| Complementary |
| Irms rated making capacity | 140 A AC; 250 A DC |
| Permissible short-time rating | 100 A 60 °C 1 s; 120 A 60 °C 500 ms; 140 A 60 °C 100 ms |
| Protection type | GG fuse 10 A |
| Mechanical durability | 5 Mcycles |
| Minimum switching current | 5 mA |
| Minimum switching voltage | 17 V |
| Non-overlap time | 1.5 ms on de-energisation no overlap between NC and NO contact; 1.5 ms on energisation no overlap between NC and NO contact |
| Insulation resistance | > 10 MOhm |
| Connections - terminals | Lugs-ring terminals (external diameter: 8 mm) |
| Tightening torque | 1.7 N.m - with screwdriver flat Ø 6 mm; 1.7 N.m - with screwdriver Philips No 2; 1.7 N.m - with screwdriver pozidriv No 2 |
| Height | 48 mm |
| Width | 44 mm |
| Depth | 61 mm |
| Colour | Dark grey |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Environmental characteristic | Normal environment |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068 |
| Ambient air temperature for storage | -60…80 °C |
| Ambient air temperature for operation | -40…70 °C |
| Operating altitude | 3000 m |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys; TeSys Deca |
| Product name | TeSys Deca |
| Product or component type | Time delay auxiliary contact block |
| Range compatibility | TeSys D CAD; TeSys D LC1D; TeSys F LC1F; TeSys F CR1F; TeSys Deca CAD; TeSys Deca LC1D |
| Mounting location | Front |
| Pole contact composition | 1 NO + 1 NC |
| Contacts operation | Time delay |
| Timer type | Off delay |
| Time delay range | 0.3...3 s |
| [Ue] rated operational voltage | 690 V AC 25...400 Hz |
| [Ie] rated operational current | 6 A at 120 V AC-15; 1.04 A at 690 V AC-15; 0.55 A at 125 V DC-13; 0.1 A at 600 V DC-13 |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-5-1; 600 V conforming to UL 60947-5-1; 600 V conforming to CSA C22.2 No 60947-5-1 |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) |
| Standards | EN/IEC 60947-5-1; UL 60947-5-1; CSA C22.2 No 60947-5-1; GB/T 14048.5; EN 50012; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ |
| Product certifications | IECEE CB Scheme; UL; CSA; CCC; EAC; UKCA |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.1 cm |
| Package 1 Width | 5.2 cm |
| Package 1 Length | 6.6 cm |
| Package 1 Weight | 75 g |
| Unit Type of Package 2 | BB1 |
| Number of Units in Package 2 | 10 |
| Package 2 Height | 5.2 cm |
| Package 2 Width | 14 cm |
| Package 2 Length | 24 cm |
| Package 2 Weight | 757 g |
| Unit Type of Package 3 | S03 |
| Number of Units in Package 3 | 140 |
| Package 3 Height | 30 cm |
| Package 3 Width | 30 cm |
| Package 3 Length | 40 cm |
| Package 3 Weight | 10.828 kg |
The LADR06 from Schneider Electric is a time-delayed auxiliary switch block from the TeSys Deca series, specifically designed for mounting on the front side of contactors from the TeSys D and TeSys F series. It serves as an auxiliary contact module with an off-delay function, enabling time-controlled switching operations in industrial control systems. The device features one normally closed contact and one normally open contact (1 S + 1 Ö) and allows for a delay time of 0.3 to 3 seconds, making it suitable for applications requiring delayed de-energization of auxiliary circuits, for example, to avoid inrush currents or to synchronize machine components.
Applications
The auxiliary switch block is used in industrial control systems where time-controlled switching operations are required. It is compatible with various contactor models from the TeSys D and TeSys F families, including LC1D, LC1F, CR1F, CAD, and LC1D models from the TeSys Deca series. Typical use cases include installations requiring precise timing of switching operations, such as conveyor systems, packaging machines, or systems with sequential operating procedures.
Functions and Features in Detail
The LADR06 provides an off-delay time ranging from 0.3 to 3 seconds, achieved through a mechanical timing mechanism. The contacts are designed to prevent overlap between the normally open and normally closed contacts — during de-energization and actuation, the non-overlapping time is 1.5 ms. This ensures a safe and precise switching sequence. The contacts are rated for an operating voltage of 690 V AC (25–400 Hz), with operating current ratings varying by voltage: 6 A at 120 V AC-15, 1.04 A at 690 V AC-15, 0.55 A at 125 V DC-13, and 0.1 A at 600 V DC-13. Minimum switching voltage and current values are 17 V and 5 mA, enabling reliable operation even under low-load conditions.
Technical Explanation
The time delay is achieved via a mechanical reset mechanism that maintains a defined delay period after the switch is de-energized before the contact closes or opens. The rated insulation voltage is 690 V (corresponding to IEC 60947-5-1) and 600 V (corresponding to UL 60947-5-1 and CSA C22.2 No. 60947-5-1), ensuring safe insulation even at high voltages. The conventional thermal current is 10 A at 60 °C in free air, indicating the device’s thermal load capacity. The permissible short-time performance is 100 A for 1 second, 120 A for 500 ms, and 140 A for 100 ms at 60 °C, defining its short-term overload capability.
Compatibility and Accessories
The LADR06 is intended for mounting on contactors from the TeSys D and TeSys F series, particularly models such as LC1D1156N7, LC1D386MD, LC1D126B7, LC1D1156F7, LC1D096R7, LC1D1506G7, LC1D096CD, LC1D40A6U7, LC1DT206BD, LC1D186G7, LC1DT256P7, LC1D1506BD, LC1D806BD, LC1D186ND, LC1D096B7, LC1D65A6G7, LC1D1156U7, LC1D50A6P7, LC1D1156M5, and LC1D126FD. Connections are made via ring terminal lugs with an outer diameter of 8 mm, to be tightened with a torque of 1.7 Nm (using a flat screwdriver Ø 6, Phillips No. 2, or position No. 2). The protection rating IP20 corresponds to IEC 60529 and protects against finger contact, but not against dust or water.
Mounting and Installation
The auxiliary switch block is mounted on the front side of the contactor and is designed for normal ambient conditions. The operating temperature range is from -40 °C to 70 °C, and the storage temperature range is from -60 °C to 80 °C. The maximum operating altitude is 3,000 m above sea level. Dimensions are 44 mm (width), 48 mm (height), and 61 mm (depth), allowing integration into standardized control panels. The color is dark gray, providing good visibility in control installations.
Operational Advantages
The LADR06 offers reliable and precise time delay, essential for controlling complex industrial processes. The mechanical life is 5 million switching cycles, ensuring high operational safety and long service life. Insulation resistances exceed 10 MΩ, ensuring high electrical insulation. Compliance with international standards such as EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No. 60947-5-1, GB/T 14048.5, EN 50012, IEC 60335-1:Clause 30.2, IEC 60335-2-40:Annex JJ, and UL 60335-2-40:Annex JJ guarantees conformity with global safety and quality standards. Certifications include IECEE CB Scheme, UL, CSA, CCC, EAC, and UKCA, highlighting the device’s worldwide applicability.