| Complementary |
| Irms rated making capacity | 140 A at |
| Permissible short-time rating | 100 A 60 °C 1 s; 120 A 60 °C 500 ms; 140 A 60 °C 100 ms |
| Protection type | GG fuse 10 A |
| Mechanical durability | 5 Mcycles |
| Minimum switching current | 5 mA |
| Minimum switching voltage | 17 V |
| Non-overlap time | 1.5 ms on de-energisation no overlap between NC and NO contact; 1.5 ms on energisation no overlap between NC and NO contact |
| Insulation resistance | > 10 MOhm |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end; Screw clamp terminals 1 cable(s) 1…2.5 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 1…2.5 mm²rigid; Screw clamp terminals 2 cable(s) 1…2.5 mm²rigid; Screw clamp terminals |
| Tightening torque | 1.7 N.m - with screwdriver flat Ø 6 mm; 1.7 N.m - with screwdriver Philips No 2; 1.7 N.m - with screwdriver pozidriv No 2 |
| Height | 48 mm |
| Width | 44 mm |
| Depth | 61 mm |
| Colour | Dark grey |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Environmental characteristic | Normal environment |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068 |
| Ambient air temperature for storage | -60…80 °C |
| Ambient air temperature for operation | -40…70 °C |
| Operating altitude | 3000 m |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys; TeSys Deca |
| Product name | TeSys Deca |
| Product or component type | Time delay auxiliary contact block |
| Range compatibility | TeSys Deca CAD; TeSys Deca LC1D; TeSys F LC1F; TeSys F CR1F |
| Device application | Star delta starter |
| Mounting location | Front |
| Pole contact composition | 1 NO + 1 NC |
| Contacts operation | Time delay |
| Timer type | On delay |
| Time delay range | 1...30 s |
| [Ue] rated operational voltage | 690 V AC 25...400 Hz |
| [Ie] rated operational current | 6 A at 120 V AC-15; 1.04 A at 690 V AC-15; 0.55 A at 125 V DC-13; 0.1 A at 600 V DC-13 |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-5-1; 600 V conforming to UL 60947-5-1; 600 V conforming to CSA C22.2 No 60947-5-1 |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) |
| Standards | EN/IEC 60947-5-1; UL 60947-5-1; CSA C22.2 No 60947-5-1; GB/T 14048.5; EN 50012; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ |
| Product certifications | IECEE CB Scheme; UL; CSA; CCC; EAC; UKCA |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.2 cm |
| Package 1 Width | 6.5 cm |
| Package 1 Length | 4.8 cm |
| Package 1 Weight | 82 g |
| Unit Type of Package 2 | BB1 |
| Number of Units in Package 2 | 10 |
| Package 2 Height | 5.2 cm |
| Package 2 Width | 13 cm |
| Package 2 Length | 24 cm |
| Package 2 Weight | 836 g |
| Unit Type of Package 3 | S03 |
| Number of Units in Package 3 | 140 |
| Package 3 Height | 30 cm |
| Package 3 Width | 30 cm |
| Package 3 Length | 40 cm |
| Package 3 Weight | 12.202 kg |
The
TeSys Deca auxiliary switch block type LAD-S2 from Schneider Electric is a
time-delayed auxiliary switch block with
ansprechverzögerter function, specifically designed for use in
star-delta starter applications. It serves as an
on-delay and enables controlled, time-regulated switching operations to reduce mechanical stress during the motor start-up phase. The delay time can be adjusted within a range of
1 to 30 seconds, making it suitable for applications with variable start-up durations. The block is designed for
front mounting on contactors of the series
TeSys Deca CAD, TeSys Deca LC1D, TeSys F LC1F, and TeSys F CR1F and is secured using a
front-side snap-in mounting method.
Applications primarily include motor control in industrial systems where a gentle start-up phase is required to minimize current surges and mechanical stress. Use in star-delta circuits is typical, as the delay controls the time between switching from star to delta configuration. The
composition of the pole contact consists of
1 normally open (S) and 1 normally closed (Ö), enabling flexible integration into existing control circuits.
Functions and equipment in detail include an
on-delay with a defined time range of 1 to 30 seconds. The contacts are designed to prevent overlap between the normally closed and normally open contacts — the
non-overlapping time is 1.5 ms both during energizing and de-energizing. This ensures a safe and reliable switching sequence. The
screw terminals allow connection of cables with a cross-section of
1 to 2.5 mm², both flexible and rigid, with or without wire end ferrules. The
tightening torque is 1.7 Nm, and mounting can be done using a flat-head screwdriver (Ø 6), a Phillips screwdriver No. 2, or a positioning screwdriver No. 2.
Technology explained simply shows that the block supports an
operating rated voltage of 690 V AC at frequencies from 25 to 400 Hz. The
rated insulation voltage is 690 V according to IEC 60947-5-1, 600 V according to UL 60947-5-1, and CSA C22.2 No. 60947-5-1. The
conventional thermal current in free air is 10 A at 60 °C, describing the thermal load capacity under normal operating conditions. The
mechanical life is 5 million switching cycles, indicating high reliability and longevity. The
minimum switching voltage is 17 V, and the minimum switching current is 5 mA, highlighting the sensitivity of the block at low signal levels.
Compatibility and accessories refer to use with contactors of the series
TeSys Deca CAD, TeSys Deca LC1D, TeSys F LC1F, and TeSys F CR1F. Compatible contactors available in the range include models such as LC1DT80AM7, LC1DT40BL, LC1D18Q7, LC1D32X7, LC1D25SC7, LC1D188P7, LC1D258BD, LC1D95M5, LC1D18U7TQ, LC1D115U7, LC1D95E7, LC1D12D7, LC1D25BNE, LC1D80E5, LC1D40008B7, LC1D32D7, LC1D09V7, LC1D40AFE7, LC1D80BW, LC1DT32B7. These contactors are designed for different power ratings, voltages, and control current types and allow flexible combination with the LAD-S2.
Mounting and installation is performed on the front side of the contactors, with the block secured via a snap mechanism. Dimensions are
44 mm width, 48 mm height, and 61 mm depth. The color is
dark gray, matching the standard design of the TeSys series. The
protection rating IP20 according to IEC 60529 protects against finger contact and solid foreign objects, but not against water or dust. The
operating ambient temperature ranges from -40 to 70 °C, and the storage temperature ranges from -60 to 80 °C. The maximum operating altitude is
3,000 meters above sea level.
Operational advantages include
safe and precise time control for start-up processes,
high mechanical life, and
easy mounting on compatible contactors. The
screw terminals provide a robust and reliable connection, while the
adjustable delay time allows adaptation to specific requirements. The
certifications according to EN/IEC 60947-5-1, UL, CSA, CCC, EAC, and UKCA ensure compliance with international safety and quality standards. The
rated make capacity of 140 A and the
permissible short-time performance (100 A/1 s, 120 A/500 ms, 140 A/100 ms) ensure stability under transient loads. The
insulation resistance exceeding 10 MΩ guarantees high electrical insulation and safety.
The block is designed for
normal ambient conditions and complies with
coating class TH according to IEC 60068. The warranty period is 18 months.