| Complementary |
| Irms rated making capacity | 140 A AC; 250 A DC |
| Permissible short-time rating | 100 A 60 °C 1 s; 120 A 60 °C 500 ms; 140 A 60 °C 100 ms |
| Protection type | GG fuse 10 A |
| Mechanical durability | 5 Mcycles |
| Minimum switching current | 5 mA |
| Minimum switching voltage | 17 V |
| Non-overlap time | 1.5 ms on de-energisation no overlap between NC and NO contact; 1.5 ms on energisation no overlap between NC and NO contact |
| Insulation resistance | > 10 MOhm |
| Connections - terminals | Lugs-ring terminals (external diameter: 8 mm) |
| Tightening torque | 1.7 N.m - with screwdriver flat Ø 6 mm; 1.7 N.m - with screwdriver Philips No 2; 1.7 N.m - with screwdriver pozidriv No 2 |
| Height | 48 mm |
| Width | 44 mm |
| Depth | 61 mm |
| Colour | Dark grey |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Environmental characteristic | Normal environment |
| IP degree of protection | IP2X conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068 |
| Ambient air temperature for storage | -60…80 °C |
| Ambient air temperature for operation | -40…70 °C |
| Operating altitude | 3000 m |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys; TeSys Deca |
| Product name | TeSys Deca |
| Product or component type | Time delay auxiliary contact block |
| Range compatibility | TeSys D CAD; TeSys D LC1D; TeSys F LC1F; TeSys F CR1F; TeSys Deca CAD; TeSys Deca LC1D |
| Mounting location | Front |
| Pole contact composition | 1 NO + 1 NC |
| Contacts operation | Time delay |
| Timer type | On delay |
| Time delay range | 10...180 s |
| [Ue] rated operational voltage | 690 V AC 25...400 Hz |
| [Ie] rated operational current | 6 A at 120 V AC-15; 1.04 A at 690 V AC-15; 0.55 A at 125 V DC-13; 0.1 A at 600 V DC-13 |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-5-1; 600 V conforming to UL; 600 V conforming to CSA |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) |
| Standards | EN/IEC 60947-5-1; UL 60947-5-1; CSA C22.2 No 60947-5-1; GB/T 14048.5; EN 50012; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ |
| Product certifications | CB; UL; CSA; CCC; UKCA |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 4.900 cm |
| Package 1 Width | 5.400 cm |
| Package 1 Length | 6.700 cm |
| Package 1 Weight | 72.000 g |
The article LADT46 from Schneider Electric is a time-delayed auxiliary switch block from the TeSys Deca series. It serves as an add-on module for power contactors of the TeSys D and TeSys F series, as well as for the TeSys Deca product family, enabling time-delayed control of auxiliary functions. The switch block is designed for mounting on the front side of contactors and provides an on-delay in the range of 10 to 180 seconds. This function is used to implement time-staggered switching operations in industrial plants, for example, to avoid current peaks or for sequential start-up of motors.
Applications
LADT46 is designed for use in industrial control and switching installations where a controlled time-delayed switching function is required. It is frequently used in plants with multiple motors or loads, where start-up is to occur sequentially to reduce the load on the power grid. The application is typically in combination with power contactors from the TeSys D and TeSys F series, with compatibility based on specific model designations such as LC1D, LC1F, CR1F, CAD, or LC1D-TeSys Deca.
Functions and Equipment in Detail
The auxiliary switch block features a contact arrangement of 1 normally open (S) and 1 normally closed (Oe), controlled by a mechanical time delay. The on-delay allows the contact to switch only after a preset delay time (between 10 and 180 seconds) once the contactor is activated. The contacts are designed to avoid overlap between the normally closed and normally open contacts — the non-overlap time is 1.5 ms during de-energization and during actuation. This ensures a safe and precise switching sequence. The rated operational voltage is 690 V AC in the range of 25 to 400 Hz. The rated switching currents are 6 A at 120 V AC-15, 1.04 A at 690 V AC-15, 0.55 A at 125 V DC-13, and 0.1 A at 600 V DC-13. The minimum switching voltage is 17 V, and the minimum switching current is 5 mA.
Technology Explained Simply
The time delay is achieved through a mechanical system that maintains a defined delay period after the contactor is energized, before the contact switches. This principle is commonly used in industrial controls to distribute the load on the network or to ensure that certain components are activated in a defined sequence. The insulation resistance values exceed 10 MΩ, ensuring high electrical insulation and thus safe operation. The rated insulation voltage is 690 V according to IEC 60947-5-1, and 600 V according to UL and CSA. The permissible short-time performance is 100 A at 60 °C for 1 second, 120 A for 500 ms, and 140 A for 100 ms. The mechanical life is 5 million switching cycles, indicating high robustness and longevity.
Compatibility and Accessories
LADT46 is compatible with various power contactors from the TeSys D and TeSys F series, including models such as LC1D256G7, LC1D1156BD, LC1D80A6P7, LC1D65A6U7, LC1D1156L7, LC1D096ND, LC1D326GD, LC1D1150046P7, LC1D256L7, LC1D126G7, LC1D186L7, LC1D956P7, LC1D326F7, LC1D096G7, LC1D126BD, LC1D1506F7, LC1D1150046BD, LC1D186P7, LC1D65A6P7, and LC1D65A6B7. These contactors are available in various power ratings and voltage ranges, enabling integration of the time block into different plant configurations. Combining with these contactors extends their functionality with time-delayed auxiliary functions.
Mounting and Installation
The time block is mounted on the front side of the power contactor and is designed for easy installation. Connections are made via ring terminal lugs with an outer diameter of 8 mm. The required tightening torque is 1.7 Nm, and mounting can be performed using a flat screwdriver (Ø 6 mm), a Phillips screwdriver No. 2, or a positioning screwdriver No. 2. The module dimensions are 44 mm (width), 48 mm (height), and 61 mm (depth). The degree of protection is IP2x according to IEC 60529, providing protection against finger contact and against solid foreign objects larger than 12.5 mm. The operating temperature range is from -40 °C to +70 °C, and the storage temperature range is from -60 °C to +80 °C. The operating altitude is up to 3,000 m above sea level.
Advantages in Operation
The use of LADT46 enables precise time-controlled switching of auxiliary functions in industrial plants. The high mechanical life of 5 million switching cycles and the robust construction ensure reliable operation over a long period. The clear contact arrangement with 1S+1Oe and the secure non-overlap of contacts prevent incorrect switching. Compatibility with a wide range of TeSys contactors expands application possibilities and simplifies integration into existing systems. Operational safety is ensured by high insulation resistance values and defined short-time performances. Mounting is simple and requires no special tools, accelerating maintenance and installation.
Color and Appearance
The time block is finished in dark gray, integrating it visually into the TeSys Deca series. The surface is smooth and corresponds to coating class TH according to IEC 60068, ensuring high resistance to environmental influences. The compact design with a width of 44 mm and a height of 48 mm allows dense mounting in enclosures.
Standards and Certifications
LADT46 complies with standards EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No. 60947-5-1, GB/T 14048.5, EN 50012, IEC 60335-1:Clause 30.2, IEC 60335-2-40:Annex JJ, and UL 60335-2-40:Annex JJ. Product certifications include CB, UL, CSA, CCC, and UKCA, confirming international usability and safety. The warranty period is 18 months.
Connections and Terminals
Connections are made via ring terminal lugs with an outer diameter of 8 mm. The terminals are designed for secure and durable connections. The tightening torque is 1.7 Nm, and mounting can be performed using a flat screwdriver (Ø 6 mm), a Phillips screwdriver No. 2, or a positioning screwdriver No. 2. The terminals are not equipped with EverLink technology, as this is specifically intended for TeSys D series power contactors in power ratings from 40 to 65 A and does not apply to auxiliary switch blocks such as LADT46.
Degree of Protection and Environmental Conditions
The degree of protection IP2x according to IEC 60529 protects against finger contact and solid foreign objects larger than 12.5 mm. The operating temperature range is from -40 °C to +70 °C, and the storage temperature range is from -60 °C to +80 °C. The operating altitude is up to 3,000 m above sea level. Environmental conditions are defined as normal, meaning operation occurs under typical industrial conditions without special environmental requirements such as high humidity or aggressive chemicals.