| Complementary |
| Motor power kW | 4 kW at 220/230 V AC 50/60 Hz (AC-3); 7.5 kW at 380/400 V AC 50/60 Hz (AC-3); 9 kW at 415/440 V AC 50/60 Hz (AC-3); 10 kW at 500 V AC 50/60 Hz (AC-3); 10 kW at 660/690 V AC 50/60 Hz (AC-3); 4 kW at 220/230 V AC 50/60 Hz (AC-3e); 7.5 kW at 380/400 V AC 50/60 Hz (AC-3e); 9 kW at 415/440 V AC 50/60 Hz (AC-3e); 10 kW at 500 V AC 50/60 Hz (AC-3e); 10 kW at 660/690 V AC 50/60 Hz (AC-3e); 4 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power hp | 1 hp at 115 V AC 50/60 Hz for 1 phase motors; 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors; 5 hp at 200/208 V AC 50/60 Hz for 3 phases motors; 5 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 10 hp at 460/480 V AC 50/60 Hz for 3 phases motors; 15 hp at 575/600 V AC 50/60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit; 32 A (at 60 °C) for power circuit |
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 300 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 300 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 145 A 40 °C - 10 s for power circuit; 240 A 40 °C - 1 s for power circuit; 40 A 40 °C - 10 min for power circuit; 84 A 40 °C - 1 min for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 50 A gG at |
| Average impedance | 2.5 mOhm - Ith 32 A 50 Hz for power circuit |
| Power dissipation per pole | 2.5 W AC-1; 0.8 W AC-3; 0.8 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 15 Mcycles |
| Electrical durability | 1.65 Mcycles 18 A AC-3 at Ue |
| Control circuit type | AC at 50/60 Hz |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz |
| Inrush power in VA | 70 VA 60 Hz cos phi 0.75 (at 20 °C); 70 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Hold-in power consumption in VA | 7.5 VA 60 Hz cos phi 0.3 (at 20 °C); 7 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 2…3 W at 50/60 Hz |
| Operating time | 12...22 ms closing; 4...19 ms opening |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Connections - terminals | Control circuit: lugs-ring terminals - external diameter: 8 mm; Power circuit: lugs-ring terminals - external diameter: 8 mm |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Rail; Plate |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; CSA C22.2 No 60947-4-1 |
| Product certifications | UL; CCC; CSA; Marine; UKCA; EAC; CB Scheme |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor open (10 Gn for 11 ms) ; Shocks contactor closed (15 Gn for 11 ms) |
| Height | 77 mm |
| Width | 45 mm |
| Depth | 86 mm |
| Net weight | 0.33 kg |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Motor control; Resistive load |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 18 A (at |
| [Uc] control circuit voltage | 120 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 9.4 cm |
| Package 1 Width | 8.1 cm |
| Package 1 Length | 5.4 cm |
| Package 1 Weight | 326.0 g |
| Unit Type of Package 2 | PAL |
| Number of Units in Package 2 | 256 |
| Package 2 Height | 60.0 cm |
| Package 2 Width | 80.0 cm |
| Package 2 Length | 256.0 cm |
| Package 2 Weight | 151.296 kg |
The LC1D186G7 contactor from the TeSys Deca Advanced series by Schneider Electric is a 3-pole contactor for motor control and operation with resistive loads. It features a main contact configuration of 3 closers and integrated auxiliary contacts in the configuration of 1 closer + 1 opener. The control circuit voltage is 120 V AC at 50/60 Hz, making it suitable for standard applications in industrial and commercial electrical installations. The device is designed for usage categories AC-1, AC-3, AC-3e, and AC-4, with a rated operational power of 7.5 kW at AC-3 and 400 V AC. The rated operational current Ie is 18 A under these conditions. The rated operational voltage for the circuit is not explicitly specified, however, the rated insulation voltage for the circuit is specified as 690 V according to IEC 60947-4-1, enabling application in high-voltage installations up to 690 V. The coil technology is designed without an integrated switching module, enabling simple installation and maintenance.
Applications
The contactor is primarily designed for controlling electric motors, particularly in applications with motor power up to 7.5 kW at 400 V AC (AC-3). It can also be used for resistive loads, where usage category AC-1 forms the basis for such applications. Category AC-4 allows use under heavy starting conditions, such as those found in crane or conveyor systems. Certifications according to GOST, CCC, BV, CSA, UL, RINA, GL, DNV, and LROS (Lloyds Register of Shipping) make the device suitable for use in shipping and international industrial facilities. Overvoltage category III and pollution degree 3 indicate that the device is designed for environments with increased electrical stress and contamination risk.
Functions and Equipment in Detail
The contactor features a safety cover that enables mechanical interlocking of contacts, thereby increasing safety during maintenance work. The contacts are mechanically coupled and feature mirror contacts, which increases reliability in safety-critical applications. Electrical connections are made via Everlink and spring terminals, ensuring a secure and long-lasting connection. The auxiliary contacts (1S1Ö) enable integration into control and monitoring systems, for example, for feedback of the contactor status to a control system. The operating time is 12 to 22 ms, ensuring a fast switching response.
Technology Explained Simply
The contactor coil is powered by 120 V AC, with the operating voltage required to be between 0.8 and 1.1 times the nominal voltage to ensure safe operation. The pickup power is 70 VA at 50 Hz and 60 Hz, while the holding power consumption is 7 VA at 50 Hz and 7.5 VA at 60 Hz. The heat dissipation is between 2 and 3 W at 50/60 Hz, indicating low thermal load on the surrounding environment. The rated short-time withstand current is 145 A for 10 seconds and 240 A for 1 second for the circuit, ensuring high stability under short-circuit conditions. The rated breaking capacity is 300 A at 440 V, highlighting the contactor’s ability to interrupt fault currents. The mechanical life is 15 million switching cycles, while the electrical life is 1.65 million switching cycles at 18 A AC-3 and nominal voltage. The safety level corresponds to EN/ISO 13849-1 with a B10d value of 1,369,863 cycles at nominal load and 20,000,000 cycles at mechanical load.
Compatibility and Accessories
The contactor is equipped with compatibility designation LC1D, enabling the use of accessories such as auxiliary switch blocks (e.g. LADR06, LADN316, LADN116), switching modules (e.g. LAD4RCG), protective covers (e.g. LAD9ET1S), and timing modules (e.g. LADT26, LA4DT4U). These components can be used to extend functionality, integrate into control systems, or increase safety. The use of motor protection relays such as LRD216 or GV2LE20 is recommended to protect the motor against overload. Combination with three-phase busbar systems such as GV2G445 or GV2G245 enables flexible integration into existing power supply systems.
Mounting and Installation
Mounting is done via standard screw fastening, with device dimensions of 45 mm (width) × 77 mm (height) × 86 mm (depth). The weight is 0.33 kg, enabling easy handling. Spring terminals and Everlink technology ensure secure and reliable connections for wiring. Installation is carried out in a closed enclosure, with ambient temperature allowed between -40 °C and +70 °C. The control circuit voltage limits ensure stable operation even with voltage fluctuations within the defined range.
Operational Advantages
The contactor offers high reliability through mechanically coupled contacts and mirror contacts, increasing safety in critical applications. The long service life (15 million mechanical and 1.65 million electrical switching cycles) reduces maintenance frequency and downtime. Integrated auxiliary contacts enable easy integration into control and monitoring systems. Certifications according to international standards (UL, CSA, IEC, etc.) ensure suitability for use in various markets. Low heat dissipation and high short-time current withstand capability increase operational safety and reduce the risk of thermal damage. Simple mounting and maintenance via Everlink and spring terminals reduce installation effort and error susceptibility.