| Complementary |
| Compatibility code | LC1D |
| Pole contact composition | 2 NO + 2 NC |
| Protective cover | With |
| [Ith] conventional free air thermal current | 25 A (at 60 °C) for power circuit; 10 A (at 60 °C) for signalling circuit |
| Irms rated making capacity | 250 A at 440 V for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 250 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 105 A 40 °C - 10 s for power circuit; 210 A 40 °C - 1 s for power circuit; 30 A 40 °C - 10 min for power circuit; 61 A 40 °C - 1 min for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 40 A gG at |
| Average impedance | 2.5 mOhm - Ith 25 A 50 Hz for power circuit |
| Power dissipation per pole | 1.56 W AC-1 |
| [Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 15 Mcycles |
| Electrical durability | 0.8 Mcycles 25 A AC-1 at Ue |
| Control circuit type | AC at 50/60 Hz |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz |
| Inrush power in VA | 70 VA 60 Hz cos phi 0.75 (at 20 °C); 70 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Hold-in power consumption in VA | 7.5 VA 60 Hz cos phi 0.3 (at 20 °C); 7 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 2…3 W at 50/60 Hz |
| Operating time | 12...22 ms closing; 4...19 ms opening |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Plate; Rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; CSA C22.2 No 60947-4-1 |
| Product certifications | UL; CCC; CSA; Marine; UKCA; EAC; CB Scheme |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor open (10 Gn for 11 ms) ; Shocks contactor closed (15 Gn for 11 ms) |
| Height | 85 mm |
| Width | 45 mm |
| Depth | 92 mm |
| Net weight | 0.365 kg |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load |
| Utilisation category | AC-1 |
| Poles description | 4P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 25 A (at |
| [Uc] control circuit voltage | 240 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.700 cm |
| Package 1 Width | 9.500 cm |
| Package 1 Length | 12.000 cm |
| Package 1 Weight | 396.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 16 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 6.821 kg |
The LC1D128U7 contactor from the TeSys Deca Advanced series by Schneider Electric is a 4-pole contactor designed for use in industrial applications. It is intended for resistive loads and corresponds to usage category AC-1. The device features a current circuit contact configuration of 2 NO and 2 NC contacts, along with additional auxiliary contacts comprising 1 NO and 1 NC. The control circuit voltage is 240 V AC at 50/60 Hz. The contactor is supplied without an integrated wiring module, enabling flexible adaptation to various requirements.
Applications
This contactor is suitable for use in industrial control systems and switchgear, particularly in applications involving resistive loads such as heating, lighting, or resistance operation. Category AC-1 ensures reliability under continuous load conditions. The integrated auxiliary contacts allow use in control circuits, for example, for feedback of switching states or actuation of additional components. Certifications according to GOST, GL, RINA, LROS, CSA, BV, CCC, UL, and DNV indicate international applicability across various industries, including marine technology and power supply.
Functions and Equipment in Detail
The device offers a rated operational current of 25 A in the main circuit and is designed for a rated operating voltage in the main circuit. The conventional thermal current rating is 25 A at 60 °C in the main circuit and 10 A at 60 °C in the signal circuit. The rated breaking capacity is 250 A at 440 V, confirming its ability to safely interrupt loads under these conditions. The rated making capacity is 250 A at 440 V for the main circuit and 140 A AC or 250 A DC for the signal circuit, as per IEC 60947. The mechanical life is 15 million switching cycles, and the electrical life is 0.8 million cycles at 25 A AC-1 and rated voltage.
Technology Explained Simply
The contactor coil is supplied with 240 V AC and operates at frequencies of 50/60 Hz. The operating voltage range is between 0.8 and 1.1 times the nominal voltage at temperatures from -40 to 60 °C, with a requirement of 1.0 to 1.1 times nominal voltage at higher temperatures (60–70 °C). The pickup power is 70 VA at 50 Hz and 60 Hz, and the holding power consumption is 7 VA at 50 Hz and 7.5 VA at 60 Hz. Heat dissipation is between 2 and 3 W at 50/60 Hz. The operating time is 12–22 ms for closing and 4–19 ms for opening. The maximum operating rate is 3600 switching operations per hour at 60 °C.
Compatibility and Accessories
The contactor is equipped with a safety cover that restricts access to the contacts. The auxiliary contacts are mechanically linked (1 NO + 1 NC) and comply with IEC 60947-5-1. A mirror contact (1 NC) is also present and complies with IEC 60947-4-1. This design makes the device suitable for safety applications requiring mechanical coupling of contacts. Compatible accessories include various auxiliary switch blocks such as LADN20, LADN11, LADN22, LADN40, LADN13, LADN31, LAD8N11, LAD8N20, delayed auxiliary switch blocks such as LADT2, LADT4, LAD-S2, LAD-R4, time blocks such as LADR0, wiring module LAD4RCU, and motor protection relays such as LRD04, LRD02, LRD03. These components can be used to extend the functionality of the contactor.
Mounting and Installation
Mounting is done via screw terminals with a tightening torque of 1.7 Nm, using flat-blade screwdrivers Ø 6 or Phillips No. 2. Dimensions are 45 mm (width) × 85 mm (height) × 92 mm (depth). The Everlink connection technology and spring terminals ensure a secure and long-lasting electrical connection. Installation is carried out in enclosures or control systems, with ambient temperatures ranging from -40 °C to +70 °C.
Advantages in Operation
The contactor offers high reliability due to the mechanical coupling of contacts and its long service life. The integrated auxiliary contacts enable flexible control and feedback. Certifications according to international standards ensure applicability across various industries. The use of Everlink and spring terminals ensures a secure and maintenance-friendly connection. The operating voltage range and heat dissipation are designed for industrial environments, with a maximum operating rate of 3600 cycles per hour at 60 °C enabling high load capacity. The rated surge voltage withstand is 6 kV, ensuring robustness against transient overvoltages. The overvoltage category III and pollution degree 3 meet the requirements for industrial installations. The rated insulation voltage is 690 V in the main circuit and signal circuit, with additional CSA and UL certifications available for 600 V. The safety level rating according to EN/ISO 13849-1 shows a B10d value of 1,369,863 cycles at rated load and 20,000,000 cycles at mechanical load, confirming suitability for safety applications.