| Complementary |
| Motor power kW | 30 kW at 220/230 V AC 50/60 Hz (AC-3); 55 kW at 380/400 V AC 50/60 Hz (AC-3); 59 kW at 415/440 V AC 50/60 Hz (AC-3); 75 kW at 500 V AC 50/60 Hz (AC-3); 80 kW at 660/690 V AC 50/60 Hz (AC-3); 65 kW at 1000 V AC 50/60 Hz (AC-3); 30 kW at 220/230 V AC 50/60 Hz (AC-3e); 55 kW at 380/400 V AC 50/60 Hz (AC-3e); 59 kW at 415/440 V AC 50/60 Hz (AC-3e); 75 kW at 500 V AC 50/60 Hz (AC-3e); 80 kW at 660/690 V AC 50/60 Hz (AC-3e); 65 kW at 1000 V AC 50/60 Hz (AC-3e); 18.5 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power hp | 30 hp at 200/208 V AC 50/60 Hz for 3 phases motors; 40 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 75 hp at 460/480 V AC 50/60 Hz for 3 phases motors; 100 hp at 575/600 V AC 50/60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 200 A (at 60 °C) for power circuit |
| Irms rated making capacity | 1260 A at 440 V for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 1100 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 250 A 40 °C - 10 min for power circuit; 550 A 40 °C - 1 min for power circuit; 950 A 40 °C - 10 s for power circuit; 1100 A 40 °C - 1 s for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 250 A gG at |
| Average impedance | 0.6 mOhm - Ith 200 A 50 Hz for power circuit |
| Power dissipation per pole | 24 W AC-1; 7.9 W AC-3; 7.9 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Power circuit: 1000 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 684932 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 10000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 8 Mcycles |
| Electrical durability | 0.8 Mcycles 200 A AC-1 at Ue |
| Control circuit type | AC at 50/60 Hz |
| Coil technology | Built-in bidirectional peak limiting diode suppressor |
| Control circuit voltage limits | 0.3...0.5 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.15 Uc (-40…55 °C):operational AC 50/60 Hz; 1...1.15 Uc (55…70 °C):operational AC 50/60 Hz |
| Inrush power in VA | 280…350 VA 60 Hz cos phi 0.8 (at 20 °C); 280…350 VA 50 Hz cos phi 0.8 (at 20 °C) |
| Hold-in power consumption in VA | 2…18 VA 60 Hz cos phi 0.3 (at 20 °C); 2…18 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 3…8 W at 50/60 Hz |
| Operating time | 6...20 ms opening; 20...50 ms closing |
| Maximum operating rate | 2400 cyc/h at 60 °C |
| Connections - terminals | Control circuit: lugs-ring terminals - external diameter: 8 mm; Power circuit: lugs-ring terminals - external diameter: 25 mm; Power circuit: bars 1 - busbar cross section: 5 x 25 mm |
| Tightening torque | Control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M3.5; Control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5; Power circuit: 12 N.m - on lugs-ring terminals hexagonal screw head 13 mm M8; Power circuit: 12 N.m - on bars hexagonal screw head 13 mm M8; Control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver pozidriv No 2 M3.5 |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Rail; Plate |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; IEC 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; UL 60947-4-1; CSA C22.2 No 60947-4-1; JIS C8201-4-1 |
| Product certifications | UL; CSA; CCC; UKCA; CE; EAC; Marine |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor open (6 Gn for 11 ms) |
| Height | 158 mm |
| Width | 120 mm |
| Depth | 136 mm |
| Net weight | 2.5 kg |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load; Motor control |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 200 A (at |
| [Uc] control circuit voltage | 230 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 16.800 cm |
| Package 1 Width | 20.800 cm |
| Package 1 Length | 18.500 cm |
| Package 1 Weight | 2.110 kg |
| Unit Type of Package 2 | S04 |
| Number of Units in Package 2 | 6 |
| Package 2 Height | 30 cm |
| Package 2 Width | 40 cm |
| Package 2 Length | 60 cm |
| Package 2 Weight | 13.310 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 24 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 80.000 cm |
| Package 3 Length | 60.000 cm |
| Package 3 Weight | 61.240 kg |
The LC1D1156P7 contactor from the TeSys series by Schneider Electric is a 3-pole contactor for motor control and operation with resistive loads. It features integrated bidirectional peak-limiting diode suppressor technology, which protects the coil from transient voltage spikes and increases service life. The control circuit voltage is 230 V AC at 50/60 Hz, making it suitable for use in standard networks with this voltage. The device is designed for usage categories AC-1, AC-3, AC-3e, and AC-4, making it suitable for various applications such as operating electric motors and resistive loads.
This contactor is designed for controlling 3-phase motors and is particularly suitable for industrial applications where reliable and safe switching functions are required. It is used in installations with high operating frequencies and mechanical stresses, such as conveyor systems, pumps, or presses. Certifications according to GL, UL, DNV, LROS, GOST, CSA, BV, CCC, and RINA confirm its suitability for international operating conditions, including marine and heavy industrial applications.
The device features 3 main circuit make contacts and additional auxiliary contacts in the configuration of 1 make + 1 break. These auxiliary contacts enable integration into control and monitoring systems, for example, for signal transmission to other components or for feedback of the switching state. The contacts are mechanically coupled and equipped with mirror contacts, which increases reliability in safety-critical applications. The safety cover protects against accidental contact with the contacts and meets requirements for protection rating.
The rated operational current is 200 A at an ambient temperature of 60 °C, with the rated operational power at AC-3 and 400 V being 55 kW. The rated breaking capacity is 1100 A at 440 V, highlighting the contactor’s ability to safely interrupt short-circuit currents. The rated short-time withstand current is defined for various durations, with the maximum value reaching 1100 A for 1 second. The insulation strength is 1000 V for the circuit according to IEC 60947-4-1, ensuring high electrical safety. The overvoltage category III and pollution degree 3 indicate suitability for industrial environments with high loads.
The contactor is compatible with various accessories that extend its functionality. These include auxiliary switch blocks such as the LADN406 (4S non-delayed front) or LAD8N026 (2B non-delayed side), which provide additional contacts for control tasks. Time modules such as the LA4-DT2U (1.5–30 s) enable delayed switching operations. Motor protection relays such as the LRD4367 (95–120 A) or LR9D5369 (90–150 A) can be integrated for motor load monitoring. Interface modules such as LA4-DFB or LA4-DWB are used for communication with control devices.
Connections are made via ring terminal lugs: in the control circuit with an outer diameter of 8 mm, in the power circuit with 25 mm. Alternatively, rails with a cross-section of 5 x 25 mm can be used. The tightening torques are 1.2 Nm for control circuit terminals and 12 Nm for power circuit terminals, with installation using a screwdriver (flat Ø 6 M3.5 or Phillips No. 2 M3.5) or a hexagonal screwdriver (13 mm M8). The maximum operating rate is 2400 switching operations per hour at 60 °C, enabling high load capacity under industrial conditions.
The use of Everlink and spring terminals ensures a secure and long-lasting electrical connection. The integrated coil protection diode reduces electromagnetic interference and extends the coil’s service life. The mechanical life is 8 million switching cycles, and the electrical life is 0.8 million cycles at 200 A AC-1. The operating time is 6–20 ms for opening and 20–50 ms for closing, enabling fast response. The heat dissipation is 3–8 W at 50/60 Hz, limiting thermal load during operation. The approval for safety applications through mechanically coupled contacts and mirror contacts increases reliability in critical systems.