| Complementary |
| Motor power kW | 2.2 kW at 220...230 V AC 50/60 Hz (AC-3); 4 kW at 380...400 V AC 50/60 Hz (AC-3); 4 kW at 415...440 V AC 50/60 Hz (AC-3); 5.5 kW at 500 V AC 50/60 Hz (AC-3); 5.5 kW at 660...690 V AC 50/60 Hz (AC-3); 2.2 kW at 400 V AC 50/60 Hz (AC-4); 2.2 kW at 220...230 V AC 50/60 Hz (AC-3e); 4 kW at 380...400 V AC 50/60 Hz (AC-3e); 4 kW at 415...440 V AC 50/60 Hz (AC-3e); 5.5 kW at 500 V AC 50/60 Hz (AC-3e); 5.5 kW at 660...690 V AC 50/60 Hz (AC-3e) |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 25 A (at 60 °C) for power circuit; 10 A (at 60 °C) for signalling circuit |
| Irms rated making capacity | 250 A at 440 V for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 250 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 105 A 40 °C - 10 s for power circuit; 210 A 40 °C - 1 s for power circuit; 30 A 40 °C - 10 min for power circuit; 61 A 40 °C - 1 min for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 25 A gG at |
| Average impedance | 2.5 mOhm - Ith 25 A 50 Hz for power circuit |
| Power dissipation per pole | 1.56 W AC-1; 0.2 W AC-3; 0.2 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-1 |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 15 Mcycles |
| Electrical durability | 0.6 Mcycles 25 A AC-1 at Ue |
| Control circuit type | AC at 50/60 Hz standard |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz |
| Inrush power in VA | 70 VA 60 Hz cos phi 0.75 (at 20 °C); 70 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Hold-in power consumption in VA | 7.5 VA 60 Hz cos phi 0.3 (at 20 °C); 7 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 2…3 W at 50/60 Hz |
| Operating time | 12...22 ms closing; 4...19 ms opening |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Plate; Rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN 60947-4-1; IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; CCC; cULus; CE; UKCA; EU-RO-MR by DNV |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor open (10 Gn for 11 ms) |
| Height | 107 mm |
| Width | 45 mm |
| Depth | 86 mm |
| Net weight | 387 g |
| Main |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Motor control; Resistive load |
| Utilisation category | AC-1; AC-3; AC-3e; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 9 A (at |
| [Uc] control circuit voltage | 48 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 10.000 cm |
| Package 1 Width | 5.200 cm |
| Package 1 Length | 11.500 cm |
| Package 1 Weight | 412.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 15 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 6.460 kg |
The LC1D09AE7 contactor from the TeSys Deca Advanced series by Schneider Electric is a 3-pole contactor for motor control and operation with resistive loads. It is designed for usage categories AC-1, AC-3, AC-3e, and AC-4, and features a rated operational current of 9 A at a rated operational voltage of 400 V AC (AC-3). The coil is designed for a control circuit voltage of 48 V AC at 50/60 Hz. The device is equipped with a protective cover and offers fast and secure electrical connection via SnapIN connection terminals.
Applications
This contactor is suitable for controlling electric motors in industrial plants, particularly in applications with medium to high loads. At an operating voltage of 400 V AC (AC-3), the motor power is 4 kW. The AC-4 usage category enables use under high mechanical stress, such as frequent start-stop cycles. The AC-3e category allows operation under increased thermal stress requirements. Applications in safety systems are supported by mechanically interlocked contacts and auxiliary contacts, ensuring secure disconnection.
Functions and Equipment in Detail
The device features three closing contacts in the main circuit (3P) and additional auxiliary contacts configured as 1 closing + 1 opening contact. The auxiliary contacts are mechanically linked and comply with IEC 60947-5-1. The mirror contact (1 opening) complies with IEC 60947-4-1 and enables monitoring of the contactor status. The coil technology is designed without an integrated switching module, enabling simple installation and maintenance. The operating time is 12–22 ms for closing and 4–19 ms for opening.
Technology Explained Simply
The rated make capacity is 250 A at 440 V for the circuit, ensuring high switching capability during short-term load peaks. The rated breaking capacity of 250 A at 440 V meets the requirements of IEC 60947. The rated short-time current withstand is 105 A at 40 °C for 10 seconds in the circuit, ensuring stability during short-term overloads. The rated insulation voltage is 690 V for power and signal circuits, ensuring high electrical safety. The overvoltage category III and pollution degree 3 make the device suitable for industrial environments with increased pollution risk. The rated impulse voltage withstand is 6 kV, ensuring robustness against transient voltage surges.
Compatibility and Accessories
The contactor is equipped with compatibility code LC1D and can be combined with various accessories, including delayed auxiliary switch blocks (e.g. LAD-R4, LADR2, LADR0), time blocks (LADT0, LADT2), motor protection relays (LRD14, LRD02, LRD10), and motor protection switches (GV2ME08A, GV2ME02A, GV2ME03A, GV2ME04A, GV2ME01A, GV2ME05A). Auxiliary switch blocks such as LADN02A, LADN04A, LADN11A, LADN13A, LADN20A, and LADN22A allow expansion of the contact configuration. Combination with motor protection relays or switches is required for safe motor control.
Mounting and Installation
Mounting is done via SnapIN connection terminals, enabling fast and secure electrical connection. Dimensions are 45 mm (width) × 107 mm (height) × 86 mm (depth). The maximum operating rate is 3600 switching cycles per hour at 60 °C, enabling high operational frequency in industrial plants. The heat dissipation is 2–3 W at 50/60 Hz, limiting thermal load during operation.
Operational Advantages
The mechanical life is 15 million switching cycles, and the electrical life is 0.6 million switching cycles at 25 A AC-1. The safety level corresponds to EN/ISO 13849-1 with a B10d value of 1,369,863 cycles at rated load and 20,000,000 cycles at mechanical load. The control circuit voltage limits ensure reliable operation during voltage fluctuations. The pickup power is 70 VA at 50/60 Hz, and the holding power consumption is 7–7.5 VA, enabling efficient energy use. The minimum switching voltage for the signal circuit is 17 V, and the minimum switching current is 5 mA, ensuring reliability under low-load conditions.