The quick and easy setup via Everlink technology and spring terminals reduces installation time. Certifications according to international standards and norms enable use in various industries and regions. The power loss per pole is 2.5 W at AC-1 and 0.8 W at AC-3 and AC-3e, ensuring efficient energy use. The rated short-time current withstand is defined for various durations and temperatures, ensuring safe operation even under short-term overloads.
Safety Level and Service Life
The contactor meets the requirements of standard EN/ISO 13849-1 with a safety level B10d of 1,369,863 cycles at rated load and 20,000,000 cycles at mechanical load. The mechanical life is 15 million switching cycles, and the electrical life is 1.65 million cycles at 18 A AC-3 and nominal voltage. The construction is designed for an operating temperature range of -40 °C to +70 °C, with operating voltage ranges varying according to temperature. The conventional thermal current rating is 32 A in the circuit at 60 °C and 10 A in the signal circuit at 60 °C. The rated make capacity is 300 A in the circuit at 440 V and 140 A AC and 250 A DC in the signal circuit, according to IEC 60947.