| Complementary |
| Irms rated making capacity | 140 A AC conforming to IEC 60947-5-1; 250 A DC conforming to IEC 60947-5-1 |
| Permissible short-time rating | 100 A 1 s; 120 A 500 ms; 140 A 100 ms |
| Protection type | GG fuse 10 A |
| Mechanical durability | 30 Mcycles |
| Minimum switching current | 5 mA |
| Minimum switching voltage | 17 V |
| Overlap time | 1.5 ms |
| Non-overlap time | 1.5 ms on de-energisation no overlap between NC and NO contact; 1.5 ms on energisation no overlap between NC and NO contact |
| Insulation resistance | > 10 MOhm |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end; Screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 1…4 mm²rigid without cable end; Screw clamp terminals 2 cable(s) 1…4 mm²rigid without cable end |
| Tightening torque | 1.7 N.m - with screwdriver flat Ø 6 mm; 1.7 N.m - with screwdriver Philips No 2; 1.7 N.m - with screwdriver pozidriv No 2 |
| Height | 48 mm |
| Width | 44 mm |
| Depth | 42 mm |
| Net weight | 0.05 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Environmental characteristic | Normal environment |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068 |
| Ambient air temperature for storage | -60…80 °C |
| Ambient air temperature for operation | -5…60 °C |
| Operating altitude | 3000 m |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys; TeSys Deca |
| Product name | TeSys Deca |
| Product or component type | Auxiliary contact block |
| Range compatibility | TeSys D CAD; TeSys D LC1D; TeSys F LC1F; TeSys F CR1F; TeSys Deca CAD; TeSys Deca LC1D |
| Mounting location | Front |
| Pole contact composition | 2 NO + 2 NC |
| Contacts operation | Make before break 1 NO + 1 NC; Instantaneous 1 NO + 1 NC |
| [Ue] rated operational voltage | 690 V AC 25...400 Hz |
| [Ie] rated operational current | 6 A at 120 V AC-15; 1.04 A at 690 V AC-15; 0.55 A at 125 V DC-13; 0.1 A at 600 V DC-13 |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-5-1; 600 V conforming to UL; 600 V conforming to CSA |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) |
| Standards | EN/IEC 60947-5-1; UL 60947-5-1; CSA C22.2 No 60947-5-1; GB/T 14048.5 |
| Product certifications | CB; UL; CSA; EAC; CE; UKCA |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 4.800 cm |
| Package 1 Width | 4.200 cm |
| Package 1 Length | 5.200 cm |
| Package 1 Weight | 62.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 160 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 10.422 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 1280 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 92.000 kg |
The LADC22 is an auxiliary switch block of the TeSys Deca series from Schneider Electric, specifically designed as an add-on module for contactors of the TeSys D, TeSys F, TeSys Deca CAD, and TeSys Deca LC1D series. It serves to extend control functions of main contacts in industrial installations by providing additional switching contacts mounted directly on the front side of the contactor. Installation is done by simply snapping it on, enabling quick and tool-free assembly.
Applications
This auxiliary switch block is intended for applications in industrial automation where additional control or signaling functions are required. It is particularly suitable for installations where the reliability and safety of switching operations are critical. The certified normally-closed mirror contacts allow use in safety applications, where the contact function is certified as a safety-relevant component. The operating temperature range of -5 to 60 °C and operating altitude up to 3,000 m above sea level make it suitable for a wide range of environments, including industrial settings with normal operating conditions.
Functions and Features in Detail
The LADC22 features a contact configuration of 2 normally-closed and 2 normally-open contacts (2S+2Oe). One normally-closed and one normally-open contact are designed for uninterrupted switching, enabling an overlap time of 1.5 ms. The remaining contacts switch without delay. The contacts are designed as instantaneous contacts, meaning they react directly to the control signal as soon as the main contact is actuated. The minimum switching voltage is 17 V, and the minimum switching current is 5 mA, ensuring reliable switching even under low-load conditions.
Technology Explained Simply
The rated insulation voltage is 690 V AC, complying with IEC 60947-5-1, and 600 V DC, meeting UL and CSA requirements. The rated operational voltage is 690 V AC in the frequency range of 25 to 400 Hz. The rated operational current is 6 A at 120 V AC-15, 1.04 A at 690 V AC-15, 0.55 A at 125 V DC-13, and 0.1 A at 600 V DC-13. The conventional thermal current in free air is 10 A at an ambient temperature of 60 °C. The permissible short-time current is 100 A for 1 second, 120 A for 500 ms, and 140 A for 100 ms. The mechanical life is 30 million switching cycles, ensuring high operational reliability and longevity. The insulation resistance is greater than 10 MΩ, providing high electrical insulation and safety.
Compatibility and Accessories
The LADC22 is compatible with contactor series TeSys D CAD, TeSys D LC1D, TeSys F LC1F, TeSys F CR1F, TeSys Deca CAD, and TeSys Deca LC1D. It can be combined with other auxiliary contactors from the TeSys series, such as models CAD32FD, CAD50BL, CAD50P7TQ, CAD50BD, CAD50U7, CAD50R7, CAD50E7, CAD50FD, CAD32B7, CAD32MD, CAD32G7, CAD32X7, CAD50ED, CAD50P7, CAD50B7, CAD50L7, CAD32GD, CAD32JL, CAD32L7, and CAD32UD. These models offer different contact configurations, voltages, and currents, allowing flexible adaptation to specific requirements.
Mounting and Installation
Mounting is done on the front side of the contactor by simply snapping it on, without requiring additional tools. Connections are made via screw terminals designed for flexible and rigid conductors with cross-sections from 1 to 4 mm². The terminals are suitable for cables with and without wire end ferrules. The required tightening torque is 1.7 Nm, using screwdrivers with flat Ø 6, Phillips No. 2, or Pozidriv No. 2. Dimensions are 48 mm height, 44 mm width, and 42 mm depth. The protection rating IP20 according to IEC 60529 protects against finger contact and solid foreign objects, but not against water or dust.
Operational Advantages
The LADC22 offers high reliability through certified mirror contacts and a long service life of 30 million switching cycles. The simple front-side mounting reduces installation time and enables quick maintenance. The high insulation resistance values and robust construction ensure safe and stable operation in industrial environments. Certifications according to EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No. 60947-5-1, and GB/T 14048.5, along with product certifications CB, UL, CSA, EAC, CE, and UKCA, guarantee compliance with international standards. Conformity with RoHS and REACH ensures environmentally compatible manufacturing.
Protection Rating and Environmental Conditions
The protection rating IP20 protects against finger contact and solid foreign objects. The operating temperature range is from -5 to 60 °C, and the storage temperature range is from -60 to 80 °C. The operating altitude is up to 3,000 m above sea level. The coating corresponds to category TH according to IEC 60068, ensuring high resistance to environmental influences. The permissible short-time current and rated switching capacity of 140 A AC and 250 A DC ensure safe switching even under high loads.
Certifications and Standards
The LADC22 complies with standards EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No. 60947-5-1, and GB/T 14048.5. Product certifications include CB, UL, CSA, EAC, CE, and UKCA. Conformity with RoHS and REACH ensures environmentally compatible manufacturing. Certification as a normally-closed certified mirror contact enables use in safety applications.
Compatibility and Application
The LADC22 is specifically developed for contactor series TeSys D, TeSys F, and TeSys Deca. It can be combined with various auxiliary contactors to extend control functions. Compatibility with models CAD32FD, CAD50BL, CAD50P7TQ, CAD50BD, CAD50U7, CAD50R7, CAD50E7, CAD50FD, CAD32B7, CAD32MD, CAD32G7, CAD32X7, CAD50ED, CAD50P7, CAD50B7, CAD50L7, CAD32GD, CAD32JL, CAD32L7, and CAD32UD allows flexible adaptation to different requirements. Front-side mounting and easy installation make it a practical solution for industrial applications.