| Complementary |
| Motor power kW | 3 kW at 220/230 V AC 50/60 Hz (AC-3); 5.5 kW at 380/400 V AC 50/60 Hz (AC-3); 5.5 kW at 415/440 V AC 50/60 Hz (AC-3); 7.5 kW at 500 V AC 50/60 Hz (AC-3); 7.5 kW at 660/690 V AC 50/60 Hz (AC-3); 3 kW at 220/230 V AC 50/60 Hz (AC-3e); 5.5 kW at 380/400 V AC 50/60 Hz (AC-3e); 5.5 kW at 415/440 V AC 50/60 Hz (AC-3e); 7.5 kW at 500 V AC 50/60 Hz (AC-3e); 7.5 kW at 660/690 V AC 50/60 Hz (AC-3e); 3.7 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power hp | 0.5 hp at 115 V AC 50/60 Hz for 1 phase motors; 2 hp at 230/240 V AC 50/60 Hz for 1 phase motors; 3 hp at 200/208 V AC 50/60 Hz for 3 phases motors; 3 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 7.5 hp at 460/480 V AC 50/60 Hz for 3 phases motors; 10 hp at 575/600 V AC 50/60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 25 A (at 60 °C) for power circuit; 10 A (at 60 °C) for signalling circuit |
| Irms rated making capacity | 250 A at 440 V for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 250 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 105 A 40 °C - 10 s for power circuit; 210 A 40 °C - 1 s for power circuit; 30 A 40 °C - 10 min for power circuit; 61 A 40 °C - 1 min for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 40 A gG at |
| Average impedance | 2.5 mOhm - Ith 25 A 50 Hz for power circuit |
| Power dissipation per pole | 0.36 W AC-3; 1.56 W AC-1; 0.36 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 30 Mcycles |
| Electrical durability | 2 Mcycles 12 A AC-3 at Ue |
| Control circuit type | DC low consumption |
| Coil technology | Built-in bidirectional peak limiting diode suppressor |
| Control circuit voltage limits | 0.1...0.3 Uc (-40…70 °C):drop-out DC; 0.8...1.25 Uc (-40…60 °C):operational DC; 1...1.25 Uc (60…70 °C):operational DC |
| Inrush power in W | 2.4 W (at 20 °C) |
| Hold-in power consumption in W | 2.4 W at 20 °C |
| Operating time | 77 ±15 % ms closing; 25 ±20 % ms opening |
| Time constant | 40 ms |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Plate; Rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; CSA C22.2 No 60947-4-1 |
| Product certifications | UL; CCC; CSA; Marine; UKCA; EAC; CB Scheme |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor open (10 Gn for 11 ms) ; Shocks contactor closed (15 Gn for 11 ms) |
| Height | 77 mm |
| Width | 45 mm |
| Depth | 95 mm |
| Net weight | 0.485 kg |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load; Motor control |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 25 A (at |
| [Uc] control circuit voltage | 24 V DC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.000 cm |
| Package 1 Width | 9.200 cm |
| Package 1 Length | 11.300 cm |
| Package 1 Weight | 527.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 15 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 8.192 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 240 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 138.000 kg |
The LC1D12BL contactor from the TeSys Deca Advanced series by Schneider Electric is a 3-pole contactor for controlling motors and resistive loads. It features integrated bidirectional peak-limiting diode suppressor technology, which protects the coil from transient voltage spikes and increases service life. The control circuit voltage is 24 V DC, with operating voltage ranging from 0.8 to 1.25 times rated voltage (at -40 to 60 °C) and 1 to 1.25 times rated voltage (at 60 to 70 °C). The pickup power and holding power consumption are each 2.4 W at 20 °C. The operating time is 77 ±15 % ms for closing and 25 ±20 % ms for opening, with a time constant of 40 ms. The maximum operating rate is 3600 cycles per hour at 60 °C.
Applications
The contactor is suitable for various application categories, including AC-3, AC-3e, AC-1, and AC-4. For AC-3 at 400 V AC, the rated operational power is 5.5 kW, with a rated operational current Ie of 12 A. For AC-4 at 400 V AC, the motor power is 3.7 kW. Applications include controlling three-phase motors and resistive loads in industrial installations. Certifications according to GOST, BV, CSA, DNV, RINA, CCC, LROS (Lloyds Register of Shipping), GL, and UL ensure suitability for use in various industries and regions.
Functions and Equipment in Detail
The device features 3 main circuit closers and additional auxiliary contacts configured as 1 closer + 1 opener. This contact configuration enables integration into complex control logic. The safety cover protects against unintended access and meets requirements for safety-critical applications. Mechanically interlocked contacts and mirror contacts enhance reliability in safety applications. Current connections are made via Everlink technology and spring terminals, ensuring a secure and long-lasting connection.
Technology Explained Simply
The integrated bidirectional amplitude-limiting diode protects the coil from voltage spikes caused by switching off inductive loads. This extends the contactor’s service life and reduces interference in the control circuit. The rated insulation voltage is 690 V for the power circuit and complies with standards IEC 60947-4-1, CSA, and UL. Overvoltage category III and pollution degree 3 ensure suitability for industrial environments with increased contamination risk. The rated impulse withstand voltage is 6 kV, ensuring robustness against transient voltage surges.
Compatibility and Accessories
The contactor is compatible with various accessories, including auxiliary switch blocks such as LADN02 (2O), LADN20 (2S), and LADN11 (1S1O), which are mounted front-side with screw terminals. For integration into reversing contactor applications, the kit LAD9R1 is available. Motor protection relays such as LRD16 (9–13 A) or GV2ME16 (3p, 9–14 A) can be used for additional protection functions. Mechanical interlocks such as LAD9V2 and main circuit connectors such as LAD9V5 (parallel) or LAD9V6 (reversing screw terminal) support secure mounting and operation. The three-phase busbar system GV2G445 (63 A, 4 outlets) or GV2G245 (63 A, 2 outlets) enables integration into existing power supply systems.
Mounting and Installation
Mounting is done via standard screw terminals or spring terminals, with Everlink technology ensuring a secure and long-lasting connection. Dimensions are 45 mm (width) × 77 mm (height) × 95 mm (depth), enabling compact placement in enclosures. The weight is 0.485 kg. Installation requires no special tools, as the connection technology is standardized. The electrical life is 2 million cycles at 12 A AC-3 and rated voltage, while the mechanical life is 30 million cycles. The conventional thermal current rating is 25 A in the power circuit at 60 °C and 10 A in the signal circuit at 60 °C.
Operational Advantages
The contactor offers high reliability due to integrated coil protection technology and mechanically interlocked contacts. The low coil power consumption (2.4 W) reduces energy usage in the control circuit. High service life and robust construction ensure low-maintenance operation. Compatibility with various accessories and protection systems enables flexible integration into existing installations. Certifications according to international standards ensure suitability for use in various markets and industries.