| Complementary |
| Irms rated making capacity | 140 A AC conforming to IEC 60947-5-1; 250 A DC conforming to IEC 60947-5-1 |
| Permissible short-time rating | 100 A 60 °C 1 s; 120 A 60 °C 500 ms; 140 A 60 °C 100 ms |
| Protection type | GG fuse 10 A |
| Mechanical durability | 30 Mcycles |
| Minimum switching current | 5 mA |
| Minimum switching voltage | 17 V |
| Non-overlap time | 1.5 ms on de-energisation no overlap between NC and NO contact; 1.5 ms on energisation no overlap between NC and NO contact |
| Insulation resistance | > 10 MOhm |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end; Screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 1…4 mm²rigid without cable end; Screw clamp terminals 2 cable(s) 1…4 mm²rigid without cable end |
| Tightening torque | 1.7 N.m - with screwdriver flat Ø 6 mm; 1.7 N.m - with screwdriver Philips No 2; 1.7 N.m - with screwdriver pozidriv No 2 |
| Height | 48 mm |
| Width | 44 mm |
| Depth | 42 mm |
| Net weight | 0.05 kg |
| Colour | Dark grey |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Environmental characteristic | Normal environment |
| IP degree of protection | IP2X conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068 |
| Ambient air temperature for storage | -60…80 °C |
| Ambient air temperature for operation | -5…60 °C |
| Operating altitude | 3000 m |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys; TeSys Deca |
| Product name | TeSys Deca |
| Product or component type | Auxiliary contact block |
| Device short name | LADN |
| Range compatibility | TeSys D CAD; TeSys D LC1D; TeSys F LC1F; TeSys F CR1F; TeSys Deca CAD; TeSys Deca LC1D |
| Mounting location | Front |
| Pole contact composition | 4 NO |
| Contacts operation | Instantaneous |
| [Ue] rated operational voltage | 690 V AC 25...400 Hz |
| [Ie] rated operational current | 6 A at 120 V AC-15; 1.04 A at 690 V AC-15; 0.55 A at 125 V DC-13; 0.1 A at 600 V DC-13 |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-5-1; 600 V conforming to UL; 600 V conforming to CSA |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) |
| Standards | EN/IEC 60947-5-1; GB/T 14048.5; EN 50012; UL 60947-5-1; CSA C22.2 No 60947-5-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; UL; CSA; CCC; EAC; UKCA |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5 cm |
| Package 1 Width | 4.1 cm |
| Package 1 Length | 4.8 cm |
| Package 1 Weight | 62 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 160 |
| Package 2 Height | 30 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 10.37 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 1280 |
| Package 3 Height | 75 cm |
| Package 3 Width | 60 cm |
| Package 3 Length | 80 cm |
| Package 3 Weight | 89 kg |
The auxiliary switch block LADN40 from Schneider Electric belongs to the TeSys Deca series and serves as an additional component for power contactors of the series TeSys D CAD, TeSys D LC1D, TeSys F LC1F, TeSys F CR1F, TeSys Deca CAD and TeSys Deca LC1D. It is designed as an
auxiliary switch block and features
4 S (4 normally open contacts), which switch without delay, i.e. immediately. Mounting is done
front-side on the contactor, with the block being snap-fitted to ensure secure fastening. Connections are made via
screw terminals, designed for flexible and rigid cables with cross-sections from 1 to 4 mm², with a maximum cross-section of 2.5 mm² for flexible cables when two cables are connected. The tightening torque is 1.7 Nm, and mounting can be performed using a flat-head screwdriver Ø 6, a Phillips screwdriver No. 2, or a positioning screwdriver No. 2.
Applications include use in industrial control systems, where additional switching functions are required for signals, feedback, or controlling other components. The auxiliary switch block is designed for operating voltages up to 690 V AC (25–400 Hz) and can handle loads up to 6 A (at 120 V AC-15) or 1.04 A (at 690 V AC-15). For direct current, the rated operating current is 0.55 A at 125 V DC-13 and 0.1 A at 600 V DC-13. The rated insulation voltage is 690 V according to IEC 60947-5-1, and 600 V according to UL and CSA. The
rated switching capacity is 140 A for alternating current and 250 A for direct current, enabling use in systems with high inrush currents. The permissible short-time current is 100 A at 60 °C for 1 second, 120 A for 500 ms, and 140 A for 100 ms.
Technology explained simply indicates that the auxiliary switch block is designed for normal ambient conditions. The operating temperature ranges from -5 °C to 60 °C, and the storage temperature ranges from -60 °C to 80 °C. The operating altitude is up to 3,000 m above sea level. The protection class IP2x according to IEC 60529 protects against finger contact and ingress of solid foreign objects larger than 12.5 mm, but not against water. The coating corresponds to category TH according to IEC 60068, indicating high thermal resistance. The conventional thermal current is 10 A at 60 °C in free air, describing the thermal load capacity of the device. The mechanical life is 30 million switching cycles, ensuring high reliability in continuously operated systems. The insulation resistance is greater than 10 MΩ, ensuring high electrical insulation. The minimum switching voltage is 17 V, and the minimum switching current is 5 mA, enabling use even with weak signals. The non-overlapping time is 1.5 ms, regardless of whether the contact is actuated by control or release, ensuring precise switching sequences.
Compatibility and accessories include use with various power contactors from the TeSys family, such as LC1D, LC1F, CAD, and CR1F. Compatible power contactors available in the range include, for example, LC1DT80AFD, LC1D50AU7, LC1D65AV7, LC1D128P7, LC1DT40MD, LC1DT32F7, CAD32E7, LC1D65008E7, LC1D32E7, LC1DT40E7, CAD50FE7, LC1DT25BD, LC1D40AFE7, LP1D40008MD, LC1D32KUE, LC1D09U7TQ, LC1D80AE7, LC1D40AP7, and LC1D65ABBE. These can be combined with the auxiliary switch block LADN40 to integrate additional switching functions. Use is exclusively in conjunction with the specified contactor types, with front-side mounting.
Mounting and installation involve snap-fitting the auxiliary switch block to the front of the power contactor. The screw terminals enable a secure and reliable connection with control wiring. The terminal connections are designed for various cable types and cross-sections, with maximum cross-sections varying depending on the number of connected cables. Mounting must comply with the specified tightening torque of 1.7 Nm to ensure a secure connection. The device color is dark grey, and the dimensions are 44 mm (width), 48 mm (height), and 42 mm (depth). The product weight is 0.05 kg.
Operational advantages include the high mechanical life of 30 million switching cycles, secure and stable switching via screw terminals, and compact design enabling easy mounting and integration into existing control systems. The immediate switching of the 4 normally open contacts ensures precise and reliable signals in control systems. The high insulation strength and compliance with international standards such as EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No. 60947-5-1, as well as certifications like CB, UL, CSA, CCC, EAC, and UKCA, ensure usability in various markets and applications. The operating temperature range and operating altitude up to 3,000 m make the auxiliary switch block suitable for demanding industrial environments. The warranty period is 18 months.
The auxiliary switch block LADN40 is thus a reliable and powerful addition for industrial contactors, used in control and automation systems to implement additional switching functions safely and precisely.