| Complementary |
| Motor power kW | 30 kW at 220/230 V AC 50/60 Hz (AC-3); 55 kW at 380/400 V AC 50/60 Hz (AC-3); 59 kW at 415/440 V AC 50/60 Hz (AC-3); 75 kW at 500 V AC 50/60 Hz (AC-3); 80 kW at 660/690 V AC 50/60 Hz (AC-3); 65 kW at 1000 V AC 50/60 Hz (AC-3); 30 kW at 220/230 V AC 50/60 Hz (AC-3e); 55 kW at 380/400 V AC 50/60 Hz (AC-3e); 59 kW at 415/440 V AC 50/60 Hz (AC-3e); 75 kW at 500 V AC 50/60 Hz (AC-3e); 80 kW at 660/690 V AC 50/60 Hz (AC-3e); 65 kW at 1000 V AC 50/60 Hz (AC-3e); 18.5 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power hp | 30 hp at 200/208 V AC 50/60 Hz for 3 phases motors; 40 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 75 hp at 460/480 V AC 50/60 Hz for 3 phases motors; 100 hp at 575/600 V AC 50/60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 200 A (at 60 °C) for power circuit |
| Irms rated making capacity | 1260 A at 440 V for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 1100 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 250 A 40 °C - 10 min for power circuit; 550 A 40 °C - 1 min for power circuit; 950 A 40 °C - 10 s for power circuit; 1100 A 40 °C - 1 s for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 250 A gG at |
| Average impedance | 0.6 mOhm - Ith 200 A 50 Hz for power circuit |
| Power dissipation per pole | 24 W AC-1; 7.9 W AC-3; 7.9 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Power circuit: 1000 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 684932 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 10000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 8 Mcycles |
| Electrical durability | 0.8 Mcycles 200 A AC-1 at Ue |
| Control circuit type | AC at 50/60 Hz |
| Coil technology | Built-in bidirectional peak limiting diode suppressor |
| Control circuit voltage limits | 0.3...0.5 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.15 Uc (-40…55 °C):operational AC 50/60 Hz; 1...1.15 Uc (55…70 °C):operational AC 50/60 Hz |
| Inrush power in VA | 280…350 VA 60 Hz cos phi 0.8 (at 20 °C); 280…350 VA 50 Hz cos phi 0.8 (at 20 °C) |
| Hold-in power consumption in VA | 2…18 VA 60 Hz cos phi 0.3 (at 20 °C); 2…18 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 3…8 W at 50/60 Hz |
| Operating time | 6...20 ms opening; 20...50 ms closing |
| Maximum operating rate | 2400 cyc/h at 60 °C |
| Connections - terminals | Control circuit: lugs-ring terminals - external diameter: 8 mm; Power circuit: lugs-ring terminals - external diameter: 25 mm; Power circuit: bars 1 - busbar cross section: 5 x 25 mm |
| Tightening torque | Control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M3.5; Control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5; Power circuit: 12 N.m - on lugs-ring terminals hexagonal screw head 13 mm M8; Power circuit: 12 N.m - on bars hexagonal screw head 13 mm M8; Control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver pozidriv No 2 M3.5 |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Plate; Rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; IEC 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; UL 60947-4-1; CSA C22.2 No 60947-4-1; JIS C8201-4-1 |
| Product certifications | UL; CSA; CCC; UKCA; CE; EAC; Marine |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor open (6 Gn for 11 ms) |
| Height | 158 mm |
| Width | 120 mm |
| Depth | 136 mm |
| Net weight | 2.5 kg |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Motor control; Resistive load |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 200 A (at |
| [Uc] control circuit voltage | 240 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 17.5 cm |
| Package 1 Width | 19.0 cm |
| Package 1 Length | 21.5 cm |
| Package 1 Weight | 2.19 kg |
| Unit Type of Package 2 | S06 |
| Number of Units in Package 2 | 16 |
| Package 2 Height | 75.0 cm |
| Package 2 Width | 60.0 cm |
| Package 2 Length | 80.0 cm |
| Package 2 Weight | 48.04 kg |
The LC1D1156U7 contactor from the TeSys series by Schneider Electric is a 3-pole contactor for motor control and operation with resistive loads. It is designed for usage categories AC-3, AC-3e, AC-1, and AC-4 and features integrated bidirectional peak-limiting diode suppressor technology that protects the coil from transient voltage spikes. The control circuit voltage is 240 V AC at 50/60 Hz, making it suitable for use in standard industrial control systems. The device is equipped with a safety cover that enables safe operation and maintenance.
This contactor is primarily designed for controlling electric motors, especially in applications with high switching frequency. It is suitable for motors with a rated operational power of 55 kW at 400 V AC-3 and a rated operational current of 115 A under these conditions. Motor power ratings according to UL/CSA standards include 30 hp at 200/208 V, 40 hp at 230/240 V, 75 hp at 460/480 V, and 100 hp at 575/600 V, all for 3-phase motors. Usage category AC-3 covers typical drive applications, while AC-4 is intended for drives with high switching-on and switching-off frequencies.
The contactor features 3 normally closed contacts in the main circuit and additionally includes an auxiliary contact block with 1 normally closed and 1 normally open contact. These auxiliary contacts enable integration into control and monitoring systems, for example for signal indication or feedback of the contactor status. The contacts are mechanically coupled and equipped with mirror contacts, which increases reliability in safety-critical applications. Electrical connections are made via Everlink and spring terminals, ensuring a secure and long-lasting connection. The main circuit terminals are designed for ring cable lugs with an outer diameter of 25 mm and for busbars with a cross-section of 5 x 25 mm. The control circuit terminals are designed for ring cable lugs with an outer diameter of 8 mm.
The contactor coil is designed for an operating voltage of 240 V AC and operates at frequencies of 50/60 Hz. The control circuit voltage limits range from 0.3–0.5 Uc (drop-out voltage) to 0.8–1.15 Uc (operation) at temperatures from -40 to 70 °C. The pickup power is 280 to 350 VA at 50/60 Hz, and the holding power consumption is between 2 and 18 VA. The device’s heat dissipation is 3 to 8 W at 50/60 Hz. The operating time is 6 to 20 ms for opening and 20 to 50 ms for closing. The maximum operating rate is 2400 switching cycles per hour at an ambient temperature of 60 °C. The mechanical life is 8 million switching cycles, and the electrical life is 0.8 million switching cycles at 200 A AC-1 and rated voltage.
The contactor is equipped with compatibility code LC1D, enabling the use of compatible accessories such as auxiliary contact blocks (e.g. LADN136, LADN206, LADN026) and motor protection relays (e.g. LRD4367, LR9D5369). The integrated bidirectional peak-limiting diode suppressor technology protects the coil from transient voltage spikes, increasing its lifespan. Certifications include DNV, CSA, LROS (Lloyds Register of Shipping), GL, CCC, UL, BV, GOST, and RINA, confirming suitability for international and marine applications.
Mounting is done via the designated connection terminals. The tightening torques are 1.2 Nm for control circuit terminals (ring cable lug, M3.5) and 12 Nm for main circuit terminals (ring cable lug, M8) and busbar connections (M8). The use of appropriate tools such as a flat screwdriver (Ø 6 mm) or a Phillips screwdriver (No. 2) is required. The safety cover facilitates mounting and maintenance by providing safe access to the contacts.
The contactor offers high operational reliability through mechanically coupled contacts and mirror contacts, ensuring reliable signal transmission. The integrated peak-limiting diode suppressor technology reduces coil stress and extends service life. Everlink and spring terminals ensure a stable electrical connection, even under high switching cycles. The high mechanical life of 8 million cycles and electrical life of 0.8 million cycles under AC-1 operation make the device suitable for demanding industrial applications. Certifications according to international standards increase acceptance in global projects.