Standard contactors 0.06 -75 kW In addition to an attractive and functional design, the TeSys D contactors offer quick and easy installation with a narrow width of 45 or 55 mm. They meet international standards. The power sizes 40 to 65 A are equipped with EverLink terminals. These are patented and ensure a reliable and permanent connection.
SM 231 (231-1BD53)
Technical Data
Order no.: 231-1BD53
Type: SM 231
General Information:
- Note: -
- Features: 4x AI, 16 Bit, Voltage, Current, Resistance thermometer, Thermocouple, Parameterizable
Current Consumption/Power Loss:
- Current consumption from backplane bus: 280 mA
- Power loss: 1.4 W
Technical Data Analog Inputs:
- Number of inputs: 4
- Cable length, shielded: 200 m
- Rated load voltage: -
- Current consumption from load voltage L+ (without load): -
- Voltage inputs: yes
- Min. input resistance (voltage range): 20 MOhm
- Input voltage ranges: -50 mV ... +50 mV, -400 mV ... +400 mV, -4 V ... +4 V, -10 V ... +10 V
- Operational limit of voltage ranges: +/-0.3% ... +/-0.6%
- Operational limit of voltage ranges with SFU: -
- Basic error limit voltage ranges: +/-0.2% ... +/-0.4%
- Basic error limit voltage ranges with SFU: -
- Destruction limit voltage: max. 15 V
- Current inputs: yes
- Max. input resistance (current range): 85 Ohm
- Input current ranges: -20 mA ... +20 mA, 0 mA ... +20 mA, +4 mA ... +20 mA
- Operational limit of current ranges: +/-0.3% ... +/-0.8%
- Operational limit of current ranges with SFU: -
- Basic error limit current ranges: +/-0.2% ... +/-0.5%
- Radical error limit current ranges with SFU: -
- Destruction limit current inputs (electrical current): max. 30 mA
- Destruction limit current inputs (voltage): -
- Resistance inputs: yes
- Resistance ranges: 0 ... 60 Ohm, 0 ... 600 Ohm, 0 ... 3000 Ohm, 0 ... 6000 Ohm
- Operational limit of resistor ranges: +/-0.4% ... +/-0.8%
- Operational limit of resistor ranges with SFU: -
- Basic error limit: +/-0.2% ... +/-0.4%
- Basic error limit with SFU: -
- Destruction limit resistance inputs: max. 15 V
- Resistance thermometer inputs: yes
- Resistance thermometer ranges