| Additional features |
| [Irms] Rated making capacity | 140 A AC conforming to IEC 60947-5-1; 250 A DC conforming to IEC 60947-5-1 |
| Permissible short-time power | 100 A 60 °C 1 s; 120 A 60 °C 500 ms; 140 A 60 °C 100 ms |
| Degree of protection | GG fuse 10 A |
| Mechanical life | 30 Mcycles |
| Electrical reliability | 0.00000001 at 17 V and 1 mA |
| Min. switching current | 1 mA |
| Min. switching voltage | 17 V |
| Non-overlapping time | 1.5 ms with misoperation between normally closed contacts and normally open contacts; 1.5 ms with actuation between normally closed contacts and normally open contacts |
| Insulation resistance | > 10 MΩ |
| Connections - terminals | Screw terminals 1 cable(s) 1…4 mm² flexible with cable end; screw terminals 1 cable(s) 1…4 mm² flexible without cable end; screw terminals 2 cable(s) 1…2.5 mm² flexible with cable end; screw terminals 2 cable(s) 1…4 mm² flexible without cable end; screw terminals 1 cable(s) 1…4 mm² solid without cable end; screw terminals 2 cable(s) 1…4 mm² solid without cable end |
| Tightening moment | 1.7 Nm - with flat screwdriver Ø 6; 1.7 Nm - with Phillips screwdriver No. 2; 1.7 Nm - with screwdriver position No. 2 |
| Height | 48 mm |
| Width | 44 mm |
| Depth | 42 mm |
| Product weight | 0,06 kg |
| Colour | Dark grey |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | TeSys; TeSys Deca |
| Product name | TeSys Deca |
| Product or component type | Auxiliary switch block |
| Device short name | LADN_R |
| Compatible product family | TeSys D CAD; TeSys D LC1D; TeSys Deca CAD; TeSys Deca LC1D; TeSys F LC1F; TeSys F CR1F |
| Mounting location | front side |
| Composition of pole contact | 4 S |
| [Ue] Operational rated voltage | 690 V AC 25 - 400 Hz |
| [Ui] Rated insulation voltage | 690 V conforms to IEC 60947-5-1; 600 V conforms to UL; 600 V conforms to CSA |
| [Ith] conventional thermal current in free air | 10 A (at 60 °C) |
| Standards | EN/IEC 60947-5-1; GB/T 14048.5; EN 50012; UL 60947-5-1; CSA C22.2 No. 60947-5-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ |
| Product certifications | CB; UL; CSA; CCC; UKCA |
| Mounting |
| Environmental properties | Normal environmental conditions; harsh environmental conditions; 3S4 |
| Degree of protection (IP) | IP2x complies with IEC 60529 |
| Coating | TH corresponds to IEC 60068 |
| Ambient temperature during storage | -60…80 °C |
| Operating ambient temperature | -25…60 °C; -40…-25 °C with power reduction; 60…70 °C with power reduction |
| Operating altitude | 3.000 m |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 5,200 cm |
| VPE 1 width | 4,300 cm |
| VPE 1 length | 5,400 cm |
| Packaging weight (Lbs) | 64,000 g |
| VPE 2 type | S02 |
| VPE 2 quantity | 105 |
| VPE 2 height | 15,000 cm |
| VPE 2 width | 30,000 cm |
| VPE 2 length | 40,000 cm |
| VPE 2 weight | 7,097 kg |