Motor power hp30 hp at 200/208 V 60 Hz; 40 hp at 230/240 V 60 Hz; 75 hp at 460/480 V 60 Hz; 100 hp at 575/600 V 60 Hz
Compatibility codeLC1D
Pole contact composition3 NO
Protective coverWith
[Ith] conventional free air thermal current200 A (at 60 °C) for power circuit
Irms rated making capacity1560 A at 440 V for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity1100 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current350 A 40 °C - 10 min for power circuit; 600 A 40 °C - 1 min for power circuit; 1280 A 40 °C - 10 s for power circuit; 1800 A 40 °C - 1 s for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit
Associated fuse rating125 A aM at
Average impedance0.45 mOhm - Ith 200 A 50 Hz for power circuit
Power dissipation per pole6 W AC-3; 6 W AC-3e; 22 W AC-1
[Ui] rated insulation voltagePower circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Power circuit: 1000 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified
Overvoltage categoryIII
Pollution degree3
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947
Safety reliability levelB10d = 684932 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 10000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability8 Mcycles
Electrical durability1 Mcycles 115 A AC-3 at Ue
Control circuit typeAC at 50/60 Hz; DC
Coil technologyBuilt-in bidirectional peak limiting diode suppressor
Control circuit voltage limits0.8 Uc Min...1.1 Uc Max (-40…60 °C):operational AC/DC; 0.1 Uc Max (-40…60 °C):drop-out AC/DC
Inrush power in VA170 VA (at 20 °C)
Inrush power in W105 W (at 20 °C)
Hold-in power consumption in VA8 VA (at 20 °C)
Hold-in power consumption in W4.5 W at 20 °C
Heat dissipation1.1 W at 20 °C
Operating time25...90 ms opening; 20...90 ms closing
Maximum operating rate2400 cyc/h at 60 °C; 3600 cyc/h at Uc at 20 ºC
Tightening torquePower circuit: 12 N.m - on connector hexagonal screw head 4 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Auxiliary contact composition1 NO + 1 NC
Auxiliary contacts typetype mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency16.67...400 Hz
Minimum switching voltage17 V for signalling circuit
Minimum switching current5 mA for signalling circuit
Insulation resistance> 10 MOhm for signalling circuit
Non-overlap time1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact
Mounting supportPlate
Contractual warranty
Warranty (in months)18
Environment
StandardsEN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; UL 60947-5-1; CSA C22.2 No 60947-4-1; CSA C22.2 No 60947-5-1; JIS C8201-4-1; JIS C8201-5-1; GB/T 14048.4; GB/T 14048.5
Product certificationsCB Scheme; CCC; cULus; CE; UKCA; EU-RO-MR by DNV-GL
IP degree of protectionIP20 front face conforming to IEC 60529
Protective treatmentNone conforming to IEC 60068-2-30
Climatic withstandconforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat
Permissible ambient air temperature around the device-40…60 °C operation; 60…70 °C with derating; -60…80 °C storage
Operating altitude0...3000 m without derating
Fire resistance850 °C conforming to IEC 60695-2-11
Mechanical robustnessVibrations contactor open (2 Gn, 5...300 Hz) conforming to IEC 60068-2-6; Vibrations contactor closed (4 Gn, 5...300 Hz) conforming to IEC 60068-2-6; Shocks contactor open (10 Gn for 11 ms) conforming to IEC 60068-2-27; Shocks contactor closed (15 Gn for 11 ms) conforming to IEC 60068-2-27
Height152 mm
Width97 mm
Depth155 mm
Net weight2.4 kg
Logistical informations
Country of originCN
Main
RangeTeSys Deca
Range of productTeSys Deca Advanced
Product or component typeContactor
Device short nameLC1D
Contactor applicationMotor control; Resistive load
Utilisation categoryAC-3; AC-3e; AC-1; AC-4; DC-1; DC-3; DC-5
Poles description3P
[Ue] rated operational voltagePower circuit:
[Ie] rated operational current115 A (at
[Uc] control circuit voltage100...250 V AC 50/60 Hz; 100...250 V DC
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height18.9 cm
Package 1 Width13.2 cm
Package 1 Length18.2 cm
Package 1 Weight2.63 kg
Unit Type of Package 2S06
Number of Units in Package 248
Package 2 Height73.5 cm
Package 2 Width60 cm
Package 2 Length80 cm
Package 2 Weight139.8095 kg
TeSys Deca Advanced Schütz, 3 Pole (3NO) für Anwendungen der Kategorie AC-3 bis 115A 55kW 400_440V. Er ist mit einer elektronischen Breitbandspule 100-250V AC/DC ausgestattet, die einen geringeren Stromverbrauch hat, sowie mit integrierten 1NO+1NC-Hilfskontakten. Die Einbaulage ist beliebig, und LRD43 kann direkt unter dem Schütz montiert werden. Der Betriebstemperaturbereich liegt zwischen -40 °C und 70 °C und es kann ohne Leistungsminderung in Höhen bis zu 3000 m installiert werden. Er wurde für anspruchsvolle Anwendungen mit verbesserter Leistung unter rauen Umgebungsbedingungen wie Salznebel, Staub und starken Stößen entwickelt. Die Abmessungen betragen 152 mm x 97 mm x 155 mm (H x B x T). Die kompakte Größe reduziert den Platzbedarf. Einfache Verkabelung mit frontseitigem Zugang zum Steuerkreis verbessert die Zugänglichkeit und Sicherheit. Front IP20 sowie eine verbesserte Robustheit der Hauptstromverbindung werden durch EverLink erreicht. Zertifiziert nach mehreren Normen (CE, CB, CCC, cULus, KC, RCM). Eindeutiger QR-Code ermöglicht schnellen Zugriff auf vollständige Produktdaten.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/888568
qrcode für Schneider Electric LC1D115AKUE contactor 3p+1S+1Ö 115 A