| Complementary |
| Compatibility code | LC1D |
| Pole contact composition | 2 NO + 2 NC |
| Protective cover | With |
| [Ith] conventional free air thermal current | 20 A (at 60 °C) for power circuit; 10 A (at 60 °C) for signalling circuit |
| Irms rated making capacity | 250 A at 440 V for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 250 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 105 A 40 °C - 10 s for power circuit; 210 A 40 °C - 1 s for power circuit; 30 A 40 °C - 10 min for power circuit; 61 A 40 °C - 1 min for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 25 A gG at |
| Average impedance | 2.5 mOhm - Ith 25 A 50 Hz for power circuit |
| Power dissipation per pole | 1.56 W AC-1 |
| [Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 15 Mcycles |
| Electrical durability | 0.3 Mcycles 20 A AC-1 at Ue |
| Control circuit type | AC at 50/60 Hz |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.3...0.6 Uc (-40…60 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz |
| Inrush power in VA | 70 VA 60 Hz cos phi 0.75 (at 20 °C); 70 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Hold-in power consumption in VA | 7.5 VA 60 Hz cos phi 0.3 (at 20 °C); 7 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 2…3 W at 50/60 Hz |
| Operating time | 12...22 ms closing; 4...19 ms opening |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Plate; Rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; CSA C22.2 No 60947-4-1 |
| Product certifications | UL; CCC; CSA; Marine; UKCA; EAC; CB Scheme |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor open (10 Gn for 11 ms) ; Shocks contactor closed (15 Gn for 11 ms) |
| Height | 85 mm |
| Width | 45 mm |
| Depth | 92 mm |
| Net weight | 0.365 kg |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load |
| Utilisation category | AC-1 |
| Poles description | 4P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 20 A (at |
| [Uc] control circuit voltage | 24 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.500 cm |
| Package 1 Width | 9.500 cm |
| Package 1 Length | 12.000 cm |
| Package 1 Weight | 392.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 16 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 6.786 kg |
The LC1D098B7 contactor from the TeSys Deca Advanced series by Schneider Electric is a 4-pole contactor designed for use in industrial applications. It is intended for resistive loads and corresponds to usage category AC-1. The primary function of the contactor is the safe and reliable control of electrical circuits, with a rated operational current of 20 A. The control circuit voltage is 24 V AC at 50/60 Hz, making it suitable for applications with standard supply voltages. The device features a contact configuration of 2 normally closed and 2 normally open contacts in the main circuit, supplemented by additional auxiliary contacts with 1 normally closed and 1 normally open contact, mechanically linked to ensure secure signal transmission. The auxiliary contacts comply with standards IEC 60947-5-1 and IEC 60947-4-1, with the mirror contact providing additional safety functions.
Applications
This contactor is designed for use in industrial applications, particularly in applications involving resistive loads, such as heating, lighting, or resistance operation. The AC-1 category makes it suitable for applications where no inductive or capacitive loads are present in the main circuit. Certifications according to DNV, GL, UL, CCC, RINA, CSA, BV, LROS (Lloyds Register of Shipping), and GOST highlight its suitability for international and marine applications, where high safety and reliability requirements apply.
Functions and Equipment in Detail
The device features a safety cover that enables protected access to the contacts. Electrical connections are made via Everlink and spring terminals, ensuring a secure and long-lasting connection. The tightening torque is 1.7 Nm for all screw terminals, both in the main and control circuits, with installation possible using a flat-head screwdriver Ø 6 or Phillips No. 2. The maximum operating rate is 3600 switching cycles per hour at an ambient temperature of 60 °C, enabling high load capacity in continuously operated installations.
Technology Explained Simply
The contactor coil is designed for 24 V AC and operates at frequencies of 50/60 Hz. The pickup power is 70 VA at 50 and 60 Hz, while the holding power consumption is 7 VA (50 Hz) or 7.5 VA (60 Hz). The operating time is 12–22 ms for closing and 4–19 ms for opening, enabling rapid response to control signals. The rated insulation voltage is 690 V for the circuit and complies with standards IEC 60947-4-1, CSA, and UL for 600 V. The impulse voltage withstand is 6 kV, ensuring high electrical strength even under transient voltage surges. The overvoltage category III and pollution degree 3 indicate suitability for industrial environments with increased contamination risk.
Compatibility and Accessories
The contactor is compatible with various accessories, including auxiliary switch blocks such as LADN31, LADN11, LADN40, LADN04, LADN02, LADN13, LAD8N02, and LAD8N11, which provide additional normally closed and normally open contacts depending on requirements. Time delay blocks such as LADR0, LADR2, LADT2, LADT4, and LADT0 enable delayed switching operations. Motor protection relays such as LRD04 and LRD03, as well as varistors such as LAD-4VE and control module LAD4RCE, are also available to adapt the contactor to specific applications. Combining these components extends functionality for complex control and protection systems.
Mounting and Installation
Mounting is done via screw terminals with a tightening torque of 1.7 Nm. Dimensions are 45 mm (width) × 85 mm (height) × 92 mm (depth), allowing compact placement in enclosures. Heat dissipation is 2–3 W at 50/60 Hz, requiring efficient cooling in enclosed switchgear. The operating temperature range is from -40 °C to +60 °C, with control circuit voltage limits at 0.3–0.6 Uc (drop voltage) and 0.8–1.1 Uc (operation).
Operational Advantages
The contactor offers a high mechanical life of 15 million switching cycles and an electrical life of 300,000 cycles at 20 A AC-1. The rated short-time withstand current is 105 A at 10 s and 210 A at 1 s in the circuit, ensuring high stability during short-term overloads. The rated breaking capacity is 250 A at 440 V, ensuring reliability under high loads. The safety cover and mechanically linked auxiliary contacts enhance safety in critical applications. Certifications according to international standards guarantee suitability for global and marine applications.