| Complementary |
| Motor power kW | 30 kW at 220/230 V AC 50/60 Hz (AC-3); 55 kW at 380/400 V AC 50/60 Hz (AC-3); 59 kW at 415/440 V AC 50/60 Hz (AC-3); 75 kW at 500 V AC 50/60 Hz (AC-3); 80 kW at 660/690 V AC 50/60 Hz (AC-3); 65 kW at 1000 V AC 50/60 Hz (AC-3); 30 kW at 220/230 V AC 50/60 Hz (AC-3e); 55 kW at 380/400 V AC 50/60 Hz (AC-3e); 59 kW at 415/440 V AC 50/60 Hz (AC-3e); 75 kW at 500 V AC 50/60 Hz (AC-3e); 80 kW at 660/690 V AC 50/60 Hz (AC-3e); 65 kW at 1000 V AC 50/60 Hz (AC-3e); 18.5 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power hp | 30 hp at 200/208 V AC 50/60 Hz for 3 phases motors; 40 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 75 hp at 460/480 V AC 50/60 Hz for 3 phases motors; 100 hp at 575/600 V AC 50/60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 200 A (at 60 °C) for power circuit |
| Irms rated making capacity | 1260 A at 440 V for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 1100 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 250 A 40 °C - 10 min for power circuit; 550 A 40 °C - 1 min for power circuit; 950 A 40 °C - 10 s for power circuit; 1100 A 40 °C - 1 s for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 250 A gG at |
| Average impedance | 0.6 mOhm - Ith 200 A 50 Hz for power circuit |
| Power dissipation per pole | 24 W AC-1; 7.9 W AC-3; 7.9 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Power circuit: 1000 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 684932 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 10000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 8 Mcycles |
| Electrical durability | 0.8 Mcycles 200 A AC-1 at Ue |
| Control circuit type | DC standard |
| Coil technology | With integral suppression device |
| Control circuit voltage limits | 0.75...1.2 Uc (-40…55 °C):operational DC; 0.15...0.4 Uc (-40…70 °C):drop-out DC; 1...1.2 Uc (55…70 °C):operational DC |
| Inrush power in W | 270…365 W (at 20 °C) |
| Hold-in power consumption in W | 2.4…5.1 W at 20 °C |
| Operating time | 20...35 ms closing; 40...75 ms opening |
| Time constant | 25 ms |
| Maximum operating rate | 1200 cyc/h at 60 °C |
| Connections - terminals | Control circuit: lugs-ring terminals - external diameter: 8 mm; Power circuit: lugs-ring terminals - external diameter: 25 mm; Power circuit: bars 1 - busbar cross section: 5 x 25 mm |
| Tightening torque | Control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M3.5; Control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5; Power circuit: 12 N.m - on lugs-ring terminals hexagonal screw head 13 mm M8; Power circuit: 12 N.m - on bars hexagonal screw head 13 mm M8; Control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver pozidriv No 2 M3.5 |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Plate; Rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; IEC 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; UL 60947-4-1; CSA C22.2 No 60947-4-1; JIS C8201-4-1 |
| Product certifications | UL; CSA; CCC; UKCA; CE; EAC; Marine |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor open (6 Gn for 11 ms) |
| Height | 158 mm |
| Width | 120 mm |
| Depth | 136 mm |
| Net weight | 2.5 kg |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Motor control; Resistive load |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 200 A (at |
| [Uc] control circuit voltage | 110 V DC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 16.800 cm |
| Package 1 Width | 20.800 cm |
| Package 1 Length | 18.500 cm |
| Package 1 Weight | 2.110 kg |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 2 |
| Package 2 Height | 30 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 4.640 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 16 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 80.000 cm |
| Package 3 Length | 60.000 cm |
| Package 3 Weight | 45.120 kg |
The LC1D1156FD contactor from the TeSys series by Schneider Electric is a 3-pole contactor for motor control and operation with resistive loads. It is designed for use in industrial plants where reliable and safe switching functions are required under high loads. The device features a control circuit voltage of 110 V DC and is rated for usage categories AC-1, AC-3, AC-3e, and AC-4, with AC-3 being the standard category for motor drives. The rated operational power is 55 kW at 400 V AC-3, with the rated operational current Ie at 115 A. The maximum current load in the circuit is 200 A, enabling use with larger motors. The coil is equipped with an integrated suppression unit to stabilize switching operations and minimize electromagnetic interference.
Applications
This contactor is suitable for controlling 3-phase motors in various industrial applications, such as in manufacturing, packaging technology, or conveyor system control. The specified motor powers according to UL/CSA standards include 30 hp at 200/208 V AC, 40 hp at 230/240 V AC, 75 hp at 460/480 V AC, and 100 hp at 575/600 V AC. The AC-4 usage category also allows use in drives with high inrush currents, such as cranes or pumps. Certifications according to UL, CSA, CCC, GOST, and other international standards ensure suitability for various markets.
Functions and Features in Detail
The contactor includes 3 closed contacts in the main circuit and integrated auxiliary contacts with a configuration of 1 closed and 1 open contact. These auxiliary contacts are mechanically linked and enable feedback of the switching status to control devices or safety functions. The contacts are designed for high durability, with a mechanical life of 8 million switching cycles. The electrical life is 0.8 million cycles at 200 A AC-1. The operating time is 20–35 ms for closing and 40–75 ms for opening, ensuring fast response during switching operations. The coil has a holding power consumption of 2.4 to 5.1 W at 20 °C, enabling efficient energy use.
Technology Explained Simply
The coil technology with integrated suppression unit reduces magnetic interference and ensures clean switching performance. The control circuit voltage of 110 V DC is typical for industrial control systems. The rated surge withstand voltage is 8 kV, ensuring high insulation strength against overvoltages. The overvoltage category III and pollution degree 3 make the device suitable for industrial environments with increased pollution risk. The rated insulation voltage is 1000 V for the circuit according to IEC 60947-4-1, ensuring safe insulation even at high voltages.
Compatibility and Accessories
The contactor is compatible with various accessories, including motor protection relays from the LR9D5369, LRD3359, LRD3363, LRD4367, and LRD4365 series, designed for different current ranges. Additionally, auxiliary switch blocks such as LADN226, LADN316, LADN046, LADN116, LADN136, LADN026, LADN206, LAD8N116, LAD8N206, and LAD8N026 can be used to extend the number of auxiliary contacts. Combining it with a motor protection relay enables complete motor control with overload protection. The compatibility code LC1D allows use with other components in the TeSys series.
Mounting and Installation
Connections are made via ring cable lug terminals with an outer diameter of 8 mm for the control circuit and 25 mm for the main circuit. Alternatively, rails with a cross-section of 5 x 25 mm can be used. The tightening torques are 1.2 Nm for control circuit terminals and 12 Nm for main circuit terminals, with screws having a hexagonal head 13 mm (M8) to be installed. Mounting is done in standard control panels, with dimensions of 120 mm (width) x 158 mm (height) x 136 mm (depth) to be considered. The maximum operating rate is 1200 switching cycles per hour at 60 °C, enabling high load capacity in continuously operated plants.
Operational Advantages
The contactor offers high reliability through mechanically linked contacts and mirror contacts suitable for safety applications. The use of Everlink and spring terminals ensures a secure and long-lasting electrical connection. The integrated suppression unit reduces electromagnetic interference and improves switching quality. Certifications according to international standards such as UL, CSA, CCC, GOST, and others enable use in global markets. The high mechanical and electrical life reduces maintenance costs and increases operational safety.
Safety Aspects
The device is designed for use in environments with increased pollution risk (pollution degree 3) and overvoltage category III. The rated insulation voltage of 1000 V for the main circuit and 690 V for the signal circuit ensures safe insulation. The rated breaking capacity is 1100 A at 440 V, enabling safe interruption during short-circuit currents. The rated short-time current withstand is defined for various time intervals, with maximum withstand at 1100 A for 1 second. The safety cover protects against unintended access to moving parts.