| Additional features |
| Motor power (kW) | 3 kW at 220/230 V AC 50/60 Hz (AC-3); 5.5 kW at 380/400 V AC 50/60 Hz (AC-3); 5.5 kW at 415/440 V AC 50/60 Hz (AC-3); 7.5 kW at 500 V AC 50/60 Hz (AC-3); 7.5 kW at 660/690 V AC 50/60 Hz (AC-3); 3 kW at 220/230 V AC 50/60 Hz (AC-3e); 5.5 kW at 380/400 V AC 50/60 Hz (AC-3e); 5.5 kW at 415/440 V AC 50/60 Hz (AC-3e); 7.5 kW at 500 V AC 50/60 Hz (AC-3e); 7.5 kW at 660/690 V AC 50/60 Hz (AC-3e); 3.7 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power HP (UL / CSA standards) | 0.5 hp at 115 V AC 50/60 Hz for 1-phase motors; 2 hp at 230/240 V AC 50/60 Hz for 1-phase motors; 3 hp at 200/208 V AC 50/60 Hz for 3-phase motors; 3 hp at 230/240 V AC 50/60 Hz for 3-phase motors; 7.5 hp at 460/480 V AC 50/60 Hz for 3-phase motors; 10 hp at 575/600 V AC 50/60 Hz for 3-phase motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 S |
| Safety cover | With |
| [Ith] conventional thermal current in free air | 25 A (at 60 °C) for power circuit; 10 A (at 60 °C) for signal circuit |
| [Irms] Rated making capacity | 250 A at 440 V for circuits conforming to IEC 60947; 140 A AC for signal circuits conforming to IEC 60947-5-1; 250 A DC for signal circuits conforming to IEC 60947-5-1 |
| Rated breaking capacity | 250 A at 440 V for circuit, conforms to IEC 60947 |
| [Icw] rated short-time current withstand | 105 A 40 °C - 10 s for circuit; 210 A 40 °C - 1 s for circuit; 30 A 40 °C - 10 min for circuit; 61 A 40 °C - 1 min for circuit; 100 A - 1 s for signal circuit; 120 A - 500 ms for signal circuit; 140 A - 100 ms for signal circuit |
| Associated fuse | 10 A gG for signal circuits, complies with IEC 60947-5-1; 40 A gG at |
| Average impedance | 2.5 MOhm - Ith 25 A 50 Hz for circuit |
| Power dissipation per pole | 0,36 W AC-3; 1,56 W AC-1; 0,36 W AC-3e |
| [Ui] Rated insulation voltage | Circuit: 690 V compliant with IEC 60947-4-1; Circuit: 600 V CSA certified; Circuit: 600 V UL certified; Signal circuit: 690 V compliant with IEC 60947-1; Signal circuit: 600 V CSA certified; Signal circuit: 600 V UL certified |
| Over voltage category | III |
| Pollution degree | 3 |
| [Uimp] Rated impulse voltage withstand | 6 kV corresponds to IEC 60947 |
| Security level rating | B10d = 1369863 cycles contactor with rated load corresponds to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load corresponds to EN/ISO 13849-1 |
| Mechanical life | 30 Mcycles |
| Electrical lifetime | 2 Mcycles 12 A AC-3 at Ue |
| Control circuit type | DC Standard |
| Coil technology | With integrated suppression unit |
| Control circuit voltage limits | 0.1 - 0.25 Uc (-40…70 °C): drop voltage DC; 0.7 - 1.25 Uc (-40…60 °C): operation DC; 1 - 1.25 Uc (60…70 °C): operation DC |
| Absorption power in W | 5.4 W (at 20 °C) |
| Holding power consumption in W | 5.4 W at 20 °C |
| Operating time | 63 ±15 % ms closing; 20 ±20 % ms opening |
| Time constant | 28 ms |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Connections - terminals | Control circuit: ring terminal lugs - outer diameter: 8 mm; power circuit: ring terminal lugs - outer diameter: 8 mm |
| Configuration of auxiliary contacts | 1 S + 1 Ö |
| Type of auxiliary contacts | Mechanically linked type 1 S + 1 NC complies with IEC 60947-5-1; Mirror contact type 1 NO complies with IEC 60947-4-1 |
| Signalling angular frequency | 25 - 400 Hz |
| Min. switching voltage | 17 V for signal circuit |
| Min. switching current | 5 mA for signal circuit |
| Insulation resistance | > 10 MΩ for signal circuits |
| Non-overlapping time | 1.5 ms with switching between normally open and normally closed contact; 1.5 ms with actuation between normally open and normally closed contact |
| Mounting bracket | Rail; Plate |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Application of contactor | Resistive load; motor control |
| Application category | AC-3; AC-3e; AC-1; AC-4 |
| Pole description | 3P |
| [Ue] Rated operational voltage | Circuit: |
| [Ie] rated operational current | 25 A (at |
| [Uc] control circuit voltage | 48 V DC |
| Mounting |
| Standards | CSA C22.2 No. 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; CSA C22.2 No. 60947-4-1 |
| Product certifications | UL; CCC; CSA; Marine; UKCA; EAC; CB-Regulation |
| Degree of protection (IP) | IP20 front side corresponds to IEC 60529 |
| Protection treatment | TH corresponds to IEC 60068-2-30 |
| Climate resistance | Complies with IACS E10 damp heat exposure; complies with IEC 60947-1 Annex Q Category D damp heat exposure |
| Device ambient temperature | -40…60 °C; 60…70 °C with power reduction |
| Operating altitude | 0 - 3.000 m |
| Fire-resistance | 850 °C corresponds to IEC 60695-2-1 |
| Flame retardancy | V1 corresponds to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5 - 300 Hz); vibrations contactor closed (4 Gn, 5 - 300 Hz); shocks contactor open (10 Gn for 11 ms); shocks contactor closed (15 Gn for 11 ms) |
| Height | 77 mm |
| Width | 45 mm |
| Depth | 95 mm |
| Product weight | 0,485 kg |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 10,3 cm |
| VPE 1 width | 8,1 cm |
| VPE 1 length | 5,4 cm |
| Packaging weight (Lbs) | 501,0 g |
TeSys LC1D power contactor. 3-pole, 3 NO contacts. Additional auxiliary contacts - 1 NO + 1 NC contact, rated operating power at AC-3, 400 V 5.5 kW, rated operating current Ie at AC-3, 400 V 12 A, coil 48 V DC. Dimensions (WxHxD) 45x77x95 mm, weight 0.485 kg. Category AC-4, AC-3, AC-1. with integral suppression unit. Quick and easy setup. Safe and durable power connection with Everlink and spring terminals. Suitable for safety applications due to mechanically coupled contacts and mirror contacts. Certifications according to GL, CSA, CCC, LROS (Lloyds register of shipping), BV, RINA, UL, GOST, DNV. Product standards in accordance with.