| Complementary |
| Irms rated making capacity | 140 A AC conforming to IEC 60947-5-1; 250 A DC conforming to IEC 60947-5-1 |
| Permissible short-time rating | 100 A 1 s; 120 A 500 ms; 140 A 100 ms |
| Protection type | GG fuse 10 A |
| Mechanical durability | 30 Mcycles |
| Minimum switching current | 5 mA |
| Minimum switching voltage | 17 V |
| Overlap time | 1.5 ms |
| Non-overlap time | 1.5 ms on de-energisation no overlap between NC and NO contact; 1.5 ms on energisation no overlap between NC and NO contact |
| Insulation resistance | > 10 MOhm |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end; Screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 1…4 mm²rigid without cable end; Screw clamp terminals 2 cable(s) 1…4 mm²rigid without cable end |
| Tightening torque | 1.7 N.m - with screwdriver flat Ø 6 mm; 1.7 N.m - with screwdriver Philips No 2; 1.7 N.m - with screwdriver pozidriv No 2 |
| Height | 48 mm |
| Width | 44 mm |
| Depth | 42 mm |
| Net weight | 0.05 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Environmental characteristic | Normal environment |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068 |
| Ambient air temperature for storage | -60…80 °C |
| Ambient air temperature for operation | -5…60 °C |
| Operating altitude | 3000 m |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys; TeSys Deca |
| Product name | TeSys Deca |
| Product or component type | Auxiliary contact block |
| Range compatibility | TeSys D CAD; TeSys D LC1D; TeSys F LC1F; TeSys F CR1F; TeSys Deca CAD; TeSys Deca LC1D |
| Mounting location | Front |
| Pole contact composition | 2 NO + 2 NC |
| Contacts operation | Make before break 1 NO + 1 NC; Instantaneous 1 NO + 1 NC |
| [Ue] rated operational voltage | 690 V AC 25...400 Hz |
| [Ie] rated operational current | 6 A at 120 V AC-15; 1.04 A at 690 V AC-15; 0.55 A at 125 V DC-13; 0.1 A at 600 V DC-13 |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-5-1; 600 V conforming to UL; 600 V conforming to CSA |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) |
| Standards | EN/IEC 60947-5-1; UL 60947-5-1; CSA C22.2 No 60947-5-1; GB/T 14048.5 |
| Product certifications | CB; UL; CSA; EAC; CE; UKCA |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 4.800 cm |
| Package 1 Width | 4.200 cm |
| Package 1 Length | 5.200 cm |
| Package 1 Weight | 62.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 160 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 10.422 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 1280 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 92.000 kg |
Auxiliary switch block for TeSys D and TeSys F contactors. The front mounting block offers 2 NC+2 NO instantaneous contacts with a rated voltage of up to 10A 690V AC, of which 1 NC+1 NO with overlap time. LADC22 is an auxiliary switch block for TeSys D and TeSys F contactors. It offers 2 NC+2 NO instantaneous contacts with a rated voltage of up to 10A 690V AC, of which 1 NC+1 NO with overlap time. Thanks to its NO certified mirror contacts, it can be used in safety applications. Easy to mount on the front by clipping on, it offers high reliability and durability. It is certified according to several standards (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach).