| Complementary |
| Motor power kW | 40 kW at 220/230 V AC 50/60 Hz (AC-3); 75 kW at 380/400 V AC 50/60 Hz (AC-3); 80 kW at 415/440 V AC 50/60 Hz (AC-3); 90 kW at 500 V AC 50/60 Hz (AC-3); 100 kW at 660/690 V AC 50/60 Hz (AC-3); 75 kW at 1000 V AC 50/60 Hz (AC-3); 40 kW at 220/230 V AC 50/60 Hz (AC-3e); 75 kW at 380/400 V AC 50/60 Hz (AC-3e); 80 kW at 415/440 V AC 50/60 Hz (AC-3e); 90 kW at 500 V AC 50/60 Hz (AC-3e); 100 kW at 660/690 V AC 50/60 Hz (AC-3e); 75 kW at 1000 V AC 50/60 Hz (AC-3e); 22 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power hp | 40 hp at 200/208 V AC 50/60 Hz for 3 phases motors; 50 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 100 hp at 460/480 V AC 50/60 Hz for 3 phases motors; 125 hp at 575/600 V AC 50/60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 200 A (at 60 °C) for power circuit |
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 1660 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 1400 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 250 A 40 °C - 10 min for power circuit; 580 A 40 °C - 1 min for power circuit; 1200 A 40 °C - 10 s for power circuit; 1400 A 40 °C - 1 s for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 315 A gG at |
| Average impedance | 0.6 mOhm - Ith 200 A 50 Hz for power circuit |
| Power dissipation per pole | 24 W AC-1; 13.5 W AC-3; 13.5 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Power circuit: 1000 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 684932 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 10000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 8 Mcycles |
| Electrical durability | 0.85 Mcycles 150 A AC-3 at Ue |
| Control circuit type | DC standard |
| Coil technology | With integral suppression device |
| Control circuit voltage limits | 0.75...1.2 Uc (-40…55 °C):operational DC; 0.15...0.4 Uc (-40…70 °C):drop-out DC; 1...1.2 Uc (55…70 °C):operational DC |
| Inrush power in W | 270…365 W (at 20 °C) |
| Hold-in power consumption in W | 2.4…5.1 W at 20 °C |
| Operating time | 20...35 ms closing; 40...75 ms opening |
| Time constant | 25 ms |
| Maximum operating rate | 1200 cyc/h at 60 °C |
| Connections - terminals | Control circuit: lugs-ring terminals - external diameter: 8 mm; Power circuit: lugs-ring terminals - external diameter: 25 mm; Power circuit: bars 1 - busbar cross section: 5 x 25 mm |
| Tightening torque | Control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M3.5; Control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5; Power circuit: 12 N.m - on lugs-ring terminals hexagonal screw head 13 mm M8; Power circuit: 12 N.m - on bars hexagonal screw head 13 mm M8; Control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver pozidriv No 2 M3.5 |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Plate; Rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; IEC 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; UL 60947-4-1; CSA C22.2 No 60947-4-1; JIS C8201-4-1 |
| Product certifications | UL; CCC; CSA; CE; UKCA; Marine; EAC |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor open (6 Gn for 11 ms) |
| Height | 158 mm |
| Width | 120 mm |
| Depth | 136 mm |
| Net weight | 2.5 kg |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load; Motor control |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 200 A (at |
| [Uc] control circuit voltage | 220 V DC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 16.800 cm |
| Package 1 Width | 20.800 cm |
| Package 1 Length | 18.500 cm |
| Package 1 Weight | 2.110 kg |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 2 |
| Package 2 Height | 30 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 4.640 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 16 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 80.000 cm |
| Package 3 Length | 60.000 cm |
| Package 3 Weight | 45.120 kg |
The LC1D1506MD contactor from the TeSys series by Schneider Electric is a 3-pole contactor for motor control and operation with resistive loads. It features an integrated suppression unit and is designed for use categories AC-1, AC-3, AC-3e, and AC-4, with the primary application being the control of electric motors. The device is equipped with a control circuit for 220 V DC and offers an operational rating of 200 A in the main circuit. The rated operational power is 75 kW at 400 V AC3, with the rated operational current Ie at 150 A. The coil is designed for a control circuit voltage of 220 V DC and enables safe and reliable switching operation.
This contactor is designed for industrial applications, particularly for controlling three-phase motors in machine building, material handling, and plant engineering. The use categories AC-3 and AC-4 make it suitable for drives with high inrush currents and frequent switching operations. Certifications according to GL, UL, DNV, LROS, BV, RINA, GOST, CSA, and CCC enable use in international markets, including marine and heavy industrial applications.
The device features 3 normally closed contacts in the main circuit and an additional auxiliary contact block with 1 normally closed and 1 normally open contact. The auxiliary contacts are non-delayed and allow integration into control and monitoring systems. Mechanically coupled contacts and mirror contacts enhance safety in critical applications. The main circuit terminals are designed for ring cable lugs with an outer diameter of 25 mm, with tightening torques for the main circuit terminals at 12 Nm. The control circuit terminals support ring cable lugs with an outer diameter of 8 mm and require a tightening torque of 1.2 Nm.
The integrated suppression unit in the coil reduces magnetic overvoltages during switching off and protects the circuit from disturbances. The coil operates at a working voltage of 220 V DC and has an engagement power of 270 to 365 W at 20 °C. The holding power consumption ranges from 2.4 to 5.1 W. The operating time is 20 to 35 ms for closing and 40 to 75 ms for opening. The maximum operating rate is 1200 switching operations per hour at an ambient temperature of 60 °C. The rated short-time withstand current is 1400 A for 1 second in the main circuit, ensuring high stability under transient loads.
The contactor is equipped with the compatibility designation LC1D and can be combined with various accessories, including auxiliary switch blocks such as LADN116, LADN206, LADN136, or LADN046, as well as time blocks such as LADT46 or LADT26. For motor monitoring, the motor protection relay LR9D5369 is suitable. The use of spreader holders such as GV7AC03 enables secure mounting in enclosures.
Mounting is done via rails with a cross-section of 5 x 25 mm or via ring cable lugs. The terminals are designed for secure and long-lasting current connections, with Everlink technology and spring terminals ensuring a stable connection. The tightening torques are specified for the respective terminal types to ensure a correct connection.
The contactor offers a high mechanical life of 8 million switching cycles and an electrical life of 0.85 million cycles at 150 A AC-3. The rated insulation voltage is 1000 V in the main circuit according to IEC 60947-4-1 and 690 V in the signal circuit according to IEC 60947-1. The overvoltage category III and pollution degree 3 make the device suitable for demanding environments. The rated breaking capacity is 1400 A at 440 V, enabling safe switching off under short-circuit conditions. The safety cover protects against unintended access to conductive parts.