| Complementary |
| Motor power kW | 30 kW at 220/230 V AC 50/60 Hz (AC-3); 55 kW at 380/400 V AC 50/60 Hz (AC-3); 59 kW at 415/440 V AC 50/60 Hz (AC-3); 75 kW at 500 V AC 50/60 Hz (AC-3); 80 kW at 660/690 V AC 50/60 Hz (AC-3); 65 kW at 1000 V AC 50/60 Hz (AC-3); 30 kW at 220/230 V AC 50/60 Hz (AC-3e); 55 kW at 380/400 V AC 50/60 Hz (AC-3e); 59 kW at 415/440 V AC 50/60 Hz (AC-3e); 75 kW at 500 V AC 50/60 Hz (AC-3e); 80 kW at 660/690 V AC 50/60 Hz (AC-3e); 65 kW at 1000 V AC 50/60 Hz (AC-3e); 18.5 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power hp | 30 hp at 200/208 V AC 50/60 Hz for 3 phases motors; 40 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 75 hp at 460/480 V AC 50/60 Hz for 3 phases motors; 100 hp at 575/600 V AC 50/60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 200 A (at 60 °C) for power circuit |
| Irms rated making capacity | 1260 A at 440 V for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 1100 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 250 A 40 °C - 10 min for power circuit; 550 A 40 °C - 1 min for power circuit; 950 A 40 °C - 10 s for power circuit; 1100 A 40 °C - 1 s for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 250 A gG at |
| Average impedance | 0.6 mOhm - Ith 200 A 50 Hz for power circuit |
| Power dissipation per pole | 24 W AC-1; 7.9 W AC-3; 7.9 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Power circuit: 1000 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 684932 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 10000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 8 Mcycles |
| Electrical durability | 0.8 Mcycles 200 A AC-1 at Ue |
| Control circuit type | DC standard |
| Coil technology | With integral suppression device |
| Control circuit voltage limits | 0.75...1.2 Uc (-40…55 °C):operational DC; 0.15...0.4 Uc (-40…70 °C):drop-out DC; 1...1.2 Uc (55…70 °C):operational DC |
| Inrush power in W | 270…365 W (at 20 °C) |
| Hold-in power consumption in W | 2.4…5.1 W at 20 °C |
| Operating time | 20...35 ms closing; 40...75 ms opening |
| Time constant | 25 ms |
| Maximum operating rate | 1200 cyc/h at 60 °C |
| Connections - terminals | Control circuit: lugs-ring terminals - external diameter: 8 mm; Power circuit: lugs-ring terminals - external diameter: 25 mm; Power circuit: bars 1 - busbar cross section: 5 x 25 mm |
| Tightening torque | Control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M3.5; Control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5; Power circuit: 12 N.m - on lugs-ring terminals hexagonal screw head 13 mm M8; Power circuit: 12 N.m - on bars hexagonal screw head 13 mm M8; Control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver pozidriv No 2 M3.5 |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Rail; Plate |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; IEC 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; UL 60947-4-1; CSA C22.2 No 60947-4-1; JIS C8201-4-1 |
| Product certifications | UL; CSA; CCC; UKCA; CE; EAC; Marine |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor open (6 Gn for 11 ms) |
| Height | 158 mm |
| Width | 120 mm |
| Depth | 136 mm |
| Net weight | 2.5 kg |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Motor control; Resistive load |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 200 A (at |
| [Uc] control circuit voltage | 24 V DC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 19.500 cm |
| Package 1 Width | 24.000 cm |
| Package 1 Length | 21.000 cm |
| Package 1 Weight | 2.180 kg |
| Unit Type of Package 2 | P06 |
| Number of Units in Package 2 | 27 |
| Package 2 Height | 75.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 71.860 kg |
TeSys LC1D power contactor. 3-pole, 3 NO contacts. Additional auxiliary contacts - 1 NO + 1 NC contact, rated operating power at AC-3, 400 V 55 kW, rated operating current Ie at AC-3, 400 V 115 A, coil 24 V DC. Dimensions (WxHxD) 120x158x136 mm, weight 2.5 kg. Category AC-3, AC-1, AC-4. with integral suppression unit. Quick and easy setup. Safe and durable power connection with Everlink and spring terminals. Suitable for safety applications due to mechanically coupled contacts and mirror contacts. Certifications according to GOST, CCC, RINA, CSA, UL, BV, GL, LROS (Lloyds register of shipping), DNV. Product standards in accordance with.