| Complementary |
| Motor power kW | 4 kW at 220/230 V AC 50/60 Hz (AC-3); 7.5 kW at 380/400 V AC 50/60 Hz (AC-3); 9 kW at 415/440 V AC 50/60 Hz (AC-3); 10 kW at 500 V AC 50/60 Hz (AC-3); 10 kW at 660/690 V AC 50/60 Hz (AC-3); 4 kW at 220/230 V AC 50/60 Hz (AC-3e); 7.5 kW at 380/400 V AC 50/60 Hz (AC-3e); 9 kW at 415/440 V AC 50/60 Hz (AC-3e); 10 kW at 500 V AC 50/60 Hz (AC-3e); 10 kW at 660/690 V AC 50/60 Hz (AC-3e); 4 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power hp | 1 hp at 115 V AC 50/60 Hz for 1 phase motors; 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors; 5 hp at 200/208 V AC 50/60 Hz for 3 phases motors; 5 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 10 hp at 460/480 V AC 50/60 Hz for 3 phases motors; 15 hp at 575/600 V AC 50/60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit; 32 A (at 60 °C) for power circuit |
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 300 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 300 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 145 A 40 °C - 10 s for power circuit; 240 A 40 °C - 1 s for power circuit; 40 A 40 °C - 10 min for power circuit; 84 A 40 °C - 1 min for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 50 A gG at |
| Average impedance | 2.5 mOhm - Ith 32 A 50 Hz for power circuit |
| Power dissipation per pole | 2.5 W AC-1; 0.8 W AC-3; 0.8 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 30 Mcycles |
| Electrical durability | 1.65 Mcycles 18 A AC-3 at Ue |
| Control circuit type | DC standard |
| Coil technology | With integral suppression device |
| Control circuit voltage limits | 0.1...0.25 Uc (-40…70 °C):drop-out DC; 0.7...1.25 Uc (-40…60 °C):operational DC; 1...1.25 Uc (60…70 °C):operational DC |
| Inrush power in W | 5.4 W (at 20 °C) |
| Hold-in power consumption in W | 5.4 W at 20 °C |
| Operating time | 63 ±15 % ms closing; 20 ±20 % ms opening |
| Time constant | 28 ms |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Plate; Rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; CSA C22.2 No 60947-4-1 |
| Product certifications | UL; CCC; CSA; Marine; UKCA; EAC; CB Scheme |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor open (10 Gn for 11 ms) ; Shocks contactor closed (15 Gn for 11 ms) |
| Height | 77 mm |
| Width | 45 mm |
| Depth | 95 mm |
| Net weight | 0.49 kg |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Motor control; Resistive load |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 18 A (at |
| [Uc] control circuit voltage | 24 V DC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.000 cm |
| Package 1 Width | 9.000 cm |
| Package 1 Length | 11.000 cm |
| Package 1 Weight | 522.500 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 15 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 8.150 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 240 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 140.400 kg |
The LC1D18BD contactor from the TeSys Deca Advanced series by Schneider Electric is a 3-pole contactor for motor control and operation of resistive loads. It is designed for use in industrial plants where reliable and safe switching function is required at a rated operational current of 18 A. The control circuit voltage is 24 V DC, enabling integration into systems with direct current supply. The coil features an integrated suppression unit that stabilizes switching operations in the control circuit and prevents unwanted voltage spikes.
Applications
The contactor is designed for usage categories AC-1, AC-3, AC-3e, and AC-4, with AC-3 being the standard category for controlling three-phase motors. At an operating voltage of 400 V AC and a frequency of 50/60 Hz, the motor rated power is 7.5 kW. At other voltage levels, different powers are possible, such as 4 kW at 220/230 V AC or 10 kW at 660/690 V AC. The AC-4 category enables use with high inrush currents, for example with motors starting directly. Certifications according to UL, CSA, CCC, GOST, DNV, GL, RINA, BV, and LROS (Lloyds Register of Shipping) make the device suitable for marine and safety-critical applications.
Functions and Equipment in Detail
The device features three main contacts (3P) and an additional auxiliary contact block with one close contact and one open contact (1S+1Oe). These auxiliary contacts are intended for controlling secondary circuits, such as signal indication or feedback to control devices. The contacts are mechanically coupled and feature mirror contacts, increasing reliability in safety-related applications. The current connection terminals are designed as Everlink and spring terminals, ensuring a secure and long-lasting current connection. The connection terminals require a flat-blade screwdriver with Ø 6 mm.
Technology Explained Simply
The rated insulation voltage is 690 V for the current circuit and complies with standards IEC 60947-4-1 as well as CSA and UL. The overvoltage category III and pollution degree 3 indicate that the device is designed for industrial environments with increased pollution risk. The rated impulse withstand voltage is 6 kV, ensuring high electrical strength under transient voltage stresses. The rated breaking capacity is 300 A at 440 V, meeting the requirements of IEC 60947. The mechanical life is 30 million switching cycles, and the electrical life is 1.65 million switching cycles at 18 A AC-3 and rated voltage. The operating time is 63 ±15 % ms for closing and 20 ±20 % ms for opening.
Compatibility and Accessories
The contactor is equipped with compatibility code LC1D, enabling the use of accessories such as auxiliary contact blocks (e.g. LADN02, LADN04), time blocks (e.g. LADT0, LADT2, LADT4), and main current connectors (e.g. LAD9V5, LAD9V6). Additionally, mechanical interlocks (LAD9V2) and protective covers (LAD9ET1S) are available, supporting integration into enclosures and enhancing operational safety. The use of freewheeling diodes (LAD4DDL) or special diodes (LAD4TBDL) may be required in certain applications to optimize switching operations in the control circuit.
Mounting and Installation
Mounting is done in standard control panels or enclosures. Dimensions are 45 mm (width) × 77 mm (height) × 95 mm (depth). The mounting height and depth are designed for installation in standard control panels. Connection of main and auxiliary contacts is done via screw terminals. The maximum operating rate is 3600 switching cycles per hour at an ambient temperature of 60 °C.
Advantages in Operation
The contactor offers high operational safety through mechanically coupled contacts and mirror contacts. The integrated suppression unit reduces disturbances in the control circuit. The use of Everlink and spring terminals ensures a stable current connection. Certifications according to international standards enable use in various industries, including shipping and industrial automation. The high service life and reliability under heavy loads make the device suitable for demanding applications.