| Complementary |
| Motor power kW | 2.2 kW at 220/230 V AC 50/60 Hz (AC-3); 4 kW at 380/400 V AC 50/60 Hz (AC-3); 4 kW at 415/440 V AC 50/60 Hz (AC-3); 5.5 kW at 500 V AC 50/60 Hz (AC-3); 5.5 kW at 660/690 V AC 50/60 Hz (AC-3); 2.2 kW at 220/230 V AC 50/60 Hz (AC-3e); 4 kW at 380/400 V AC 50/60 Hz (AC-3e); 4 kW at 415/440 V AC 50/60 Hz (AC-3e); 5.5 kW at 500 V AC 50/60 Hz (AC-3e); 5.5 kW at 660/690 V AC 50/60 Hz (AC-3e); 2.2 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power hp | 1 hp at 230/240 V AC 50/60 Hz for 1 phase motors; 2 hp at 200/208 V AC 50/60 Hz for 3 phases motors; 2 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 5 hp at 460/480 V AC 50/60 Hz for 3 phases motors; 7.5 hp at 575/600 V AC 50/60 Hz for 3 phases motors; 0.33 hp at 115 V AC 50/60 Hz for 1 phase motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 25 A (at 60 °C) for power circuit; 10 A (at 60 °C) for signalling circuit |
| Irms rated making capacity | 250 A at 440 V for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 250 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 105 A 40 °C - 10 s for power circuit; 210 A 40 °C - 1 s for power circuit; 30 A 40 °C - 10 min for power circuit; 61 A 40 °C - 1 min for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 25 A gG at |
| Average impedance | 2.5 mOhm - Ith 25 A 50 Hz for power circuit |
| Power dissipation per pole | 1.56 W AC-1; 0.2 W AC-3; 0.2 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 15 Mcycles |
| Electrical durability | 0.6 Mcycles 25 A AC-1 at Ue |
| Control circuit type | AC at 50/60 Hz standard |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz |
| Inrush power in VA | 70 VA 60 Hz cos phi 0.75 (at 20 °C); 70 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Hold-in power consumption in VA | 7.5 VA 60 Hz cos phi 0.3 (at 20 °C); 7 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 2…3 W at 50/60 Hz |
| Operating time | 12...22 ms closing; 4...19 ms opening |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Rail; Plate |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; CSA C22.2 No 60947-4-1 |
| Product certifications | UL; CCC; CSA; Marine; UKCA; EAC; CB Scheme |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor open (10 Gn for 11 ms) ; Shocks contactor closed (15 Gn for 11 ms) |
| Height | 77 mm |
| Width | 45 mm |
| Depth | 86 mm |
| Net weight | 0.32 kg |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load; Motor control |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 9 A (at |
| [Uc] control circuit voltage | 230 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.000 cm |
| Package 1 Width | 9.200 cm |
| Package 1 Length | 11.200 cm |
| Package 1 Weight | 342.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 20 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 7.139 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 320 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 125.520 kg |
The LC1D09P7 contactor from the TeSys Deca Advanced series by Schneider Electric is a 3-pole contactor for controlling electrical loads, particularly for motor drives and resistive loads. It features a main contact configuration of 3 closers and integrated auxiliary contacts in the configuration of 1 closer + 1 opener, making it suitable for complex control tasks in industrial installations. The control circuit voltage is 230 V AC at 50/60 Hz, enabling operation in standard alternating current networks. The device is designed for usage categories AC-1, AC-3, AC-3e, and AC-4, with category AC-3 representing the typical application for motor control.
Applications
The contactor is designed for controlling motors with a rated power of up to 4 kW at 380/400 V AC (AC-3). At other voltage levels, the permissible motor powers vary accordingly: 2.2 kW at 220/230 V AC, 5.5 kW at 500 V AC, and 5.5 kW at 660/690 V AC. In category AC-4, which applies to frequent and rapid switching operations, the motor power is 2.2 kW at 400 V AC. The application includes both industrial drives and safety applications, where mechanically interlocked contacts and mirror contacts ensure reliable switching performance.
Functions and Equipment in Detail
The contactor features a safety cover that enables protected access to the contacts and supports compliance with safety regulations. The current connection is made via Everlink technology with spring terminals, ensuring a secure and long-lasting connection. The auxiliary contacts are non-delayed and allow integration into control circuits for signals, feedback, or interlock functions. The coil technology is designed without an integrated wiring module, enabling simple mounting and maintenance.
Technology Explained Simply
The rated operational current is 9 A at AC-3, representing the maximum load the contactor can switch continuously. The conventional thermal current (Ith) is 25 A at 60 °C for the circuit, describing the thermal load capacity under defined conditions. The rated make capacity is 250 A at 440 V for the circuit, demonstrating the contactor’s ability to interrupt high inrush currents. The rated breaking capacity is also 250 A at 440 V, according to IEC 60947. The rated impulse voltage withstand is 6 kV, ensuring insulation strength against transient voltage surges. The overvoltage category III and pollution degree 3 indicate suitability for industrial environments with increased contamination risk.
Compatibility and Accessories
The contactor is compatible with various accessories that extend its functionality. These include auxiliary switch blocks such as the LADN20 (2S non-delayed front-mounted) or LADN22 (2S+2O non-delayed front-mounted), enabling additional switching functions. Time modules such as the LA4-DT0U (0.1–2 s) or LA4DT4U (25–500 s) allow integration of time delays. Mechanical interlocks such as the LAD9V2 or the KIT reversing contactor LAD-9R1V support safe control of multiple contactors. Compatibility with the connection block LA9D3260 and the three-phase busbar system GV2G245 enables flexible integration into existing control panels.
Mounting and Installation
Mounting is done via screw connection, with Everlink technology ensuring a secure and quick connection. Dimensions are 45 mm (width) × 77 mm (height) × 86 mm (depth), allowing compact placement in enclosures. The weight is 0.32 kg. Control circuit voltage limits are defined: at -40 to 70 °C, the drop voltage is 0.3 to 0.6 Uc, and operation occurs at 0.8 to 1.1 Uc (at -40 to 60 °C). The pickup power is 70 VA at 50/60 Hz, the holding power consumption is 7.5 VA at 60 Hz and 7 VA at 50 Hz.
Operational Advantages
The contactor offers a high mechanical life of 15 million switching cycles and an electrical life of 0.6 million cycles at 25 A AC-1. The power loss per pole is 0.2 W at AC-3 and AC-3e, indicating efficient heat generation. Heat dissipation is between 2 and 3 W at 50/60 Hz. Certifications according to GOST, BV, LROS, DNV, CSA, RINA, CCC, UL, and GL confirm compliance with international safety and quality standards. The rated insulation voltage is 690 V for the circuit and 600 V for the signal circuit, with UL and CSA certifications also indicating 600 V. The safety class B10d is 1,369,863 cycles at rated load and 20,000,000 cycles at mechanical load, according to EN/ISO 13849-1.