| Complementary |
| Motor power kW | 2.2 kW at 220/230 V AC 50/60 Hz (AC-3); 4 kW at 380/400 V AC 50/60 Hz (AC-3); 4 kW at 415/440 V AC 50/60 Hz (AC-3); 5.5 kW at 500 V AC 50/60 Hz (AC-3); 5.5 kW at 660/690 V AC 50/60 Hz (AC-3); 2.2 kW at 220/230 V AC 50/60 Hz (AC-3e); 4 kW at 380/400 V AC 50/60 Hz (AC-3e); 4 kW at 415/440 V AC 50/60 Hz (AC-3e); 5.5 kW at 500 V AC 50/60 Hz (AC-3e); 5.5 kW at 660/690 V AC 50/60 Hz (AC-3e); 2.2 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power hp | 1 hp at 230/240 V AC 50/60 Hz for 1 phase motors; 2 hp at 200/208 V AC 50/60 Hz for 3 phases motors; 2 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 5 hp at 460/480 V AC 50/60 Hz for 3 phases motors; 7.5 hp at 575/600 V AC 50/60 Hz for 3 phases motors; 0.33 hp at 115 V AC 50/60 Hz for 1 phase motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 25 A (at 60 °C) for power circuit; 10 A (at 60 °C) for signalling circuit |
| Irms rated making capacity | 250 A at 440 V for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 250 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 105 A 40 °C - 10 s for power circuit; 210 A 40 °C - 1 s for power circuit; 30 A 40 °C - 10 min for power circuit; 61 A 40 °C - 1 min for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 25 A gG at |
| Average impedance | 2.5 mOhm - Ith 25 A 50 Hz for power circuit |
| Power dissipation per pole | 1.56 W AC-1; 0.2 W AC-3; 0.2 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 30 Mcycles |
| Electrical durability | 0.6 Mcycles 25 A AC-1 at Ue |
| Control circuit type | DC standard |
| Coil technology | Built-in bidirectional peak limiting diode suppressor |
| Control circuit voltage limits | 0.1...0.25 Uc (-40…70 °C):drop-out DC; 0.7...1.25 Uc (-40…60 °C):operational DC; 1...1.25 Uc (60…70 °C):operational DC |
| Inrush power in W | 5.4 W (at 20 °C) |
| Hold-in power consumption in W | 5.4 W at 20 °C |
| Operating time | 63 ±15 % ms closing; 20 ±20 % ms opening |
| Time constant | 28 ms |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Plate; Rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; CSA C22.2 No 60947-4-1 |
| Product certifications | UL; CCC; CSA; Marine; UKCA; EAC; CB Scheme |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor open (10 Gn for 11 ms) ; Shocks contactor closed (15 Gn for 11 ms) |
| Height | 77 mm |
| Width | 45 mm |
| Depth | 95 mm |
| Net weight | 0.48 kg |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Motor control; Resistive load |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 9 A (at |
| [Uc] control circuit voltage | 24 V DC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.500 cm |
| Package 1 Width | 10.000 cm |
| Package 1 Length | 12.000 cm |
| Package 1 Weight | 525.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 15 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 8.160 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 240 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 137.280 kg |
The LC1D09BD contactor from the TeSys Deca Advanced series by Schneider Electric is a 3-pole contactor for motor control and operation with resistive loads. It is designed for use in industrial installations where reliable and safe control of electrical consumers is required. The device features a control circuit with a rated voltage of 24 V DC and is designed for an operating rating of 9 A. The integrated bidirectional amplitude-limiting diode protects the coil from voltage spikes and increases the device's service life. The contacts are mechanically coupled and equipped with mirror contacts, enhancing reliability in safety applications.
Applications
The contactor is suitable for various usage categories, including AC-1, AC-3, AC-3e, and AC-4. At an operating voltage of 400 V AC and category AC-3, the motor power is 4 kW. Category AC-4 allows use under high mechanical stress, for example, in drives with frequent starts and stops. The rated voltage of the circuit is 690 V, with insulation strength specified according to IEC-4-1. The overvoltage category III and pollution degree 3 make the device suitable for industrial environments with increased stress.
Functions and Equipment in Detail
The contactor features 3 normally closed contacts in the main circuit and additionally includes one auxiliary contact with 1 normally closed and 1 normally open contact. The contacts are designed for a safe and long-lasting current connection, with Everlink technology and spring terminals ensuring a stable connection. The mechanical life is 30 million switching cycles, while the electrical life at 25 A AC-1 and rated voltage is 0.6 million switching cycles. The operating time is 63 ±15 % ms for closing and 20 ±20 % ms for opening. The time constant is 28 ms.
Technology Explained Simply
The contactor coil operates at 24 V DC and includes an integrated bidirectional peak-limiting diode suppressor that reduces voltage spikes when the coil is switched off. The pickup power is 5.4 W at 20 °C, as is the holding power consumption. The control circuit voltage limits range from 0.1–0.25 Uc (drop voltage) to 0.7–1.25 Uc (operation) at temperatures from -40 to 70 °C. The rated impulse voltage withstand is 6 kV, ensuring high insulation strength for use in industrial installations.
Compatibility and Accessories
The contactor is compatible with various accessories, including auxiliary switch blocks such as LADN11 (1NO1NC), LADN20 (2NO), LADN22 (2NO+2NC), and LADN31 (3NO1NC), which can be mounted front-side. Time blocks such as LADR0 (delayed release 0.10–3.00 s) or LADT0 (delayed pickup 0.10–3.00 s) enable time-controlled functions. For mounting in busbar systems, products such as GV2G245 or GV2G445 are available. Additionally, special diodes such as LAD4TBDL (24 VDC) or freewheeling diodes such as LAD4DDL are available. For reversing contactor applications, kits such as LAD-9R1V or LAD9R1 are available.
Mounting and Installation
Mounting is done via screw terminals, with Everlink technology ensuring a secure and long-lasting connection. Dimensions are 45 mm (width) × 77 mm (height) × 95 mm (depth). The device is designed for use in enclosures and industrial controls. The maximum operating rate is 3600 switching cycles per hour at 60 °C. Certifications include CSA, UL, GOST, DNV, CCC, GL, BV, and RINA, enabling use in international installations.
Advantages in Operation
The contactor offers high reliability through mechanically coupled contacts and mirror contacts, ensuring a secure switching function. The integrated diode suppression reduces stress on control electronics. Spring terminals and Everlink technology ensure a stable current connection. Certifications according to international standards enable use in various industries, including marine technology (LROS) and power supply. The high service life and robust construction make the device suitable for demanding industrial applications.