| Complementary |
| Irms rated making capacity | 140 A at |
| Permissible short-time rating | 100 A 60 °C 1 s; 120 A 60 °C 500 ms; 140 A 60 °C 100 ms |
| Protection type | GG fuse 10 A |
| Mechanical durability | 5 Mcycles |
| Minimum switching current | 5 mA |
| Minimum switching voltage | 17 V |
| Non-overlap time | 1.5 ms on de-energisation no overlap between NC and NO contact; 1.5 ms on energisation no overlap between NC and NO contact |
| Insulation resistance | > 10 MOhm |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end; Screw clamp terminals 1 cable(s) 1…2.5 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 1…2.5 mm²rigid; Screw clamp terminals 2 cable(s) 1…2.5 mm²rigid; Screw clamp terminals |
| Tightening torque | 1.7 N.m - with screwdriver flat Ø 6 mm; 1.7 N.m - with screwdriver Philips No 2; 1.7 N.m - with screwdriver pozidriv No 2 |
| Height | 48 mm |
| Width | 44 mm |
| Depth | 61 mm |
| Colour | Dark grey |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Environmental characteristic | Normal environment |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068 |
| Ambient air temperature for storage | -60…80 °C |
| Ambient air temperature for operation | -40…70 °C |
| Operating altitude | 3000 m |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys; TeSys Deca |
| Product name | TeSys Deca |
| Product or component type | Time delay auxiliary contact block |
| Range compatibility | TeSys Deca CAD; TeSys Deca LC1D; TeSys F LC1F; TeSys F CR1F |
| Mounting location | Front |
| Pole contact composition | 1 NO + 1 NC |
| Contacts operation | Time delay |
| Timer type | Off delay |
| Time delay range | 1...30 s |
| [Ue] rated operational voltage | 690 V AC 25...400 Hz |
| [Ie] rated operational current | 6 A at 120 V AC-15; 1.04 A at 690 V AC-15; 0.55 A at 125 V DC-13; 0.1 A at 600 V DC-13 |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-5-1; 600 V conforming to UL 60947-5-1; 600 V conforming to CSA C22.2 No 60947-5-1 |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) |
| Standards | EN/IEC 60947-5-1; UL 60947-5-1; CSA C22.2 No 60947-5-1; GB/T 14048.5; EN 50012; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ |
| Product certifications | IECEE CB Scheme; UL; CSA; CCC; EAC; UKCA |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.200 cm |
| Package 1 Width | 6.500 cm |
| Package 1 Length | 5.000 cm |
| Package 1 Weight | 74.000 g |
| Unit Type of Package 2 | BB1 |
| Number of Units in Package 2 | 10 |
| Package 2 Height | 5.200 cm |
| Package 2 Width | 13.000 cm |
| Package 2 Length | 24.000 cm |
| Package 2 Weight | 756.000 g |
| Unit Type of Package 3 | S03 |
| Number of Units in Package 3 | 140 |
| Package 3 Height | 30.000 cm |
| Package 3 Width | 30.000 cm |
| Package 3 Length | 40.000 cm |
| Package 3 Weight | 11.121 kg |
The LADR2 is a time-delayed auxiliary switch block from the TeSys Deca series by Schneider Electric, specifically designed for integration into contactors of the TeSys Deca CAD, TeSys Deca LC1D, TeSys F LC1F, and TeSys F CR1F series. As a
drop-out delayed time block, it enables controlled delay during switching off, allowing better control and synchronization of switching operations in industrial plants. The function is implemented via an
off-delay type, providing a delay time range of 1 to 30 seconds. This adjustable range is suitable for applications requiring precise timing coordination of switching operations, such as sequential motor starts or avoiding short-term current surges.
Applications include industrial automation, particularly in systems where targeted time delay is required when switching off auxiliary functions. The time block is mounted directly on the
front side of the contactor, enabling compact and quick installation. Mounting is done by snap-on, ensuring a mechanically robust and reliable connection. The
protection rating IP20 according to IEC 60529 protects against finger contact and ingress of solid foreign objects larger than 12.5 mm, but not against water or dust—thus, it is intended for indoor installations under normal environmental conditions.
Functions and equipment in detail include a
pole contact configuration of 1 normally open (S) and 1 normally closed (Oe). The contacts are rated for an operating voltage of 690 V AC, with permissible operating currents varying by voltage: 6 A at 120 V AC-15, 1.04 A at 690 V AC-15, 0.55 A at 125 V DC-13, and 0.1 A at 600 V DC-13. The
conventional thermal current is 10 A at an ambient temperature of 60 °C, defining the thermal load capacity under operating conditions. The
rated insulation voltage is 690 V according to IEC 60947-5-1, 600 V according to UL 60947-5-1, and CSA C22.2 No. 60947-5-1, ensuring electrical insulation for safe operation.
Technology explained simply shows that the time block operates via a mechanical time delay activated during switching off. The delay is achieved through a mechanical timing mechanism that slows the reset of the contacts. The
non-overlapping time is 1.5 ms, regardless of whether the switch is operated control-based or release-based, ensuring that the normally closed and normally open contacts are never active simultaneously. This prevents short circuits and enhances reliability. The
permissible short-time current is 100 A for 1 second, 120 A for 500 ms, and 140 A for 100 ms at 60 °C, defining the mechanical load capacity under sudden current surges. The
rated make capacity is 140 A, indicating the maximum current during switching on. The
mechanical life is 5 million switching cycles, indicating high robustness and longevity.
Compatibility and accessories include use with various contactor models from the TeSys Deca and TeSys F series, such as LC1D80ABBE, LC1D50AU7, LC1D09JD, LC1DT25MD, LC1D258V7, LC1DT32F7, LC1D80AE7, LC1DT80AE7, LC1D098FD, LC1DT40E7, LC1D95MD, LC1D65ABBE, LC1D50AP7, LC1D50AEHE, LC1D40AX7, LC1DT25BD, LC1D65AR7, LC1D09G7, LC1D09SD, and LC1D150FD. These contactors can be combined with the LADR2 to integrate additional time-delay functions for auxiliary contacts.
Connections are made via screw terminals, suitable for cable cross-sections of 1 to 2.5 mm² flexible (with or without cable end) and 1 to 2.5 mm² rigid. The
torque is 1.7 Nm, and mounting can be done with a flat screwdriver (Ø 6), a Phillips screwdriver No. 2, or a positioning screwdriver No. 2.
Mounting and installation is done by simple snap-on to the front side of the contactor, requiring no additional tools or mounting aids. Dimensions are 48 mm height, 44 mm width, and 61 mm depth, allowing integration into standardized control panels. The
color is dark gray, contributing to visual harmony in industrial control systems. The
ambient temperature during operation ranges from -40 °C to +70 °C, and during storage from -60 °C to +80 °C. The maximum
operating altitude is 3,000 m above sea level, enabling use in high-altitude industrial facilities. The
insulation resistance is greater than 10 MΩ, ensuring high electrical insulation. The
coating corresponds to category TH according to IEC 60068, indicating resistance to environmental influences such as humidity and temperature fluctuations.
Operational advantages include high reliability, a long life of 5 million switching cycles, and easy mounting. The 1 to 30-second time delay enables precise control of switching operations, enhancing operational safety in industrial plants. Certifications according to EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No. 60947-5-1, GB/T 14048.5, EN 50012, IEC 60335-1:Clause 30.2, IEC 60335-2-40:Annex JJ, UL 60335-2-40:Annex JJ, as well as product certifications IECEE CB-Scheme, UL, CSA, CCC, EAC, and UKCA, guarantee compliance with international standards. Compliance with RoHS and REACH (Green Premium) ensures environmental compatibility of the product. The
minimum switching voltage is 17 V, and the
minimum switching current is 5 mA, defining the sensitivity of the switch to weak signals. The
protection rating GG fuse 10 A protects the time block against overloads and short circuits.
The LADR2 is thus a reliable, standard-compliant auxiliary switch block for industrial applications, used in control systems of the TeSys Deca and TeSys F series due to its easy mounting, long life, and precise time-delay functions. Technical specifications and norm compliance ensure safe and reliable operation under industrial conditions.