| Complementary |
| Motor power kW | 40 kW at 220/230 V AC 50/60 Hz (AC-3); 75 kW at 380/400 V AC 50/60 Hz (AC-3); 80 kW at 415/440 V AC 50/60 Hz (AC-3); 90 kW at 500 V AC 50/60 Hz (AC-3); 100 kW at 660/690 V AC 50/60 Hz (AC-3); 75 kW at 1000 V AC 50/60 Hz (AC-3); 40 kW at 220/230 V AC 50/60 Hz (AC-3e); 75 kW at 380/400 V AC 50/60 Hz (AC-3e); 80 kW at 415/440 V AC 50/60 Hz (AC-3e); 90 kW at 500 V AC 50/60 Hz (AC-3e); 100 kW at 660/690 V AC 50/60 Hz (AC-3e); 75 kW at 1000 V AC 50/60 Hz (AC-3e); 22 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power hp | 40 hp at 200/208 V AC 50/60 Hz for 3 phases motors; 50 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 100 hp at 460/480 V AC 50/60 Hz for 3 phases motors; 125 hp at 575/600 V AC 50/60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 200 A (at 60 °C) for power circuit |
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 1660 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 1400 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 250 A 40 °C - 10 min for power circuit; 580 A 40 °C - 1 min for power circuit; 1200 A 40 °C - 10 s for power circuit; 1400 A 40 °C - 1 s for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 315 A gG at |
| Average impedance | 0.6 mOhm - Ith 200 A 50 Hz for power circuit |
| Power dissipation per pole | 24 W AC-1; 13.5 W AC-3; 13.5 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Power circuit: 1000 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 684932 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 10000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 8 Mcycles |
| Electrical durability | 0.85 Mcycles 150 A AC-3 at Ue |
| Control circuit type | AC at 50/60 Hz |
| Coil technology | Built-in bidirectional peak limiting diode suppressor |
| Control circuit voltage limits | 0.3...0.5 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.15 Uc (-40…55 °C):operational AC 50/60 Hz; 1...1.15 Uc (55…70 °C):operational AC 50/60 Hz |
| Inrush power in VA | 280…350 VA 60 Hz cos phi 0.9 (at 20 °C); 280…350 VA 50 Hz cos phi 0.9 (at 20 °C) |
| Hold-in power consumption in VA | 2…18 VA 60 Hz cos phi 0.9 (at 20 °C); 2…18 VA 50 Hz cos phi 0.9 (at 20 °C) |
| Heat dissipation | 3…4.5 W at 50/60 Hz |
| Operating time | 20...35 ms closing; 40...75 ms opening |
| Maximum operating rate | 1200 cyc/h at 60 °C |
| Connections - terminals | Control circuit: lugs-ring terminals - external diameter: 8 mm; Power circuit: lugs-ring terminals - external diameter: 25 mm; Power circuit: bars 1 - busbar cross section: 5 x 25 mm |
| Tightening torque | Control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M3.5; Control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5; Power circuit: 12 N.m - on lugs-ring terminals hexagonal screw head 13 mm M8; Power circuit: 12 N.m - on bars hexagonal screw head 13 mm M8; Control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver pozidriv No 2 M3.5 |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Plate; Rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; IEC 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; UL 60947-4-1; CSA C22.2 No 60947-4-1; JIS C8201-4-1 |
| Product certifications | UL; CCC; CSA; CE; UKCA; Marine; EAC |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor open (6 Gn for 11 ms) |
| Height | 158 mm |
| Width | 120 mm |
| Depth | 136 mm |
| Net weight | 2.5 kg |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load; Motor control |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 200 A (at |
| [Uc] control circuit voltage | 440 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 16.800 cm |
| Package 1 Width | 20.800 cm |
| Package 1 Length | 18.500 cm |
| Package 1 Weight | 2.130 kg |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 2 |
| Package 2 Height | 30 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 4.680 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 16 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 80.000 cm |
| Package 3 Length | 60.000 cm |
| Package 3 Weight | 45.440 kg |
The LC1D1506R7 contactor from the TeSys series by Schneider Electric is a 3-pole contactor for controlling electrical drives, particularly for motor control and resistive loads. It features integrated bidirectional peak-limiting diode suppressor technology, which increases coil life and improves electromagnetic compatibility. The coil is designed for a control circuit voltage of 440 V AC at 50/60 Hz, making it suitable for applications in industrial networks with high voltage. The device is certified for usage categories AC-1, AC-3, AC-3e, and AC-4, with AC-3 being the standard category for controlling three-phase motors. The rated operational power is 75 kW at 400 V AC-3, with a rated operational current Ie of 150 A. At an operating voltage of 440 V AC, the operational rated current is 200 A. The construction includes 3 main circuit closers and additional auxiliary contacts in the configuration of 1 closer + 1 opener, which can be used for controlling auxiliary functions such as signaling or feedback.
Applications
This contactor is designed for use in industrial plants, particularly in manufacturing and processing industries, where it can be used to control three-phase motors with powers up to 125 hp at 575/600 V AC. Motor power ratings include 40 hp at 200/208 V AC, 50 hp at 230/240 V AC, 100 hp at 460/480 V AC, and 125 hp at 575/600 V AC. The application is in environments with an overvoltage category III and pollution degree 3, indicating use in industrial environments with increased contamination risk. The rated insulation voltage is 1000 V for the power circuit according to IEC 60947-4-1 and 690 V for the signal circuit according to IEC 60947-1. The rated impulse withstand voltage is 8 kV, ensuring high electrical strength and safety.
Functions and Equipment in Detail
The device has a mechanical life of 8 million switching cycles and an electrical life of 0.85 million switching cycles at 150 A AC-3. The operating time is 20–35 ms for closing and 40–75 ms for opening. The maximum operating rate is 1200 switching cycles per hour at 60 °C. The heat dissipation is 3–4.5 W at 50/60 Hz. The coil is equipped with integrated bidirectional peak-limiting diode suppressor technology, which increases coil life and improves electromagnetic compatibility. The control circuit voltage limits are 0.3–0.5 Uc for drop-out and 0.8–1.15 Uc for operation at temperatures from -40 to 70 °C. The pickup power is 280–350 VA at 50/60 Hz, and the holding power consumption is 2–18 VA at 50/60 Hz.
Technology Explained Simply
The integrated bidirectional peak-limiting diode suppressor technology protects the coil from voltage spikes during switching off and reduces electromagnetic interference. The Everlink and spring terminal technology ensures a secure and long-lasting current connection that remains stable even under high mechanical stress. The mechanically coupled contacts and mirror contacts enable safe use in safety applications, as the contacts are mechanically linked, ensuring a secure switching function. The rated breaking capacity is 1400 A at 440 V, providing high safety under short-circuit conditions. The rated short-time current withstand is 1400 A for 1 s in the power circuit, highlighting the contactor’s ability to interrupt high current surges.
Compatibility and Accessories
The contactor is compatible with various auxiliary contacts and time blocks for extending functionality. Compatible accessories include auxiliary switch blocks such as LADN226 (2S2O), LAD8N206 (2S), LADN046 (4O), LADN316 (3S1O), LADN116 (1S1O), LADT26 (1S1O delayed pickup), LADR06 (1S1O latched release), LADS26 (1S1O delayed pickup), LADN136 (1S3O), LADT46 (1S1O delayed pickup), LAD8N026 (2O), LAD8N116 (1S+1O), LADN206 (2S), GV7AC03 (spreading holder), LADR26 (1S1O latched release), LADN026 (2O), and LADN406 (4S). These components can be used to extend control functions, such as signaling or time delays. As an alternative or successor, the LC1D150A6LSE contactor (TeSys Deca LC1D 3p +1S+1O 75 kW 150 A) is offered.
Mounting and Installation
Connections are made via ring terminal lugs with an outer diameter of 8 mm for the control circuit and 25 mm for the power circuit. For the power circuit, rails with a cross-section of 5 x 25 mm are also available. The tightening torque is 1.2 Nm for the control circuit (with flat screwdriver Ø 6 M3.5 or Phillips No. 2 M3.5) and 12 Nm for the power circuit (with hexagonal screw head 13 mm M8). Mounting is done in standard control panels, with the device dimensions being 120 mm (width) x 158 mm (height) x 136 mm (depth). The net weight is 2.5 kg.
Operational Advantages
The contactor offers high reliability through mechanical coupling of contacts and integrated suppressor technology. Its long service life and high switching frequency make it suitable for continuous operating conditions. Certifications according to CSA, DNV, RINA, LROS (Lloyds Register of Shipping), GOST, UL, CCC, BV, and GL ensure compliance with international safety and quality standards. The use of Everlink and spring terminals ensures a secure and long-lasting current connection that remains stable even under high mechanical stress. The integrated bidirectional peak-limiting diode suppressor technology reduces electromagnetic interference and increases coil life.