| Complementary |
| Motor power hp | 30 hp at 200/208 V 60 Hz; 40 hp at 230/240 V 60 Hz; 75 hp at 460/480 V 60 Hz; 100 hp at 575/600 V 60 Hz |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 200 A (at 60 °C) for power circuit |
| Irms rated making capacity | 1560 A at 440 V for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 1100 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 350 A 40 °C - 10 min for power circuit; 600 A 40 °C - 1 min for power circuit; 1280 A 40 °C - 10 s for power circuit; 1800 A 40 °C - 1 s for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 125 A aM at |
| Average impedance | 0.45 mOhm - Ith 200 A 50 Hz for power circuit |
| Power dissipation per pole | 6 W AC-3; 6 W AC-3e; 22 W AC-1 |
| [Ui] rated insulation voltage | Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Power circuit: 1000 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 684932 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 10000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 8 Mcycles |
| Electrical durability | 1 Mcycles 115 A AC-3 at Ue |
| Control circuit type | AC at 50/60 Hz; DC |
| Coil technology | Built-in bidirectional peak limiting diode suppressor |
| Control circuit voltage limits | 0.8 Uc Min...1.1 Uc Max (-40…60 °C):operational AC/DC; 0.1 Uc Max (-40…60 °C):drop-out AC/DC |
| Inrush power in VA | 170 VA (at 20 °C) |
| Inrush power in W | 105 W (at 20 °C) |
| Hold-in power consumption in VA | 8 VA (at 20 °C) |
| Hold-in power consumption in W | 4.5 W at 20 °C |
| Heat dissipation | 1.1 W at 20 °C |
| Operating time | 25...90 ms opening; 20...90 ms closing |
| Maximum operating rate | 2400 cyc/h at 60 °C; 3600 cyc/h at Uc at 20 ºC |
| Tightening torque | Power circuit: 12 N.m - on connector hexagonal screw head 4 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 16.67...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Plate |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; UL 60947-5-1; CSA C22.2 No 60947-4-1; CSA C22.2 No 60947-5-1; JIS C8201-4-1; JIS C8201-5-1; GB/T 14048.4; GB/T 14048.5 |
| Product certifications | CB Scheme; CCC; cULus; CE; UKCA; EU-RO-MR by DNV-GL |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | None conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C operation; 60…70 °C with derating; -60…80 °C storage |
| Operating altitude | 0...3000 m without derating |
| Fire resistance | 850 °C conforming to IEC 60695-2-11 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) conforming to IEC 60068-2-6; Vibrations contactor closed (4 Gn, 5...300 Hz) conforming to IEC 60068-2-6; Shocks contactor open (10 Gn for 11 ms) conforming to IEC 60068-2-27; Shocks contactor closed (15 Gn for 11 ms) conforming to IEC 60068-2-27 |
| Height | 152 mm |
| Width | 97 mm |
| Depth | 155 mm |
| Net weight | 2.4 kg |
| Logistical informations |
| Country of origin | CN |
| Main |
| Range | TeSys Deca |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Motor control; Resistive load |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4; DC-1; DC-3; DC-5 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 115 A (at |
| [Uc] control circuit voltage | 100...250 V AC 50/60 Hz; 100...250 V DC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 18.9 cm |
| Package 1 Width | 13.2 cm |
| Package 1 Length | 18.2 cm |
| Package 1 Weight | 2.63 kg |
| Unit Type of Package 2 | S06 |
| Number of Units in Package 2 | 48 |
| Package 2 Height | 73.5 cm |
| Package 2 Width | 60 cm |
| Package 2 Length | 80 cm |
| Package 2 Weight | 139.8095 kg |
TeSys Deca Advanced Schütz, 3 Pole (3NO) für Anwendungen der Kategorie AC-3 bis 115A 55kW 400_440V. Er ist mit einer elektronischen Breitbandspule 100-250V AC/DC ausgestattet, die einen geringeren Stromverbrauch hat, sowie mit integrierten 1NO+1NC-Hilfskontakten. Die Einbaulage ist beliebig, und LRD43 kann direkt unter dem Schütz montiert werden. Der Betriebstemperaturbereich liegt zwischen -40 °C und 70 °C und es kann ohne Leistungsminderung in Höhen bis zu 3000 m installiert werden. Er wurde für anspruchsvolle Anwendungen mit verbesserter Leistung unter rauen Umgebungsbedingungen wie Salznebel, Staub und starken Stößen entwickelt. Die Abmessungen betragen 152 mm x 97 mm x 155 mm (H x B x T). Die kompakte Größe reduziert den Platzbedarf. Einfache Verkabelung mit frontseitigem Zugang zum Steuerkreis verbessert die Zugänglichkeit und Sicherheit. Front IP20 sowie eine verbesserte Robustheit der Hauptstromverbindung werden durch EverLink erreicht. Zertifiziert nach mehreren Normen (CE, CB, CCC, cULus, KC, RCM). Eindeutiger QR-Code ermöglicht schnellen Zugriff auf vollständige Produktdaten.