| Complementary |
| Mounting location | Side |
| [Ui] rated insulation voltage | 600 V conforming to IEC 60947-5-1; 600 V - certifications CSA; 600 V - certifications UL |
| [Ue] rated operational voltage | 600 V AC 25...400 Hz |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) |
| Irms rated making capacity | 140 A AC conforming to IEC 60947-5-1; 250 A DC conforming to IEC 60947-5-1 |
| Permissible short-time rating | 100 A 60 °C 1 s; 120 A 60 °C 500 ms; 140 A 60 °C 100 ms |
| Protection type | GG fuse 10 A |
| Mechanical durability | 8 Mcycles |
| Minimum switching current | 1 mA |
| Minimum switching voltage | 17 V |
| Non-overlap time | 1.5 ms on de-energisation no overlap between NC and NO contact; 1.5 ms on energisation no overlap between NC and NO contact |
| Insulation resistance | > 10 MOhm |
| Height | 55.8 mm |
| Width | 15.4 mm |
| Depth | 84.8 mm |
| Net weight | 0.05 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-5-1; UL 60947-5-1; CSA C22.2 No 60947-5-1; GB 14048.5; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-1; UL 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; CCC; cULus; CE; UKCA |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Protective treatment | TH |
| Ambient air temperature for operation | -25…60 °C |
| Ambient air temperature for storage | -60…80 °C |
| Operating altitude | 3000 m |
| Logistical informations |
| Country of origin | CN |
| Main |
| Range compatibility | TeSys G LC1G |
| Range of product | TeSys G |
| Range | TeSys |
| Device short name | LAG8N |
| Product or component type | Auxiliary contact block |
| Auxiliary contacts operation | Instantaneous |
| Pole contact composition | 1 NO + 1 NC |
| Connections - terminals | Screw clamp terminals0.75…2.5 mm²solid stranded without cable end; Screw clamp terminals0.75…2.5 mm²flexible with cable end |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 3.400 cm |
| Package 1 Width | 6.700 cm |
| Package 1 Length | 9.500 cm |
| Package 1 Weight | 59.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 64 |
| Package 2 Height | 15 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 3.969 kg |
TeSys Hilfsschalter Block für TeSys control - Giga Leistungsschütz mit einem Schließer und einem Öffner Kontakt. Schaltkontakte für zuverlässige Signalführung bei minimal 17V / 1mA wie bei Eingängen onPCs oder Controllern mit sehr geringer Belastbarkeit. Die Hilfskontakte werden an der Seite montiert und verfügen über wartungsfreundliche Push-In klemmen. Der Hilfskontaktblock hat die Schutzart IP20 gemäß IEC 60529. Green Premium-konform (RoHs/Reach).