| Complementary |
| Irms rated making capacity | 140 A AC conforming to IEC 60947-5-1; 250 A DC conforming to IEC 60947-5-1 |
| Permissible short-time rating | 100 A 60 °C 1 s; 120 A 60 °C 500 ms; 140 A 60 °C 100 ms |
| Protection type | GG fuse 10 A |
| Mechanical durability | 30 Mcycles |
| Minimum switching current | 5 mA |
| Minimum switching voltage | 17 V |
| Non-overlap time | 1.5 ms on de-energisation no overlap between NC and NO contact; 1.5 ms on energisation no overlap between NC and NO contact |
| Insulation resistance | > 10 MOhm |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end; Screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 1…4 mm²rigid without cable end; Screw clamp terminals 2 cable(s) 1…4 mm²rigid without cable end |
| Tightening torque | 1.7 N.m - with screwdriver flat Ø 6 mm; 1.7 N.m - with screwdriver Philips No 2; 1.7 N.m - with screwdriver pozidriv No 2 |
| Height | 48 mm |
| Width | 13 mm |
| Depth | 35 mm |
| Net weight | 0.02 kg |
| Colour | Dark grey |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Environmental characteristic | Normal environment |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068 |
| Ambient air temperature for storage | -60…80 °C |
| Ambient air temperature for operation | -5…60 °C |
| Operating altitude | 3000 m |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys; TeSys Deca |
| Product name | TeSys Deca |
| Product or component type | Auxiliary contact block |
| Device short name | LADN |
| Range compatibility | TeSys Deca LC1D80/95 3P; TeSys Deca LC1D80 4P; TeSys Deca LC1D40008; TeSys Deca LC1D65008; TeSys F LC1F; TeSys Deca LC1D115 |
| Mounting location | Front |
| Pole contact composition | 1 NO |
| Contacts operation | Instantaneous |
| [Ue] rated operational voltage | 690 V AC 25...400 Hz |
| [Ie] rated operational current | 6 A at 120 V AC-15; 1.04 A at 690 V AC-15; 0.55 A at 125 V DC-13; 0.1 A at 600 V DC-13 |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-5-1; 600 V conforming to UL; 600 V conforming to CSA |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) |
| Standards | EN/IEC 60947-5-1; GB/T 14048.5; EN 50012; UL 60947-5-1; CSA C22.2 No 60947-5-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; UL; CSA; CCC; EAC; UKCA |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 2.700 cm |
| Package 1 Width | 4.200 cm |
| Package 1 Length | 5.000 cm |
| Package 1 Weight | 19.000 g |
| Unit Type of Package 2 | S01 |
| Number of Units in Package 2 | 84 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 15.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 1.778 kg |
The auxiliary switch block LADN10 from Schneider Electric belongs to the TeSys Deca series and serves as an additional component for contactors of the TeSys D and TeSys F series. It is designed as a front-mounting block and enables the integration of an additional normally open contact (1S) directly on the front side of the contactor. Installation is done by simply snapping it on, allowing for quick and secure mounting without additional tools. The block is designed for use in industrial applications where reliable signal transmission and status indication are required.
Applications
LADN10 is used in industrial control systems to monitor the operating status of a contactor or to transmit signals to external devices such as indicators, relays, or control units. It is particularly suitable for applications requiring an instantaneous normally open contact, for example, to provide feedback of the switched-on state to a control unit. Compatibility with various contactor types such as LC1D80/95 3P, LC1D40008, LC1D65008, LC1F, and LC1D115 makes it flexible for use in different system configurations.
Functions and Features in Detail
The auxiliary switch block features an instantaneous normally open contact that closes immediately upon actuation of the contactor. The contact arrangement is designed to prevent overlap between normally open and normally closed contacts, ensuring precise signal transmission. The minimum switching voltage is 17 V, and the minimum switching current is 5 mA, enabling use even with weak signals. The mechanical life expectancy is 30 million operations, indicating high operational reliability and durability.
Technology Explained Simply
The block is rated for an operating voltage of 690 V AC and can be operated at various voltage and current levels. The rated operating currents are 6 A at 120 V AC-15, 1.04 A at 690 V AC-15, 0.55 A at 125 V DC-13, and 0.1 A at 600 V DC-13. The rated insulation voltage is 690 V according to IEC 60947-5-1, and 600 V according to UL and CSA. The rated switching capacity is 140 A for AC and 250 A for DC, demonstrating the ability to safely switch under load. The permissible short-time performance is defined as 100 A (1 s), 120 A (500 ms), and 140 A (100 ms) at 60 °C, describing the thermal load capacity under transient conditions.
Compatibility and Accessories
The LADN10 is specifically designed for contactor series TeSys Deca LC1D80/95 3P, LC1D80 4P, LC1D40008, LC1D65008, LC1F, and LC1D115. It can be combined with the connection block GV2AF3 to simplify wiring between the contactor and auxiliary switch. The screw terminals allow connection with flexible and rigid cables in cross-sections from 1 to 4 mm², with tightening torques specified at 1.7 Nm for various screwdrivers (flat Ø 6, Phillips No. 2, Pozidriv No. 2).
Mounting and Installation
Mounting is done on the front side of the contactor by snapping it on, requiring no additional mounting aids. The screw terminals are designed for various cable types and ensure a secure and durable connection. The protection rating IP20 according to IEC 60529 protects against contact with fingers and larger objects, but is not suitable for outdoor use or humid environments. The operating temperature range is from -5 °C to 60 °C, and the storage temperature range is from -60 °C to 80 °C. The maximum operating altitude is 3,000 m above sea level.
Operational Advantages
The LADN10 offers high reliability with a mechanical life of 30 million operations and a robust design. The instantaneous switching function enables precise control signals, and compatibility with various contactor types increases flexibility in system planning. Certifications according to EN/IEC 60947-5-1, UL, CSA, CCC, EAC, and UKCA, as well as compliance with RoHS and REACH, ensure suitability for various markets and industries. Insulation resistances exceeding 10 MΩ ensure high electrical safety.