Schneider Electric LADN116, EAN: 3389110820799

Schneider Electric LADN116 auxiliary switch block 1S1Ö unzinc-plated

Industrial Material > Control devices / Pilot devices > Motor protection switch

Schneider Electric LADN116 auxiliary switch block 1S1Ö unzinc-plated

Lieske Part No. 583420
Mfg Part No LADN116
EAN-Code 3389110820799
Manufacturer Schneider Electric
Here only 14,96 EUR
17,80 EUR incl. VAT

Further information for Schneider Electric LADN116 auxiliary switch block 1S1Ö unzinc-plated

Complementary
Irms rated making capacity140 A AC conforming to IEC 60947-5-1; 250 A DC conforming to IEC 60947-5-1
Permissible short-time rating100 A 60 °C 1 s; 120 A 60 °C 500 ms; 140 A 60 °C 100 ms
Protection typeGG fuse 10 A
Mechanical durability30 Mcycles
Minimum switching current5 mA
Minimum switching voltage17 V
Non-overlap time1.5 ms on de-energisation no overlap between NC and NO contact; 1.5 ms on energisation no overlap between NC and NO contact
Insulation resistance> 10 MOhm
Connections - terminalsLugs-ring terminals (external diameter: 8 mm)
Tightening torque1.7 N.m - with screwdriver flat Ø 6 mm M3.5; 1.7 N.m - with screwdriver Philips No 2 M3.5; 1.7 N.m - with screwdriver pozidriv No 2 M3.5
Height48 mm
Width26 mm
Depth42 mm
ColourDark grey
Contractual warranty
Warranty (in months)18
Environment
Environmental characteristicNormal environment
IP degree of protectionIP20 conforming to IEC 60529
Protective treatmentTH conforming to IEC 60068
Ambient air temperature for storage-60…80 °C
Ambient air temperature for operation-5…60 °C
Operating altitude3000 m
Logistical informations
Country of originFR
Main
RangeTeSys; TeSys Deca
Product nameTeSys Deca
Product or component typeAuxiliary contact block
Device short nameLADN
Range compatibilityTeSys D CAD; TeSys D LC1D; TeSys F LC1F; TeSys F CR1F; TeSys Deca CAD; TeSys Deca LC1D
Mounting locationFront
Pole contact composition1 NO + 1 NC
Contacts operationInstantaneous
[Ue] rated operational voltage690 V AC 25...400 Hz
[Ie] rated operational current6 A at 120 V AC-15; 1.04 A at 690 V AC-15; 0.55 A at 125 V DC-13; 0.1 A at 600 V DC-13
[Ui] rated insulation voltage690 V conforming to IEC 60947-5-1; 600 V conforming to UL; 600 V conforming to CSA
[Ith] conventional free air thermal current10 A (at 60 °C)
StandardsEN/IEC 60947-5-1; GB/T 14048.5; EN 50012; UL 60947-5-1; CSA C22.2 No 60947-5-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ
Product certificationsCB Scheme; UL; CSA; CCC; EAC; UKCA
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height3.000 cm
Package 1 Width4.000 cm
Package 1 Length5.000 cm
Package 1 Weight33.000 g
Unit Type of Package 2S03
Number of Units in Package 2320
Package 2 Height30.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight11.016 kg
The auxiliary switch block LADN116 from Schneider Electric belongs to the TeSys Deca series and serves as an additional component for contactors. It is designed as an auxiliary switch block and features a contact configuration of 1 normally open (S) and 1 normally closed (Ö). The contacts operate instantaneously, meaning they switch directly upon actuation of the main contact, without any time delay. The switch block is mounted on the front side of the contactor and is intended for use in industrial control systems and switchgear.

Applications include signal transmission in control circuits, for example, to indicate the switching state of a contactor, to provide feedback to a control system, or to interlock switching operations. It is compatible with various product families, including TeSys D CAD, TeSys D LC1D, TeSys F LC1F, TeSys F CR1F, TeSys Deca CAD, and TeSys Deca LC1D. This compatibility enables flexible integration into existing installations with different contactor types.

Functions and specifications in detail include an operating voltage rating of up to 690 V AC in the frequency range of 25 to 400 Hz. The rated operating current is 6 A at 120 V AC-15, 1.04 A at 690 V AC-15, 0.55 A at 125 V DC-13, and 0.1 A at 600 V DC-13. The rated insulation voltage is 690 V according to IEC 60947-5-1, 600 V according to UL, and 600 V according to CSA. The conventional thermal current is 10 A at an ambient temperature of 60 °C. The mechanical life is specified as 30 million switching cycles (Mcycles), indicating high durability in industrial applications.

Technology explained simply shows that the auxiliary switch block is designed for operation under normal environmental conditions. The protection rating IP20 according to IEC 60529 protects against finger contact and solid foreign objects, but is not waterproof. The coating TH corresponds to IEC 60068 and ensures a certain resistance to environmental influences. The permissible short-time current is 100 A at 60 °C for 1 second, 120 A for 500 ms, and 140 A for 100 ms, highlighting its capability to handle short-term overloads. The insulation resistance is greater than 10 MΩ, ensuring high electrical insulation.

Compatibility and accessories include use with various contactors from the TeSys and TeSys Deca series, such as LC1D1156F5, LC1D80A6P7, LC1D096ND, or LC1D1506F7. These contactors cover power ranges from 0.06 to 75 kW, enabling broad application in industrial environments. Combining them with these contactors allows expansion of control functions without additional components.

Mounting and installation is performed on the front side of the contactor. The terminals consist of ring cable lug terminals with an outer diameter of 8 mm. The tightening torque is 1.7 Nm, and mounting can be done using a flathead screwdriver (Ø 6, M3,5), a Phillips screwdriver (No. 2, M3,5), or a positioning screwdriver (No. 2, M3,5). The dimensions of the device are 48 mm height, 26 mm width, and 42 mm depth. The color is dark gray.

Operational advantages include high mechanical life, reliability at high switching cycles, and easy installation. The instantaneous switching function enables precise signal transmission. Compliance with international standards such as EN/IEC 60947-5-1, UL 60947-5-1, and CSA C22.2 No. 60947-5-1, as well as certifications like CB Scheme, UL, CSA, CCC, EAC, and UKCA, ensure safety and worldwide use. The operating temperature range is from -5 °C to 60 °C, and the storage temperature range is from -60 °C to 80 °C. The maximum operating altitude is 3,000 m above sea level.

The auxiliary switch block is designed for use in industrial installations where reliable and durable signal transmission is required. It is an integral part of control and protection systems in automation technology.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/583420
qrcode für Schneider Electric LADN116 auxiliary switch block 1S1Ö unzinc-plated