| Complementary |
| Motor power kW | 40 kW at 220/230 V AC 50/60 Hz (AC-3); 75 kW at 380/400 V AC 50/60 Hz (AC-3); 80 kW at 415/440 V AC 50/60 Hz (AC-3); 90 kW at 500 V AC 50/60 Hz (AC-3); 100 kW at 660/690 V AC 50/60 Hz (AC-3); 75 kW at 1000 V AC 50/60 Hz (AC-3); 40 kW at 220/230 V AC 50/60 Hz (AC-3e); 75 kW at 380/400 V AC 50/60 Hz (AC-3e); 80 kW at 415/440 V AC 50/60 Hz (AC-3e); 90 kW at 500 V AC 50/60 Hz (AC-3e); 100 kW at 660/690 V AC 50/60 Hz (AC-3e); 75 kW at 1000 V AC 50/60 Hz (AC-3e); 22 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power hp | 40 hp at 200/208 V AC 50/60 Hz for 3 phases motors; 50 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 100 hp at 460/480 V AC 50/60 Hz for 3 phases motors; 125 hp at 575/600 V AC 50/60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 200 A (at 60 °C) for power circuit |
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 1660 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 1400 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 250 A 40 °C - 10 min for power circuit; 580 A 40 °C - 1 min for power circuit; 1200 A 40 °C - 10 s for power circuit; 1400 A 40 °C - 1 s for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 315 A gG at |
| Average impedance | 0.6 mOhm - Ith 200 A 50 Hz for power circuit |
| Power dissipation per pole | 24 W AC-1; 13.5 W AC-3; 13.5 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Power circuit: 1000 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 684932 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 10000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 8 Mcycles |
| Electrical durability | 0.85 Mcycles 150 A AC-3 at Ue |
| Control circuit type | AC at 50/60 Hz |
| Coil technology | Built-in bidirectional peak limiting diode suppressor |
| Control circuit voltage limits | 0.3...0.5 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.15 Uc (-40…55 °C):operational AC 50/60 Hz; 1...1.15 Uc (55…70 °C):operational AC 50/60 Hz |
| Inrush power in VA | 280…350 VA 60 Hz cos phi 0.9 (at 20 °C); 280…350 VA 50 Hz cos phi 0.9 (at 20 °C) |
| Hold-in power consumption in VA | 2…18 VA 60 Hz cos phi 0.9 (at 20 °C); 2…18 VA 50 Hz cos phi 0.9 (at 20 °C) |
| Heat dissipation | 3…4.5 W at 50/60 Hz |
| Operating time | 20...35 ms closing; 40...75 ms opening |
| Maximum operating rate | 1200 cyc/h at 60 °C |
| Connections - terminals | Control circuit: lugs-ring terminals - external diameter: 8 mm; Power circuit: lugs-ring terminals - external diameter: 25 mm; Power circuit: bars 1 - busbar cross section: 5 x 25 mm |
| Tightening torque | Control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M3.5; Control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5; Power circuit: 12 N.m - on lugs-ring terminals hexagonal screw head 13 mm M8; Power circuit: 12 N.m - on bars hexagonal screw head 13 mm M8; Control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver pozidriv No 2 M3.5 |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Rail; Plate |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; IEC 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; UL 60947-4-1; CSA C22.2 No 60947-4-1; JIS C8201-4-1 |
| Product certifications | UL; CCC; CSA; CE; UKCA; Marine; EAC |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor open (6 Gn for 11 ms) |
| Height | 158 mm |
| Width | 120 mm |
| Depth | 136 mm |
| Net weight | 2.5 kg |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Motor control; Resistive load |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 200 A (at |
| [Uc] control circuit voltage | 120 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 16.800 cm |
| Package 1 Width | 20.800 cm |
| Package 1 Length | 18.500 cm |
| Package 1 Weight | 2.130 kg |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 2 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 4.680 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 16 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 45.440 kg |
The LC1D1506G7 contactor from the TeSys series by Schneider Electric is a 3-pole contactor for motor control and operation with resistive loads. It is designed for use categories AC-3, AC-3e, AC-1, and AC-4, and is particularly suitable for use in industrial plants where reliable and safe switching performance is required. The device features integrated bidirectional peak-limiting diode suppressor technology, which protects the coil from transient voltage spikes and increases service life. The control circuit voltage is 120 V AC at 50/60 Hz, making it suitable for use in standard networks with this voltage.
Applications
This contactor is primarily designed for controlling electric motors, especially in drive systems with a rated operational power of 75 kW at 400 V AC-3. It can also be used for resistive loads. Motor power ratings according to UL/CSA standards include 40 hp at 200/208 V, 50 hp at 230/240 V, 100 hp at 460/480 V, and 125 hp at 575/600 V, all for 3-phase motors. Use categories AC-3 and AC-4 indicate applications in drives with high switching and interruption loads, such as those found in production plants or conveyor systems.
Functions and Equipment in Detail
The contactor has 3 normally closed contacts in the main circuit and additionally features an auxiliary contact block with 1 normally closed and 1 normally open contact. These auxiliary contacts enable integration into control and monitoring systems, for example, to provide feedback on the switching status to a control system. The mechanical service life is 8 million switching cycles, and the electrical service life at 150 A and AC-3 operation is 0.85 million cycles. The operating time is 20–35 ms for closing and 40–75 ms for opening. The maximum operating rate is 1200 switching operations per hour at an ambient temperature of 60 °C.
Technology Explained Simply
The contactor coil is designed for an operating voltage of 120 V AC and operates at frequencies of 50/60 Hz. The pickup power is between 280 and 350 VA, and the holding power is between 2 and 18 VA. The integrated bidirectional diode suppressor technology reduces voltage spikes during switching off and protects the coil. The rated impulse voltage withstand is 8 kV, ensuring high insulation strength and safety in industrial environments. The overvoltage category III and pollution degree 3 indicate that the device is suitable for industrial applications with increased pollution risk.
Compatibility and Accessories
The contactor is compatible with various accessories, including auxiliary switch blocks such as LADN226 (2NO2NC unzinc-plated front-side ring terminal), LADN046 (4NC unzinc-plated front-side ring terminal), or LADT26 (time delay block 1NO1NC delayed pickup). Motor protection relays such as LR9D5369 (90–150 A, Class 10) can also be combined to achieve complete motor control. The main circuit connections are designed for ring terminals with an outer diameter of 25 mm, and the control circuit connections are for 8 mm. The main circuit terminals also support busbars with a cross-section of 5 x 25 mm.
Mounting and Installation
Mounting is done via the integrated connection terminals, designed for ring terminals. The tightening torques are 12 Nm for the main circuit terminals (hexagonal head 13 mm, M8) and 1.2 Nm for the control circuit terminals (M3.5, with flat or Phillips screwdriver). The dimensions of the device are 120 mm (width) x 158 mm (height) x 136 mm (depth), and the net weight is 2.5 kg. The safety cover is integrated as standard, facilitating compliance with safety regulations.
Operational Advantages
The contactor offers high reliability through mechanically coupled contacts and mirror contacts, suitable for safety applications. The Everlink and spring clamp technology ensures a secure and long-lasting electrical connection. The rated insulation voltage is 1000 V for the main circuit according to IEC 60947-4-1, ensuring high electrical safety. Certifications according to CSA, UL, DNV, GOST, RINA, LROS, GL, CCC, and BV demonstrate international recognition and suitability for use in various markets. The rated breaking capacity is 1400 A at 440 V, enabling use in plants with high short-circuit currents.