| Complementary |
| Irms rated making capacity | 140 A AC conforming to IEC 60947-5-1; 250 A DC conforming to IEC 60947-5-1 |
| Permissible short-time rating | 100 A 60 °C 1 s; 120 A 60 °C 500 ms; 140 A 60 °C 100 ms |
| Protection type | GG fuse 10 A |
| Mechanical durability | 30 Mcycles |
| Minimum switching current | 5 mA |
| Minimum switching voltage | 17 V |
| Non-overlap time | 1.5 ms on de-energisation no overlap between NC and NO contact; 1.5 ms on energisation no overlap between NC and NO contact |
| Insulation resistance | > 10 MOhm |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end; Screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 1…4 mm²rigid without cable end; Screw clamp terminals 2 cable(s) 1…4 mm²rigid without cable end |
| Tightening torque | 1.7 N.m - with screwdriver flat Ø 6 mm; 1.7 N.m - with screwdriver Philips No 2; 1.7 N.m - with screwdriver pozidriv No 2 |
| Height | 48 mm |
| Width | 44 mm |
| Depth | 42 mm |
| Net weight | 0.05 kg |
| Colour | Red (RAL 3000) |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Environmental characteristic | Normal environment |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068 |
| Ambient air temperature for storage | -60…80 °C |
| Ambient air temperature for operation | -5…60 °C |
| Operating altitude | 3000 m |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys; TeSys Deca |
| Product name | TeSys Deca |
| Product or component type | Auxiliary contact block |
| Device short name | LADN |
| Range compatibility | TeSys D CAD; TeSys D LC1D; TeSys F LC1F; TeSys F CR1F; TeSys Deca CAD; TeSys Deca LC1D |
| Mounting location | Front |
| Pole contact composition | 2 NO + 2 NC |
| Contacts operation | Instantaneous |
| [Ue] rated operational voltage | 690 V AC 25...400 Hz |
| [Ie] rated operational current | 6 A at 120 V AC-15; 1.04 A at 690 V AC-15; 0.55 A at 125 V DC-13; 0.1 A at 600 V DC-13 |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-5-1; 600 V conforming to UL; 600 V conforming to CSA |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) |
| Standards | EN/IEC 60947-5-1; GB/T 14048.5; EN 50012; UL 60947-5-1; CSA C22.2 No 60947-5-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; UL; CSA; CCC; EAC; UKCA |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 4.800 cm |
| Package 1 Width | 4.800 cm |
| Package 1 Length | 5.200 cm |
| Package 1 Weight | 70.000 g |
| Unit Type of Package 2 | S01 |
| Number of Units in Package 2 | 32 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 15.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 2.240 kg |
The auxiliary switch block LADN22S from Schneider Electric belongs to the TeSys Deca series and serves as an additional component for contactors of the TeSys D and TeSys U series. It is specifically designed for mounting on the front side of contactors and enables the expansion of control and signaling functions in industrial installations. The block features a red cover, which serves for visual identification of safety circuits and thus facilitates maintenance and servicing. It is equipped with screw terminals that allow a secure and reliable connection to cables with a cross-section of 1 to 4 mm², either flexible or rigid. The terminals are designed for connecting one or two cables, with tightening torques specified at 1.7 Nm for screwdrivers with flat Ø 6, Phillips No. 2, or position No. 2.
Applications
The auxiliary switch block LADN22S is used in industrial control systems where additional auxiliary contacts are required for signal transmission, feedback of switching states, or interconnection of control circuits. It is compatible with contactors of types LC1 D09 to D65A, DT20 to DT80A, LC1 D80 and D150, as well as with the TeSys D, TeSys U series, and auxiliary contact blocks. Use is intended in installations operated under normal ambient conditions, with an operating temperature range of -5 to 60 °C and a maximum operating altitude of 3,000 m above sea level. Storage is permitted at temperatures from -60 to 80 °C.
Functions and Equipment in Detail
The block features a contact configuration of 2 normally closed contacts (S) and 2 normally open contacts (Ö), which switch without delay. The contacts are rated for an operating voltage of 690 V AC in the frequency range of 25 to 400 Hz. The rated voltage for direct current is 600 V DC. The operating rated currents are 6 A at 120 V AC-15, 1.04 A at 690 V AC-15, 0.55 A at 125 V DC-13, and 0.1 A at 600 V DC-13. The conventional thermal current is 10 A at an ambient temperature of 60 °C. The mechanical life of the block is 30 million switching cycles, ensuring high reliability in continuously operated installations. The minimum values for switching current and switching voltage are 5 mA and 17 V, enabling functionality even with weak signals.
Technology Explained Simply
The screw terminals of the auxiliary switch block are designed for a secure and durable connection. The insulation resistance is greater than 10 MΩ, ensuring high electrical insulation and thus safe operation. The permissible short-time current is 100 A at 60 °C for 1 second, 120 A for 500 ms, and 140 A for 100 ms, demonstrating the load capacity under transient current peaks. The rated switching capacity is 140 A AC and 250 A DC, according to IEC 60947-5-1. The non-overlap time is 1.5 ms, regardless of whether the contact is actuated by de-energizing or energizing, ensuring precise and reliable switching sequences. The protection rating IP20 according to IEC 60529 protects against finger contact and against entry of solid foreign objects larger than 12.5 mm, but not against water or dust.
Compatibility and Accessories
The auxiliary switch block LADN22S is designed for use with contactors from the TeSys D and TeSys U series, as well as with auxiliary contact blocks. It is specifically intended for models LC1 D09 to D65A, DT20 to DT80A, LC1 D80 and D150. As accessories, additional auxiliary contactors from the CAD series are available, for example the CAD32P7 with 3S+2Ö for 230 V AC or the CAD50B7 with 5S for 24 V 50/60 Hz. These can be used in control circuits according to requirements to realize additional functions such as feedback, interlock logic, or signaling.
Mounting and Installation
Mounting is done on the front side of the contactor, with the block dimensions being 44 mm (width), 48 mm (height), and 42 mm (depth). Installation does not require special tools, but adherence to the specified tightening torque of 1.7 Nm for the screw terminals is important to ensure a reliable electrical connection. The coating corresponds to category TH according to IEC 60068, ensuring high resistance to environmental conditions such as humidity and temperature fluctuations.
Operational Advantages
The auxiliary switch block LADN22S offers a compact and robust solution for expanding control functions in industrial installations. The red cover supports visual identification of safety circuits, making maintenance and servicing safer and more efficient. The high mechanical life and reliability of the contacts ensure long-term operation without maintenance. Compatibility with a wide range of contactor models from the TeSys family facilitates integration into existing systems. Compliance with international standards such as EN/IEC 60947-5-1, UL 60947-5-1, and CSA C22.2 No. 60947-5-1 ensures the safety and reliability of the product in various markets. Certifications CB, UL, CSA, CCC, and EAC confirm compliance with applicable safety and quality requirements.