| Complementary |
| Irms rated making capacity | 140 A AC conforming to IEC 60947-5-1; 250 A DC conforming to IEC 60947-5-1 |
| Permissible short-time rating | 100 A 60 °C 1 s; 120 A 60 °C 500 ms; 140 A 60 °C 100 ms |
| Protection type | GG fuse 10 A |
| Mechanical durability | 30 Mcycles |
| Minimum switching current | 5 mA |
| Minimum switching voltage | 17 V |
| Non-overlap time | 1.5 ms on de-energisation no overlap between NC and NO contact; 1.5 ms on energisation no overlap between NC and NO contact |
| Insulation resistance | > 10 MOhm |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end; Screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 1…4 mm²rigid without cable end; Screw clamp terminals 2 cable(s) 1…4 mm²rigid without cable end |
| Tightening torque | 1.7 N.m - with screwdriver flat Ø 6 mm; 1.7 N.m - with screwdriver Philips No 2; 1.7 N.m - with screwdriver pozidriv No 2 |
| Height | 48 mm |
| Width | 26 mm |
| Depth | 42 mm |
| Colour | Dark grey |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Environmental characteristic | Normal environment |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068 |
| Ambient air temperature for storage | -60…80 °C |
| Ambient air temperature for operation | -5…60 °C |
| Operating altitude | 3000 m |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys; TeSys Deca |
| Product name | TeSys Deca |
| Product or component type | Auxiliary contact block |
| Device short name | LADN |
| Range compatibility | TeSys D CAD; TeSys D LC1D; TeSys F LC1F; TeSys F CR1F; TeSys Deca CAD; TeSys Deca LC1D |
| Mounting location | Front |
| Pole contact composition | 2 NO |
| Contacts operation | Instantaneous |
| [Ue] rated operational voltage | 690 V AC 25...400 Hz |
| [Ie] rated operational current | 6 A at 120 V AC-15; 1.04 A at 690 V AC-15; 0.55 A at 125 V DC-13; 0.1 A at 600 V DC-13 |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-5-1; 600 V conforming to UL; 600 V conforming to CSA |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) |
| Standards | EN/IEC 60947-5-1; GB/T 14048.5; EN 50012; UL 60947-5-1; CSA C22.2 No 60947-5-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; UL; CSA; CCC; EAC; UKCA |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5 cm |
| Package 1 Width | 2.8 cm |
| Package 1 Length | 4.3 cm |
| Package 1 Weight | 34 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 320 |
| Package 2 Height | 30 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 11.413 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 2560 |
| Package 3 Height | 75 cm |
| Package 3 Width | 60 cm |
| Package 3 Length | 80 cm |
| Package 3 Weight | 98.5 kg |
The auxiliary switch block LADN20 from Schneider Electric belongs to the TeSys Deca product range and serves as an additional component for power contactors of the series TeSys D CAD, TeSys D LC1D, TeSys F LC1F, TeSys F CR1F, as well as TeSys Deca CAD and TeSys Deca LC1D. It is designed as an
auxiliary switch block and features two
closing contacts (2S) that switch without delay. Mounting is done
front-side on the contactor, with the block securely fixed by a snap-in construction. Connections are made via
screw terminals, designed for flexible and rigid conductors with a cross-section of 1 to 4 mm², where wire ends may optionally be present. Fastening requires a tightening torque of 1.7 Nm, using screwdrivers with flat Ø 6, Phillips No. 2, or Position No. 2.
Applications
LADN20 is used in industrial plants where additional switching functions are required for control and monitoring tasks. The immediate switching of contacts makes it suitable for applications requiring exact synchronization of switching operations, for example in conjunction with starter controls, safety circuits, or signal transmission. Compatibility with various contactor types from the TeSys family enables flexible integration into existing systems.
Functions and Equipment in Detail
The auxiliary switch block features two
closing contacts (2S) that close immediately upon actuation of the main contact. The contacts are rated for an
operating voltage of 690 V AC at frequencies from 25 to 400 Hz. Permissible operating currents vary depending on voltage and switching type: 6 A at 120 V AC-15, 1.04 A at 690 V AC-15, 0.55 A at 125 V DC-13, and 0.1 A at 600 V DC-13. The
rated insulation voltage is 690 V according to IEC 60947-5-1, 600 V according to UL and CSA. The
mechanical life is 30 million switching cycles, ensuring high reliability under industrial operating conditions. The
minimum switching voltage is 17 V, and the
minimum switching current is 5 mA, enabling use even with low loads.
Technology Explained Simply
The LADN20 is an
instantaneous auxiliary switch block that reacts immediately upon actuation of the main contact. Contacts switch without delay, ensuring precise signal transmission. The
protection rating IP20 according to IEC 60529 protects against contact with fingers and larger objects, but is not suitable for use in damp or dusty environments. The
insulation class meets the requirements of standards IEC 60947-5-1, UL 60947-5-1, and CSA C22.2 No. 60947-5-1. The
permissible short-time current is 100 A at 60 °C for 1 second, 120 A for 500 ms, and 140 A for 100 ms, demonstrating load capacity during short-term current surges. The
conventional thermal current (Ith) is 10 A at an ambient temperature of 60 °C, describing the thermal load capacity during operation.
Compatibility and Accessories
The LADN20 is specifically designed for use with power contactors from the TeSys family, particularly models such as LC1D, LC1F, CAD, and CR1F. It can be combined with various contactor types, including LC1D80008P7, LC1D12CD, LC1D188F7, LC1D32FD, LC1D12C7, LC1DT40BD, LC1D115MD, CAD50R7, CAD50P7, CAD50ED, LC1D115FD, LC1D40008E7, LC1D40008P7, LC1D32MD, LC1D12FD, LC1D09P7TQ, LC1D25C7, CAD32U7, and LC1D18GD. Combining with these contactors enables expansion of control functions, for example by adding signal transmission or feedback of switching status.
Mounting and Installation
Mounting is done
front-side on the contactor, with the auxiliary switch block securely fastened by a snap-in construction. Screw terminals allow for easy and secure connection with cables having a cross-section of 1 to 4 mm², supporting both flexible and rigid conductors. Dimensions are 48 mm height, 26 mm width, and 42 mm depth. Operating temperature ranges from -5 °C to 60 °C, and storage temperature ranges from -60 °C to 80 °C. Maximum operating altitude is 3,000 m above sea level.
Operational Advantages
The LADN20 offers a high mechanical life of 30 million switching cycles, enabling long service life and low maintenance frequency. The instantaneous switching of contacts ensures precise signal transmission. Screw terminals allow flexible and secure connections with various cable types. Compatibility with a wide range of TeSys contactors simplifies integration into existing installations. Compliance with international standards such as EN/IEC 60947-5-1, UL, and CSA ensures reliability and safety in industrial applications. The
certifications include CB Scheme, UL, CSA, CCC, and EAC, supporting worldwide usability.