| Complementary |
| Irms rated making capacity | 140 A AC; 250 A DC |
| Permissible short-time rating | 100 A 60 °C 1 s; 120 A 60 °C 500 ms; 140 A 60 °C 100 ms |
| Protection type | GG fuse 10 A |
| Mechanical durability | 5 Mcycles |
| Minimum switching current | 5 mA |
| Minimum switching voltage | 17 V |
| Non-overlap time | 1.5 ms on de-energisation no overlap between NC and NO contact; 1.5 ms on energisation no overlap between NC and NO contact |
| Insulation resistance | > 10 MOhm |
| Connections - terminals | Lugs-ring terminals (external diameter: 8 mm) |
| Tightening torque | 1.7 N.m - with screwdriver flat Ø 6 mm; 1.7 N.m - with screwdriver Philips No 2; 1.7 N.m - with screwdriver pozidriv No 2 |
| Height | 48 mm |
| Width | 44 mm |
| Depth | 61 mm |
| Colour | Dark grey |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Environmental characteristic | Normal environment |
| IP degree of protection | IP2X conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068 |
| Ambient air temperature for storage | -60…80 °C |
| Ambient air temperature for operation | -40…70 °C |
| Operating altitude | 3000 m |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys; TeSys Deca |
| Product name | TeSys Deca |
| Product or component type | Time delay auxiliary contact block |
| Range compatibility | TeSys D CAD; TeSys D LC1D; TeSys F LC1F; TeSys F CR1F; TeSys Deca CAD; TeSys Deca LC1D |
| Device application | Star delta starter |
| Mounting location | Front |
| Pole contact composition | 1 NO + 1 NC |
| Contacts operation | Time delay |
| Timer type | On delay |
| Time delay range | 1...30 s |
| [Ue] rated operational voltage | 690 V AC 25...400 Hz |
| [Ie] rated operational current | 6 A at 120 V AC-15; 1.04 A at 690 V AC-15; 0.55 A at 125 V DC-13; 0.1 A at 600 V DC-13 |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-5-1; 600 V conforming to UL; 600 V conforming to CSA |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) |
| Standards | EN/IEC 60947-5-1; UL 60947-5-1; CSA C22.2 No 60947-5-1; GB/T 14048.5; EN 50012; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ |
| Product certifications | CB; UL; CSA; CCC; UKCA |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.6 cm |
| Package 1 Width | 4.8 cm |
| Package 1 Length | 5.1 cm |
| Package 1 Weight | 88.0 g |
The LADS26 from Schneider Electric is a time-delayed auxiliary switch block from the TeSys Deca series, specifically designed for use in star-delta starter applications. It serves as an add-on module for contactors of the TeSys D and TeSys F families, as well as for the TeSys Deca series, enabling precise control of switching operations through a delayed closing function. The block features a contact configuration of 1 normally open and 1 normally closed contact (1 S + 1 Ö) and is designed for a closing delay in the range of 1 to 30 seconds. This time delay is particularly important to ensure controlled and damage-free motor operation when switching from star to delta configuration.
Applications
The LADS26 is used in industrial installations where time-controlled switching of electrical loads is required, particularly in the control of three-phase motors via star-delta starters. The time delay ensures that the motor is initially started in star mode before switching to delta configuration, thereby limiting inrush currents. This protects the motor and the system from mechanical and electrical stress. Compatibility with various contactor types such as LC1D, LC1F, CR1F, and CAD enables flexible integration into existing systems.
Functions and Features in Detail
The auxiliary switch block is rated for an operating voltage of 690 V AC (25–400 Hz) and supports various operating currents depending on load type, for example, 6 A at 120 V AC-15 or 1.04 A at 690 V AC-15. The rated insulation voltage is 690 V according to IEC 60947-5-1, ensuring safe electrical isolation. The mechanical life expectancy is 5 million switching cycles, indicating high reliability and durability. The contacts are equipped with ring terminal connectors with an outer diameter of 8 mm, to be tightened with a torque of 1.7 Nm, using screwdrivers with flat Ø 6, Phillips No. 2, or position No. 2.
Technology Explained Simply
The closing delay of the LADS26 is achieved through an integrated timing control that maintains a defined delay period of 1 to 30 seconds after the control voltage is applied, before the normally open contact is activated. This enables controlled switching in star-delta control applications. The non-overlap time is 1.5 ms, meaning that the normally open and normally closed contacts are not simultaneously closed during switching, preventing short circuits. The insulation resistance values exceed 10 MΩ, ensuring high electrical safety. The operating temperature range is between -40 °C and +70 °C, allowing use in various industrial environments.
Compatibility and Accessories
The LADS26 is compatible with a wide range of contactor models from the TeSys D and TeSys F series, including LC1D40A6LE7, LC1D096FD, LC1D50A6P7, LC1D386L7, LC1D326FD, LC1D65A6FD, LC1D186B7, LC1D126L7, LC1D096SD, LC1D1506U7, LC1D126G7, LC1D326B7, LC1D256F7, LC1D1156G7, LC1D126F7, LP1D800086SW, LC1D096MD, LC1D126BD, LC1D40A6B7, and LC1D186SD. These contactors cover a power range from 0.06 to 75 kW, enabling broad application in various industrial installations. Mounting is done on the front side of the contactor, ensuring easy integration into existing control systems.
Mounting and Installation
The LADS26 is mounted on the front side of the main contactor and is designed for installation in normal environmental conditions. The protection rating IP2x according to IEC 60529 protects against finger contact and ingress of solid foreign objects, but not against water. The operating altitude is up to 3,000 m above sea level, allowing use in high-altitude industrial facilities. Dimensions are 44 mm (width), 48 mm (height), and 61 mm (depth), making the block compact and space-saving. The color is dark gray, enabling visual integration into standard control systems.
Operational Advantages
The use of the LADS26 provides precise and reliable control of star-delta starter applications. The integrated time delay reduces mechanical and electrical stress during motor start-up, extending the lifespan of the system. The high mechanical life of 5 million switching cycles and the robust construction with ring terminal connectors ensure long-term operation without maintenance. Compatibility with a wide range of contactor models enables flexible and cost-efficient system configuration. Compliance with international standards such as EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No. 60947-5-1, and GB/T 14048.5 ensures safety and reliability of the device in various markets.